 "manufacturer": "Intesis",
 "manufacturer_slug": "intesis",
 "model": "INBACTOS001R100 (Toshiba gateway)",
 "model_slug": "inbactos001r100",
 "aliases": [
  "Toshiba BACnet gateway",
  "Toshiba VRF BACnet",
  "Toshiba BACnet points list",
  "TO-RC-BAC-1L",
  "Toshiba VRF BACnet MS/TP"
 ],
 "equipment_type": "Air conditioner BACnet gateway (1 indoor unit)",
 "applies_to": "Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.",
 "summary": "A one-unit Intesis BACnet MS/TP interface on a Toshiba indoor unit's A/B remote-controller bus. It exposes 42 fixed objects: the standard on/off, mode, setpoint, fan and louvre set, errors, filter, occupancy logic, mode-restriction status and per-function remote-controller lock objects.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": 246000,
 "access_inferred": false,
 "notes": [
  "AirDirectionUD_command state 2 is printed as Swing while the status object shows 2=Up; check on site.",
  "Units shown as °C follow the °C/°F DIP switch.",
  "ErrorCodeM state texts are the Toshiba error codes listed in the manual.",
  "An older 2014 manual (INBACTOS001R000, BACnet IP/MSTP) exists with 29 objects; this file follows the R100 model."
 ],
 "source": {
  "title": "Intesis BACnet MSTP - Toshiba AC User Manual (INBACTOS001R100)",
  "doc_number": "TO-RC-BAC-1L (legacy code)",
  "revision_date": "9/2024 v1.2",
  "url": "https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inbactos001r100.pdf"
 },
 "integration": {
  "summary": "Connect the gateway to the indoor unit (A/B remote-controller bus, no polarity), set the BACnet network on its DIP switches, then write the _command objects (on/off, mode, setpoint, fan) and read back the matching _status objects. One gateway serves one indoor unit (or one remote-controller group), so give each gateway its own MAC address and device instance.",
  "minimum_points": [
   {
    "ref": "BO 0",
    "name": "OnOff_command",
    "why": "Start/stop the indoor unit"
   },
   {
    "ref": "MO 0",
    "name": "Mode_command",
    "why": "Heat/cool/fan/dry/auto selection"
   },
   {
    "ref": "AO 0",
    "name": "SetPoint_command",
    "why": "Temperature setpoint from the BMS"
   },
   {
    "ref": "MO 1",
    "name": "FanSpeed_command",
    "why": "Fan speed selection"
   },
   {
    "ref": "BI 0",
    "name": "OnOff_status",
    "why": "Confirm the unit is running"
   },
   {
    "ref": "AI 0",
    "name": "SetPoint_status",
    "why": "Setpoint the unit is really using"
   },
   {
    "ref": "AI 1",
    "name": "RoomTemperature_status",
    "why": "Room/return temperature for trending"
   },
   {
    "ref": "BI 1",
    "name": "ErrorActive",
    "why": "Unit alarm"
   },
   {
    "ref": "AI 2",
    "name": "ErrorCode",
    "why": "Which fault is active"
   }
  ],
  "enable": "No enable point or BMS/local switch is documented; the gateway accepts BACnet commands as soon as it is communicating with the unit. A wired remote controller can still be used in parallel; the LockRemoteControl..._command objects (BO 6-11) lock it per function.",
  "heartbeat": null,
  "remote_sensors": "Write the BMS room temperature to AO 1 RoomTemperature_command and keep using AO 0 SetPoint_command for the user setpoint. The gateway then runs its Virtual Temperature function: it offsets the setpoint it sends to the unit by the difference between the BMS temperature and the unit's own return temperature, so AI 0 SetPoint_status can differ from what you wrote. Until a first value is written, AO 1 shows Reliability = UNRELIABLE_OTHER and the function stays off.",
  "setup": [
   "BACnet MS/TP only; the EIA-485 port has DIP switches for the 120-ohm terminator and bus biasing.",
   "MS/TP MAC address 0-127 is set on DIP switches; baud rate is DIP-selectable (9600-115200) with autobaud as the default, which matches the baud rate of another MS/TP device running a fixed rate.",
   "Default device instance 246000. In automatic mode the instance is 246000 + the MAC address; writing Object_Identifier from BACnet switches to manual mode until a factory reset."
  ],
  "gotchas": [
   "Every function has a separate _command (AO/BO/MO, commandable) and _status (AI/BI/MI) object; write the command, read the status.",
   "Temperatures follow the Celsius/Fahrenheit DIP switch; the BACnet Units property changes with it.",
   "The Occupancy MV and its four AVs drive built-in logic that sets mode, setpoint and on/off; leave Occupancy at 3 (Disabled) unless you use it, and any manual on/off, mode or setpoint change cancels it."
  ]
 },
 "points": [
  {
   "type": "BI",
   "instance": 0,
   "name": "OnOff_status",
   "description": "Unit on/off status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "OnOff_command",
   "description": "Start/stop command for the indoor unit",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "MI",
   "instance": 0,
   "name": "Mode_status",
   "description": "Operating mode currently active",
   "units": "",
   "access": "R",
   "states": "1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool"
  },
  {
   "type": "MO",
   "instance": 0,
   "name": "Mode_command",
   "description": "Operating mode command",
   "units": "",
   "access": "C",
   "states": "1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto"
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "SetPoint_status",
   "description": "Setpoint the indoor unit is actually using",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "SetPoint_command",
   "description": "Temperature setpoint command from the BMS",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 1,
   "name": "FanSpeed_status",
   "description": "Current fan speed",
   "units": "",
   "access": "R",
   "states": "1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5"
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "FanSpeed_command",
   "description": "Fan speed command",
   "units": "",
   "access": "C",
   "states": "1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5"
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "AirDirectionUD_status",
   "description": "Vertical (up/down) vane position",
   "units": "",
   "access": "R",
   "states": "1=Stop, 2=Up, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Down, 7=Swing"
  },
  {
   "type": "MO",
   "instance": 2,
   "name": "AirDirectionUD_command",
   "description": "Vertical (up/down) vane command",
   "units": "",
   "access": "C",
   "states": "1=Stop, 2=Swing, 3=Mid-1, 4=Mid-2, 5=Mid-3, 6=Down, 7=Swing"
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "RoomTemperature_status",
   "description": "Room temperature used by the indoor unit",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "RoomTemperature_command",
   "description": "Room temperature written by the BMS (external sensor)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "ErrorCode",
   "description": "Active error code as a number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 4,
   "name": "ErrorCodeM",
   "description": "Active error code as a multistate value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "ErrorActive",
   "description": "An error is active on the indoor unit",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Error"
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "ErrorAddress",
   "description": "Address of the indoor unit reporting the error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "OnTimeCounter",
   "description": "Accumulated run time of the unit",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "FilterSign",
   "description": "Filter-clean indication",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "FilterReset",
   "description": "Resets the filter sign",
   "units": "",
   "access": "C",
   "states": "0=Normal, 1=Reset"
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "Occupancy",
   "description": "Occupancy input for the built-in occupancy logic",
   "units": "",
   "access": "W",
   "states": "1=Occupied, 2=Unoccupied, 3=Disabled"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "OccupiedCoolSetPoint",
   "description": "Cooling setpoint used while occupied",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "OccupiedHeatSetPoint",
   "description": "Heating setpoint used while occupied",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "UnoccupiedCoolSetPoint",
   "description": "Cooling setpoint used while unoccupied",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "UnoccupiedHeatSetPoint",
   "description": "Heating setpoint used while unoccupied",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "OccupancyContinuousCheck",
   "description": "Re-run occupancy logic on every temperature change",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "UnoccupiedDeadbandAction",
   "description": "Off or stay on when unoccupied inside the deadband",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=CurrentMode"
  },
  {
   "type": "MI",
   "instance": 7,
   "name": "RuntimeModeRestriction",
   "description": "Operating mode restriction in force",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Auto, 3=Heat, 4=Heat, Auto, 5=Cool, Dry, 6=Cool, Dry, Auto, 7=Cool, Dry, Heat, Auto"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "LockRemoteControlAll_status",
   "description": "Remote controller lock of all functions (status)",
   "units": "",
   "access": "R",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "LockRemoteControlAll_command",
   "description": "Remote controller lock of all functions (command)",
   "units": "",
   "access": "C",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "LockRemoteControlOnOff_status",
   "description": "Remote controller lock of on/off (status)",
   "units": "",
   "access": "R",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BO",
   "instance": 7,
   "name": "LockRemoteControlOnOff_command",
   "description": "Remote controller lock of on/off (command)",
   "units": "",
   "access": "C",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "LockRemoteControlMode_status",
   "description": "Remote controller lock of mode (status)",
   "units": "",
   "access": "R",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BO",
   "instance": 8,
   "name": "LockRemoteControlMode_command",
   "description": "Remote controller lock of mode (command)",
   "units": "",
   "access": "C",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "LockRemoteControlSetPoint_status",
   "description": "Remote controller lock of setpoint (status)",
   "units": "",
   "access": "R",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BO",
   "instance": 9,
   "name": "LockRemoteControlSetPoint_command",
   "description": "Remote controller lock of setpoint (command)",
   "units": "",
   "access": "C",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "LockRemoteControlFanSpeed_status",
   "description": "Remote controller lock of fan speed (status)",
   "units": "",
   "access": "R",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BO",
   "instance": 10,
   "name": "LockRemoteControlFanSpeed_command",
   "description": "Remote controller lock of fan speed (command)",
   "units": "",
   "access": "C",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "LockRemoteControlVanesUD_status",
   "description": "Remote controller lock of up/down vanes (status)",
   "units": "",
   "access": "R",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BO",
   "instance": 11,
   "name": "LockRemoteControlVanesUD_command",
   "description": "Remote controller lock of up/down vanes (command)",
   "units": "",
   "access": "C",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "DIP_SW_S1_status",
   "description": "DIP switch SW1 position (decimal), read at boot",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "DIP_SW_S2_status",
   "description": "DIP switch SW2 position (decimal), read at boot",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "SerialNumber",
   "description": "Gateway serial number",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "covers_brands": [
  "Toshiba"
 ],
 "short_model": "Toshiba Gateway INBACTOS001R100",
 "page": "https://easybacnet.com/bacnet-points-lists/intesis/inbactos001r100",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}