Pump communication module · BACnet points list
Grundfos CIM 300 / CIM 500 BACnet (pumps) BACnet points list
Updated 28 October 2026
The CIM 300 add-on module (or CIU 300 box) gives Grundfos electronic pumps a BACnet MS/TP interface; the CIM 500 does the same over BACnet IP. The pump functional profile is a fixed object list: status binary inputs, command binary outputs, multistate objects for control and operating mode, analog inputs for measured values and counters, analog outputs for setpoint and flow limit, and analog values for module configuration. Many points depend on pump family, MGE motor model (G, H or later) and fitted sensors.
This page lists 105 BACnet objects for the Grundfos CIM 300 / CIM 500 BACnet (pumps) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Grundfos’s own free documentation, linked below.
- Manufacturer
- Grundfos
- Model
- CIM 300 / CIM 500 BACnet (pumps)
- Equipment
- Pump communication module
- Equipment type
- VFDs & pumps
- BACnet objects
- 105 (21 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 227000 + MAC address (CIM 300 default); custom value via AV 0 with SW3 on
- Also known as
- CIM 300, CIU 300, CIM 500, CIU 500, CIM300, MAGNA3, TPE, MGE, CUE, E-pumps
Reference only, provided as-is: verify against Grundfos’s current documentation and the live device before use. Not official Grundfos information. Terms of use.
BMS integration notes: Grundfos CIM 300 / CIM 500 BACnet (pumps)
Set the control mode (MO 0), operating mode (MO 1) and setpoint (AO 0) first, then take control by writing BO 0 = 1 (bus control). Set AV 1 so the pump drops back to its local settings if BACnet goes quiet. Read status from the BI, MI and AI objects, and reset faults with BO 4.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 0 | Set control source | Takes bus control (1) or gives it back (0) | Write |
| MO 1 | Set operating mode | Start/stop: 1 = Start, 2 = Stop | Write |
| MO 0 | Set control mode | Control mode, e.g. constant or proportional pressure | Write |
| AO 0 | Set setpoint | Setpoint in % of range or nominal frequency | Write |
| BO 4 | Reset fault | Resets an alarm on a 0-to-1 edge (bus control only) | Write |
| BI 0 | Control source status | Confirms bus control; drops to local if the watchdog trips | Read |
| BI 2 | Rotation status | Pump running | Read |
| AI 9 | Actual setpoint | Setpoint actually in use | Read |
| AI 0 | Fault code | Active Grundfos alarm code | Read |
Enable & remote start
Write the desired control mode (MO 0), operating mode (MO 1, 1 = Start, 2 = Stop) and setpoint (AO 0), then set BO 0 Set control source = 1 for bus control. BI 0 and MI 14 show the active control source. Relay, reset and simulation commands only act while bus control is on.
Heartbeat & communication loss
AV 1 BACnet watchdog: 0 = disabled (default), or 5-3600 s. If no BACnet traffic is seen for that time while in bus control, the pump switches to local control and uses its local settings. After comms return the BAS must set BO 0 back to 1. Make the local settings first (Grundfos GO or PC Tool).
Sensors & values from the BMS
AV 12 Remote sensor feedback lets the BAS send the sensor value (0-100 %) to MAGNA3 and MGE model H and later pumps.
Network setup
- CIM 300 default device instance is 227000 + MAC address (227000-227127); for a custom value write AV 0 and turn DIP switch SW3 on.
- MAC address is set with the hexadecimal rotary switches.
- MS/TP baud with DIP switches SW4/SW5: 9600 (default), 19200, 38400 or 76800.
- CIM 500 (BACnet IP) is set up from its built-in webserver; factory webserver address 192.168.1.100.
Watch out for
- A setpoint of 0 does not stop the pump; use MO 1 = 2 (Stop).
- AO 0 is a percentage: of the setpoint range in closed-loop modes and of nominal frequency in open loop. Use AI 133/134 and the sensor range to scale.
- The manual's fault section refers to the fault and warning codes as AV 0 / AV 1, but the object tables list them as AI 0 / AI 1.
- Many points only exist on certain pump families or MGE model G/H, or need an external sensor.
Grundfos CIM 300 / CIM 500 BACnet (pumps) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 0 | Control source status | Whether the pump is under local or bus control | Read | 0=Local control, 1=Bus control | |
| BI | 1 | Actual direction | Impeller rotation direction | Read | 0=Clockwise, 1=Counterclockwise | |
| BImin | 2 | Rotation status | Pump running | Read | 0=No rotation, 1=Rotation (pump running) | |
| BI | 3 | At minimum speed | Running at minimum speed | Read | 0=Not at minimum speed, 1=At minimum speed | |
| BI | 4 | At maximum speed | Running at maximum speed | Read | 0=Not at maximum speed, 1=At maximum speed | |
| BI | 9 | Low Flow stop active | Low flow stop function active | Read | 0=Not active, 1=Active | |
| BI | 11 | Digital input 1 status | Digital input 1 state | Read | 0=Not active, 1=Active | |
| BI | 12 | Digital input 2 status | Digital input 2 state | Read | 0=Not active, 1=Active | |
| BI | 13 | Digital input 3 status | Digital input 3 state | Read | 0=Not active, 1=Active | |
| BI | 14 | Digital output 1 status | Digital output 1 state | Read | 0=Not active, 1=Active | |
| BI | 15 | Digital output 2 status | Digital output 2 state | Read | 0=Not active, 1=Active | |
| BI | 28 | Fault simulation status | Fault simulation running | Read | 0=Not active, 1=Active | |
| BI | 31 | At power limit | Running at power limit | Read | 0=Not at power limit, 1=At power limit | |
| BI | 38 | Setpoint influence | Setpoint influence active | Read | 0=Not active, 1=Active | |
| BI | 39 | Max. flow limit | Maximum flow limit active | Read | 0=Not active, 1=Active | |
| BI | 62 | Flow estimation below range | Estimated flow below the estimation range | Read | 0=Inside range, 1=Below range | |
| BI | 63 | Flow estimation above range | Estimated flow above the estimation range | Read | 0=Not above range, 1=Above range | |
| BI | 64 | Forced to local | Pump forced to local control | Read | 0=Not forced to local, 1=Forced to local | |
| BI | 86 | Status direct control (Positive Kp) | Direct control (positive Kp) status | Read | 0=Disabled, 1=Enabled (positive Kp) | |
| BOmin | 0 | Set control source | Selects local or BACnet (bus) control | Write | 0=Local control (default), 1=Bus control | |
| BO | 1 | Relay 1 control | Relay 1 command when bus control and bus relay mode are set | Write | 0=Closed (default), 1=Open | |
| BO | 2 | Relay 2 control | Relay 2 command when bus control and bus relay mode are set | Write | 0=Closed (default), 1=Open | |
| BOmin | 4 | Reset fault | Resets an alarm on a rising edge (bus control only) | Write | 0=No reset (default), 1=Reset | |
| BO | 5 | Fault simulation | Turns on a simulated fault (bus control only) | Write | 0=Disabled (default), 1=Enabled | |
| BO | 6 | Copy settings to local | Copies remote settings to local settings on remote-to-local change | Write | 0=Disabled, 1=Enabled | |
| BO | 9 | Enable max. flow limit | Enables the maximum flow limit | Write | 0=Disabled, 1=Enabled | |
| BO | 21 | Set direct control | Selects direct (positive Kp) or reverse control | Write | 0=Disabled (negative Kp), 1=Enabled (positive Kp) | |
| MI | 0 | Actual control mode | Control mode currently in use | Read | 1=Constant speed, 2=Constant pressure, 3=Proportional pressure, 4=Automatic/AUTOADAPT, 5=Constant flow, 6=Constant temperature, 7=Constant level, 8=Constant percentage, 9=FLOWADAPT, 10=Closed-loop sensor control, 11=Constant diff. pressure, 12=Constant diff. temperature | |
| MI | 1 | Actual operating mode | Operating mode currently in use | Read | 1=Start (normal), 2=Stop, 3=Minimum, 4=Maximum, 5=User curve | |
| MI | 2 | Next bearing-service type | Type of the next bearing service | Read | 1=Service type unknown, 2=Lubricate bearings, 3=Change bearings | |
| MI | 3 | CIM status | CIM module health | Read | 1=OK, 2=EEPROM fault, 3=Memory fault | |
| MI | 11 | Feedback sensor unit | Engineering unit of the feedback sensor | Read | 1=Unknown, 2=bar, 3=mbar, 4=m, 5=kPa, 6=psi, 7=ft, 8=m3/h, 9=m3/s, 10=l/s, 11=gpm, 12=°C, 13=°F, 14=%, 15=K, 16=l/h | |
| MI | 14 | Control Source | Where the pump is currently controlled from | Read | 1=Display, 2=Bus, 3=Handheld, 4=Digital in, 5=ON/OFF button | |
| MOmin | 0 | Set control mode | Sets the control mode (bus control only) | Write | 1=Constant speed (default), 2=Constant pressure, 3=Proportional pressure, 4=Automatic/AUTOADAPT, 5=Constant flow, 6=Constant temperature, 7=Constant level, 8=Constant percentage, 9=FLOWADAPT, 10=Closed-loop sensor control, 11=Constant diff. pressure, 12=Constant diff. temperature | |
| MOmin | 1 | Set operating mode | Sets the operating mode (bus control only) | Write | 1=Start (normal), 2=Stop (default), 3=Minimum, 4=Maximum | |
| MO | 2 | Product simulation | Simulates a pump type for commissioning without a pump | Write | 1=Disabled (default), 2=MAGNA, 3=E-pumps 0.25-7.5 kW, 4=E-pumps 11-22 kW / CUE, 8=MAGNA3, 9=E-pumps based on MGE model H | |
| AImin | 0 | Fault code | Grundfos alarm (fault) code | Read | ||
| AI | 1 | Warning code | Grundfos warning code | Read | ||
| AI | 2 | Time to bearing service | Months until bearing service (24 means 24 or more) | month | Read | |
| AI | 3 | Capacity | Actual capacity value (process feedback) | % | Read | |
| AI | 4 | Head | Actual system head/pressure | bar | Read | |
| AI | 5 | Flow | Actual system flow rate | m3/h | Read | |
| AI | 6 | Relative performance | Performance relative to maximum performance | % | Read | |
| AI | 7 | Speed | Motor speed | rpm | Read | |
| AI | 8 | Frequency | Actual control signal applied to motor | Hz | Read | |
| AImin | 9 | Actual setpoint | Setpoint in use (% of frequency or sensor range) | % | Read | |
| AI | 10 | Motor current | Actual motor current | A | Read | |
| AI | 11 | DC link voltage | Frequency converter DC Link voltage | V | Read | |
| AI | 12 | Motor voltage | Motor voltage | V | Read | |
| AI | 13 | Power | Total power consumption of the pump | W | Read | |
| AI | 14 | Remote flow | Measured flow at external sensor | m3/h | Read | |
| AI | 15 | Inlet pressure | System inlet pressure | bar | Read | |
| AI | 16 | Remote pressure | Measured pressure at external sensor | bar | Read | |
| AI | 17 | Level | Tank level | m | Read | |
| AI | 18 | Power electronic temp. | Temperature in frequency converter | °C | Read | |
| AI | 19 | Motor temperature | Motor winding temperature | °C | Read | |
| AI | 20 | Remote temperature | Temperature at external sensor | °C | Read | |
| AI | 21 | Electronic temperature | Pump electronics temperature | °C | Read | |
| AI | 22 | Fluid temperature | Pumped-liquid temperature | °C | Read | |
| AI | 23 | Bearing temperature DE | Bearing temperature, drive end | °C | Read | |
| AI | 24 | Bearing temp. NDE | Bearing temperature, non-drive end | °C | Read | |
| AI | 25 | Auxiliary sensor input | Auxiliary sensor input | % | Read | |
| AI | 26 | Specific energy | Specific energy consumption | kWh/m3 | Read | |
| AI | 27 | Runtime | Total operating time of the pump | h | Read | |
| AI | 28 | Total on time | Total power-on time of the pump | h | Read | |
| AI | 29 | Torque | Motor torque | Nm | Read | |
| AI | 30 | Energy consumption | Total energy consumption of the pump | kWh | Read | |
| AI | 31 | Number of starts | Number of times the pump has started | Read | ||
| AI | 32 | Volume | Total pumped volume | m3 | Read | |
| AI | 37 | Outlet pressure | System outlet pressure | bar | Read | |
| AI | 57 | Remote temperature 2 | Temperature at external temperature sensor 2 | °C | Read | |
| AI | 58 | User setpoint | User-selected setpoint (% of frequency or setpoint range) | % | Read | |
| AI | 85 | Min. of feedback sensor | Minimum value of feedback sensor | Read | ||
| AI | 86 | Max. of feedback sensor | Maximum value of feedback sensor | Read | ||
| AI | 92 | Load percent | Motor current in percent of rated motor current | % | Read | |
| AI | 93 | Differential pressure | Pressure between pump flanges | bar | Read | |
| AI | 95 | Actual flow limit | Actual maximum flow limit | m3/h | Read | |
| AI | 114 | Remote diff. temperature | Differential temperature at remote sensor | °C | Read | |
| AI | 115 | Inlet diff. pressure | Differential pressure at the inlet pipe | bar | Read | |
| AI | 116 | Outlet diff. pressure | Differential pressure at the outlet pipe | bar | Read | |
| AI | 117 | Remote diff. pressure | Differential pressure at remote sensor | bar | Read | |
| AI | 118 | Storage tank Level | Water level in the storage tank | m | Read | |
| AI | 119 | Heat energy counter | Accumulated heat energy in pump life | kWh | Read | |
| AI | 120 | Heat power | Actual heat power | W | Read | |
| AI | 121 | Heat diff. temperature | Differential temperature (heat) | K | Read | |
| AI | 130 | Nominal frequency | Nominal pump frequency | Hz | Read | |
| AI | 131 | Minimum frequency | Minimum frequency in % of nominal frequency | % | Read | |
| AI | 132 | Maximum frequency | Maximum frequency in % of nominal frequency | % | Read | |
| AI | 133 | Setpoint range minimum | Setpoint range minimum, % of sensor maximum | % | Read | |
| AI | 134 | Setpoint range maximum | Setpoint range maximum, % of sensor maximum | % | Read | |
| AI | 135 | Heat energy counter 2 | Heat energy counter 2 (Cooling) | kWh | Read | |
| AI | 136 | Volume counter 2 | Volume counter 2 | m3 | Read | |
| AI | 145 | Conductivity | Conductivity, 1 S/m resolution | S/m | Read | |
| AI | 146 | PhMeasure | pH, 0.1 pH resolution | pH | Read | |
| AI | 147 | Turbidity | Turbidity, 0.1 NTU resolution | NTU | Read | |
| AOmin | 0 | Set setpoint | Pump setpoint (bus control only); 0 does not stop the pump | % | Write | |
| AO | 5 | Set max. flow limit | Maximum flow limit value | m3/h | Write | |
| AV | 0 | Custom Device Object Instance Number | Custom device instance (used when DIP switch SW3 is on) | Write | ||
| AV | 1 | BACnet watchdog | Watchdog time before falling back to local control; 0 = off | s | Write | |
| AV | 2 | Simulation fault code | Fault code to simulate; write 0 to clear | Write | ||
| AV | 3 | Simulation warning code | Warning code to simulate; write 0 to clear | Write | ||
| AV | 9 | Product time and date | Pump time and date in UNIX seconds | s | Write | |
| AV | 12 | Remote sensor feedback | Sensor value written by the BAS (remote feedback) | % | Write | |
| AV | 19 | Set Kp | Controller proportional gain Kp | Write | ||
| AV | 20 | Set Ti | Controller integral time Ti | s | Write |
No points match these filters.
Object ID lookup: Grundfos CIM 300 / CIM 500 point IDs by name
BI0Control source statusBI1Actual directionBI2Rotation statusBI3At minimum speedBI4At maximum speedBI9Low Flow stop activeBI11Digital input 1 statusBI12Digital input 2 statusBI13Digital input 3 statusBI14Digital output 1 statusBI15Digital output 2 statusBI28Fault simulation statusBI31At power limitBI38Setpoint influenceBI39Max. flow limitBI62Flow estimation below rangeBI63Flow estimation above rangeBI64Forced to localBI86Status direct control (Positive Kp)BO0Set control sourceBO1Relay 1 controlBO2Relay 2 controlBO4Reset faultBO5Fault simulationBO6Copy settings to localBO9Enable max. flow limitBO21Set direct controlMI0Actual control modeMI1Actual operating modeMI2Next bearing-service typeMI3CIM statusMI11Feedback sensor unitMI14Control SourceMO0Set control modeMO1Set operating modeMO2Product simulationAI0Fault codeAI1Warning codeAI2Time to bearing serviceAI3CapacityAI4HeadAI5FlowAI6Relative performanceAI7SpeedAI8FrequencyAI9Actual setpointAI10Motor currentAI11DC link voltageAI12Motor voltageAI13PowerAI14Remote flowAI15Inlet pressureAI16Remote pressureAI17LevelAI18Power electronic temp.AI19Motor temperatureAI20Remote temperatureAI21Electronic temperatureAI22Fluid temperatureAI23Bearing temperature DEAI24Bearing temp. NDEAI25Auxiliary sensor inputAI26Specific energyAI27RuntimeAI28Total on timeAI29TorqueAI30Energy consumptionAI31Number of startsAI32VolumeAI37Outlet pressureAI57Remote temperature 2AI58User setpointAI85Min. of feedback sensorAI86Max. of feedback sensorAI92Load percentAI93Differential pressureAI95Actual flow limitAI114Remote diff. temperatureAI115Inlet diff. pressureAI116Outlet diff. pressureAI117Remote diff. pressureAI118Storage tank LevelAI119Heat energy counterAI120Heat powerAI121Heat diff. temperatureAI130Nominal frequencyAI131Minimum frequencyAI132Maximum frequencyAI133Setpoint range minimumAI134Setpoint range maximumAI135Heat energy counter 2AI136Volume counter 2AI145ConductivityAI146PhMeasureAI147TurbidityAO0Set setpointAO5Set max. flow limitAV0Custom Device Object Instance NumberAV1BACnet watchdogAV2Simulation fault codeAV3Simulation warning codeAV9Product time and dateAV12Remote sensor feedbackAV19Set KpAV20Set Ti
Integration notes
- Writes to BO 1-6, MO 0-1 and AO 0 only act when bus control is enabled with BO 0 = 1.
- If AV 1 (watchdog) is set and BACnet traffic stops for that time, the pump falls back to local control.
- Point availability differs between MAGNA3, E-pumps 0.25-7.5 kW and E-pumps 11-22 kW/CUE; many points need MGE model G or H or an external sensor.
- On MAGNA and TPE Series 2000 the flow value is estimated and meant for monitoring only.
- CIM 300 MS/TP speed is set with DIP switches SW4/SW5 (9600 default, up to 76800).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CIM 300 / CIM 500 BACnet (pumps) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Grundfos CIM 300 / CIM 500 BACnet (pumps)
How many BACnet points does the Grundfos CIM 300 / CIM 500 BACnet (pumps) have?
This list has 105 BACnet objects: 59 analog inputs, 2 analog outputs, 8 analog values, 19 binary inputs, 8 binary outputs, 6 multi-state inputs, 3 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Grundfos CIM 300 / CIM 500 BACnet (pumps) BACnet points are writable?
21 of the 105 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Grundfos CIM 300 / CIM 500 BACnet (pumps) BACnet documentation?
The source is BACnet for Grundfos pumps, CIM/CIU 300 BACnet MS/TP, CIM/CIU 500 Ethernet for BACnet IP - Functional profile and user manual (97572650), revision 09.2025, published free by Grundfos at https://api.grundfos.com/literature/Grundfosliterature-6012933.pdf.
What are the minimum BACnet points to integrate the Grundfos CIM 300 / CIM 500 BACnet (pumps)?
Start with BO 0 Set control source (Takes bus control (1) or gives it back (0)); MO 1 Set operating mode (Start/stop: 1 = Start, 2 = Stop); MO 0 Set control mode (Control mode, e.g. constant or proportional pressure); AO 0 Set setpoint (Setpoint in % of range or nominal frequency); BO 4 Reset fault (Resets an alarm on a 0-to-1 edge (bus control only)); BI 0 Control source status (Confirms bus control; drops to local if the watchdog trips); BI 2 Rotation status (Pump running); AI 9 Actual setpoint (Setpoint actually in use); AI 0 Fault code (Active Grundfos alarm code).
How do I enable BMS control of the Grundfos CIM 300 / CIM 500 BACnet (pumps)?
Write the desired control mode (MO 0), operating mode (MO 1, 1 = Start, 2 = Stop) and setpoint (AO 0), then set BO 0 Set control source = 1 for bus control. BI 0 and MI 14 show the active control source. Relay, reset and simulation commands only act while bus control is on.
Does the Grundfos CIM 300 / CIM 500 BACnet (pumps) need a BACnet heartbeat or have a communication timeout?
AV 1 BACnet watchdog: 0 = disabled (default), or 5-3600 s. If no BACnet traffic is seen for that time while in bus control, the pump switches to local control and uses its local settings. After comms return the BAS must set BO 0 back to 1. Make the local settings first (Grundfos GO or PC Tool).
Can the BMS supply sensor values to the Grundfos CIM 300 / CIM 500 BACnet (pumps)?
AV 12 Remote sensor feedback lets the BAS send the sensor value (0-100 %) to MAGNA3 and MGE model H and later pumps.
How do I check these points on the real CIM 300 / CIM 500 BACnet (pumps)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Grundfos BACnet points lists
- Booster pump system communication module
Grundfos CIM 500 BACnet IP (booster systems)
Grundfos Hydro MPC / Control MPC (CU 35X), Hydro Multi-E and Hydro Multi-B (CU 323) booster systems fitted with a CIM 500 (or CIU 500) BACnet IP module.
Also known as: CIM 500, CIU 500, CIM500, Hydro MPC, Hydro Multi-E, Hydro Multi-B, Control MPC, CU 35X, CU 323 - Wastewater pump level controller
Grundfos Level Control LC 2X1 (CIM 300 / CIM 500)
Grundfos Level Control LC 2X1 controllers for one- or two-pump wastewater pits, fitted with a CIM 300 (BACnet MS/TP) or CIM 500 (BACnet IP) module.
Also known as: LC 2X1, LC2X1, Grundfos LC 2X1, Level Control LC 2X1, CIM 300, CIM 500, CIU 300, CIU 500 - Submersible pump level controller
Grundfos Level Control LC 2X2 (CIM 300 / CIM 500)
Grundfos Level Control LC 2X2 controllers for submersible pump pits, fitted with a CIM 300 (BACnet MS/TP) or CIM 500 (BACnet IP) module.
Also known as: LC 2X2, LC2X2, Grundfos LC 2X2, Level Control LC 2X2, CIM 300, CIM 500, CIU 300, CIU 500 - Mixing loop unit (valve + pump controller)
Grundfos MIXIT mixing loop unit (BACnet MS/TP and IP)
Grundfos MIXIT mixing loop units (valve, controller and connected MAGNA3/UPM pump) with the CONNECT upgrade, for heating and cooling loops.
Also known as: MIXIT, Grundfos MIXIT, MIXIT DYNAMIC, MIXIT CONNECT, BACnet for MIXIT
Source: BACnet for Grundfos pumps, CIM/CIU 300 BACnet MS/TP, CIM/CIU 500 Ethernet for BACnet IP - Functional profile and user manual · 97572650 · rev. 09.2025. Object names, instances and units are reproduced as published; descriptions are our own.