VRF BACnet IP gateway · BACnet points list
Lennox VRF BACnet Gateway V0CTRL95P-3 BACnet points list
Updated 28 October 2026
The V0CTRL95P-3 connects Lennox VRF systems to a BMS over BACnet IP, with four RS-485 buses to the VRF units and an Ethernet port. Each indoor and outdoor unit appears as its own BACnet device whose device ID encodes the bus, unit type and unit address; inside each device the object instances are fixed, so one indoor template and one outdoor template cover the site. Indoor units take on/off, mode, fan speed and setpoint commands; outdoor units are mostly monitoring plus an emergency stop.
This page lists 42 BACnet objects for the Lennox VRF BACnet Gateway V0CTRL95P-3 — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lennox’s own free documentation, linked below.
- Manufacturer
- Lennox
- Model
- VRF BACnet Gateway V0CTRL95P-3
- Equipment
- VRF BACnet IP gateway
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 42 (13 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- V0CTRL95P-3, V0CTRL95P, Lennox VRF BACnet gateway, VRB BACnet gateway, VPB BACnet gateway, 507951
Instance calculator. This list prints one unit; the other units follow a formula. Lennox VRF BACnet gateway V0CTRL95P-3 instance calculator →
Reference only, provided as-is: verify against Lennox’s current documentation and the live device before use. Not official Lennox information. Terms of use.
BMS integration notes: Lennox VRF BACnet Gateway V0CTRL95P-3
Connect the VRF buses to the gateway's four RS-485 ports, set the gateway's IP settings from a web browser, then discover the per-unit BACnet devices. Map each indoor unit's on/off, mode, fan speed and setpoint commands plus room temperature and alarm; outdoor unit devices are for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | On/Off Setting | Start/stop indoor unit | Write |
| MV 1 | Mode Setting | Mode command (3 = cool, 4 = heat, 5 = auto) | Write |
| AV 1 | Temperature Setting | Setpoint command | Write |
| MV 2 | Fan Speed Setting | Fan speed command (8 = auto) | Write |
| AI 1 | Room Temperature | Indoor unit room temperature | Read |
| BI 2 | Alarm Indication | Indoor unit has an error code | Read |
Enable & remote start
No enable point is documented. Wired and wireless controller locks (BV 5, BV 4) and mode/fan locks (MV 3, MV 5) restrict local changes.
Network setup
- Factory IP address 192.168.1.8; configure it from a web browser on a PC plugged into the gateway's Ethernet port, using the default admin login printed in the guide.
- Device ID per unit = bus (0-3) + type (0 indoor, 1 outdoor) + 2-digit unit address, e.g. 0001 or 1105.
- Wiring details are in the LVM and BACnet Gateway installation manual (507897).
- Power is 24 VAC; the gateway is DIN-rail mounted.
Watch out for
- Instances are not unique across unit types: the same AI or BI number means different things on indoor and outdoor devices.
- The setpoint (AV 1) only applies in cool, heat and dry; auto mode uses AV 2 and AV 3.
- Outdoor BV 1 is an emergency stop for the outdoor unit, not a normal on/off.
- The indoor points list has no separate run-status object; read back BV 1 and MV 1.
Lennox VRF BACnet Gateway V0CTRL95P-3 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 1 | On/Off Setting | [Indoor unit] On/off command | Write | 0=Off; 1=On | |
| MVmin | 1 | Mode Setting | [Indoor unit] Mode command | Write | 1=Off; 2=Fan; 3=Cooling; 4=Heating; 5=Auto; 6=Dry | |
| MVmin | 2 | Fan Speed Setting | [Indoor unit] Fan speed command | Write | 1-2=Low; 3-4=Medium; 5-7=High; 8=Auto; 9=Off | |
| AVmin | 1 | Temperature Setting | [Indoor unit] Setpoint for cool, heat and dry, 62-86 °F | °F/°C | Write | |
| AV | 2 | Dual Point (Cooling) Setting | [Indoor unit] Auto mode cooling setpoint | °F/°C | Write | |
| AV | 3 | Dual Point (Heating) Setting | [Indoor unit] Auto mode heating setpoint | °F/°C | Write | |
| AV | 4 | Cool Temperature Limit Setting | [Indoor unit] Lowest allowed cooling/auto/dry setpoint | °F/°C | Write | |
| AV | 5 | Heat Temperature Limit Setting | [Indoor unit] Highest allowed heating/auto heating setpoint | °F/°C | Write | |
| MV | 3 | Mode Limit Setting | [Indoor unit] Mode lock | Write | 0=Unlocked; 1=Locked in cooling; 2=Locked in heating | |
| MV | 5 | Fan Lock/Unlock Setting | [Indoor unit] Fan speed lock | Write | 1-2=Locked low; 3-4=Locked medium; 5-7=Locked high; 8=Unlocked | |
| BV | 4 | Remote Control Lock Setting | [Indoor unit] Wireless remote lock | Write | 0=Unlocked; 1=Wireless control locked | |
| BV | 5 | Controller Lock Setting | [Indoor unit] Wired controller lock | Write | 0=Unlocked; 1=Wired control locked | |
| AImin | 1 | Room Temperature | [Indoor unit] Room temperature sensor value | °F/°C | Read | |
| BImin | 2 | Alarm Indication | [Indoor unit] Error code present | Read | 0=No malfunction code; 1=Malfunction code | |
| AI | 9 | EXV Opening | [Indoor unit] Electronic expansion valve opening | Read | ||
| AI | 10 | Software Version | [Indoor unit] Software version | Read | ||
| AI | 11 | Indoor type | [Indoor unit] Indoor unit series | Read | 1=V33B four-way cassette; 2=VWMB wall mounted; 3=VMDB medium static duct; 5=VVCB vertical air handler; 6=VHIB high static duct; 7=V22B compact four-way cassette; 8=VCFB ceiling/floor; 11=VOSB outside air duct; 14=VOWA one-way cassette; 21=AHU control kit | |
| AI | 12 | Indoor Capacity | [Indoor unit] Indoor unit capacity code | Read | 8=7k; 10=9k; 12=12k; 17=15k; 20=18k; 25=24k; 32=30k; 40=36k; 50=48k; 60=54k; 65=60k; 80=72k; 100=96k Btu/h | |
| MI | 1 | Mode Status | [Outdoor unit] Operating mode | Read | 1=Off; 2=Reserved; 3=Cooling; 4=Heating; 5=Cooling test; 6=Mix cooling; 7=Mix heating; 8=Heating test | |
| BI | 1 | On/Off Status | [Outdoor unit] Run status | Read | 0=Off; 1=On | |
| AI | 1 | Ambient Temperature | [Outdoor unit] Outdoor ambient temperature | °F/°C | Read | |
| AI | 2 | Compressor 1 Freq. | [Outdoor unit] Main compressor frequency | Hz | Read | |
| AI | 3 | Compressor 2 Freq. | [Outdoor unit] Sub compressor frequency | Hz | Read | |
| AI | 4 | Compressor 1 Discharge Temp. | [Outdoor unit] Main compressor discharge temperature | °F/°C | Read | |
| AI | 5 | Compressor 2 Discharge Temp. | [Outdoor unit] Sub compressor discharge temperature | °F/°C | Read | |
| AI | 6 | High Pressure | [Outdoor unit] Discharge pressure | psi | Read | |
| AI | 7 | Low Pressure | [Outdoor unit] Suction pressure | psi | Read | |
| AI | 9 | Fan 1 Speed | [Outdoor unit] Fan 1 speed step (not rpm) | Read | ||
| AI | 10 | Fan 2 Speed | [Outdoor unit] Fan 2 speed step (not rpm) | Read | ||
| BI | 2 | Alarm Indication | [Outdoor unit] Error code present | Read | 0=No malfunction code; 1=Malfunction code | |
| AI | 11 | T3 | [Outdoor unit] Left condenser temperature | °F/°C | Read | |
| AI | 12 | T3B | [Outdoor unit] Right condenser temperature | °F/°C | Read | |
| BI | 4 | SV2 | [Outdoor unit] Solenoid valve SV2 status | Read | 0=Off; 1=On | |
| BI | 6 | SV4 | [Outdoor unit] Solenoid valve SV4 status | Read | 0=Off; 1=On | |
| BI | 11 | ST1 | [Outdoor unit] Reversing valve ST1 status | Read | 0=Not energized; 1=Energized | |
| BI | 12 | ST2 | [Outdoor unit] Reversing valve ST2 status | Read | 0=Not energized; 1=Energized | |
| AI | 13 | Version | [Outdoor unit] Main PCB software version | Read | ||
| AI | 14 | Outdoor type | [Outdoor unit] Outdoor unit type | Read | 0=Mini VRF; 1=VRF | |
| AI | 15 | Outdoor horses | [Outdoor unit] Outdoor unit capacity | ton | Read | |
| AI | 16 | Exv1 opening | [Outdoor unit] EEV A opening | pulse | Read | |
| AI | 17 | Exv2 opening | [Outdoor unit] EEV B opening | pulse | Read | |
| BV | 1 | Emergency Stop | [Outdoor unit] Emergency stop command | Write | 0=None; 1=Emergency stop |
No points match these filters.
Object ID lookup: Lennox VRF BACnet Gateway V0CTRL95P-3 point IDs by name
BV1On/Off SettingMV1Mode SettingMV2Fan Speed SettingAV1Temperature SettingAV2Dual Point (Cooling) SettingAV3Dual Point (Heating) SettingAV4Cool Temperature Limit SettingAV5Heat Temperature Limit SettingMV3Mode Limit SettingMV5Fan Lock/Unlock SettingBV4Remote Control Lock SettingBV5Controller Lock SettingAI1Room TemperatureBI2Alarm IndicationAI9EXV OpeningAI10Software VersionAI11Indoor typeAI12Indoor CapacityMI1Mode StatusBI1On/Off StatusAI1Ambient TemperatureAI2Compressor 1 Freq.AI3Compressor 2 Freq.AI4Compressor 1 Discharge Temp.AI5Compressor 2 Discharge Temp.AI6High PressureAI7Low PressureAI9Fan 1 SpeedAI10Fan 2 SpeedBI2Alarm IndicationAI11T3AI12T3BBI4SV2BI6SV4BI11ST1BI12ST2AI13VersionAI14Outdoor typeAI15Outdoor horsesAI16Exv1 openingAI17Exv2 openingBV1Emergency Stop
Integration notes
- Device ID = 4 digits: bus (port) 0-3, unit type (0 = indoor, 1 = outdoor), unit address (indoor 00-63, outdoor 00-31). Example from the guide: 0001 = bus 0, indoor unit 01.
- The list holds two object sets: indoor unit devices (first 18 rows) and outdoor unit devices (last 24 rows). Instances repeat between the two (e.g. AI 1 is room temperature on an indoor unit and ambient temperature on an outdoor unit).
- The guide gives setpoint ranges as 62-86 °F (17-30 °C) and does not say which unit the gateway reports.
- Fan speed and fan lock values pair several codes per speed (1-2 low, 3-4 medium, 5-7 high).
- The gateway is rated for up to 320 VRB/VPB systems, 960 outdoor units and 2560 indoor units; the guide's Appendix A with the details is not part of this document.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VRF BACnet Gateway V0CTRL95P-3 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Lennox VRF BACnet Gateway V0CTRL95P-3
How many BACnet points does the Lennox VRF BACnet Gateway V0CTRL95P-3 have?
This list has 42 BACnet objects: 21 analog inputs, 5 analog values, 7 binary inputs, 4 binary values, 1 multi-state input, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Lennox VRF BACnet Gateway V0CTRL95P-3 BACnet points are writable?
13 of the 42 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Lennox VRF BACnet Gateway V0CTRL95P-3 BACnet documentation?
The source is VRF BACnet Gateway V0CTRL95P-3, Lennox VRF VRB & VPB Systems - User and Application Guide (507951-02), revision 12/2022, published free by Lennox at https://www.lennox.com/dA/020b57558a/507951-02.pdf.
What are the minimum BACnet points to integrate the Lennox VRF BACnet Gateway V0CTRL95P-3?
Start with BV 1 On/Off Setting (Start/stop indoor unit); MV 1 Mode Setting (Mode command (3 = cool, 4 = heat, 5 = auto)); AV 1 Temperature Setting (Setpoint command); MV 2 Fan Speed Setting (Fan speed command (8 = auto)); AI 1 Room Temperature (Indoor unit room temperature); BI 2 Alarm Indication (Indoor unit has an error code).
How do I enable BMS control of the Lennox VRF BACnet Gateway V0CTRL95P-3?
No enable point is documented. Wired and wireless controller locks (BV 5, BV 4) and mode/fan locks (MV 3, MV 5) restrict local changes.
How do I check these points on the real VRF BACnet Gateway V0CTRL95P-3?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Lennox BACnet points lists
- Rooftop unit controller
Lennox CORE LITE Unit Controller
Lennox rooftop units built with the CORE LITE Unit Controller, fitted with the add-on BACnet MS/TP plug-in module.
Also known as: CORE Lite, Lennox CORE Lite, CORE LITE BACnet, Lennox_M4, 508727 - Rooftop unit controller
Lennox CORE Unit Controller
Lennox commercial rooftop units built with the CORE Unit Controller.
Also known as: Lennox CORE, CORE controller, CORE RTU controller, M4 unit controller, A55, Lennox_CORE, 508112 - Rooftop unit controller BACnet module
Lennox IMC BACnet Module
Lennox rooftop units with the IMC (M1-7, v5.02 or later) unit controller and the IMC BACnet module.
Also known as: Lennox IMC BACnet, IMC M1-7, M1-7 BACnet, 0624-L5, L Series IMC BACnet - Rooftop / split unit controller (field BACnet module)
Lennox KMC BACnet Module 16X70 / 16X71 / 16X72 / 17A08 (KMC BAC-8304) for rooftop and split units
Lennox (and Allied Commercial) units fitted with the KMC BACnet module kit 16X70, 16X71, 16X72 or 17A08: a KMC BAC-8304 that drives the unit's thermostat terminals with a 2-heat / 2-cool sequence.
Also known as: 16X70, 16X71, 16X72, 17A08, BAC-8304, KMC BAC-8304-56, Lennox KMC BACnet module, Allied Commercial BACnet module, Allied Z-Series BACnet, 905-019-62E, 103902-01 - Rooftop unit controller BACnet module
Lennox Prodigy M3 BACnet Module
Lennox commercial rooftop units that use the Prodigy M3 unit controller.
Also known as: M3 BACnet Module, BM2, Prodigy M3, Lennox_M3, Prodigy 2.0 BACnet, 1404-L4, Prodigy M2, M2 BACnet Module, 0926-L11
Source: VRF BACnet Gateway V0CTRL95P-3, Lennox VRF VRB & VPB Systems - User and Application Guide · 507951-02 · rev. 12/2022. Object names, instances and units are reproduced as published; descriptions are our own.