- Home
- BACnet points lists
- Daikin Applied
- MicroTech III Fan Coil Unit Controller
Fan coil unit controller · BACnet points list
Daikin Applied MicroTech III Fan Coil Unit Controller BACnet points list
Updated 28 October 2026
The MicroTech III fan coil controller joins a BACnet MS/TP trunk through a plug-in BACnet communication module (a LonWorks module is the alternative; only the BACnet objects are listed here). Points cover space, water and discharge temperatures, occupancy setpoints and differentials, valve and economizer tuning, network space temperature and setpoint inputs, occupancy and application mode commands, alarm status and PI loop objects. Configuration (cp...) objects live in non-volatile memory.
This page lists 76 BACnet objects for the Daikin Applied MicroTech III Fan Coil Unit Controller — 50 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin Applied’s own free documentation, linked below.
- Manufacturer
- Daikin Applied
- Model
- MicroTech III Fan Coil Unit Controller
- Equipment
- Fan coil unit controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 76 (50 writable)
- Transport
- BACnet MS/TP
- Firmware
- BACnet module v1.1 or later for Receive Heartbeat and BV 5 (PICS firmware v1.3)
- Default device instance
- 3101000 + MS/TP MAC address (e.g. 3101007)
- Also known as
- MicroTech III FCU, MTIIIUC_FCU, Applied Terminal Systems fan coil, ED 15135
Reference only, provided as-is: verify against Daikin Applied’s current documentation and the live device before use. Not official Daikin Applied information. Terms of use.
BMS integration notes: Daikin Applied MicroTech III Fan Coil Unit Controller
Give the module a unique MAC and instance, then command occupancy and application mode and, if the BMS owns the setpoint, write Temperature Setpoint Input after disabling local setpoint adjust. Supply the space or water temperature from the BMS only when needed, and use Receive Heartbeat if overrides must fall back when the BMS goes quiet.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 6 | OccManCmd | Occupancy override from the BMS | Command |
| MV 9 | ApplicMode | Application mode (Auto/Heat/Cool/Off/Fan/Economy/Dehumid) | Command |
| AV 37 | Setpoint | Network reference setpoint | Command |
| BV 1 | ClearAlarm | Clear the current alarm | Write |
| MV 4 | McQFcuStatus | Unit operating status | Read |
| AV 22 | EffectSpaceTemp | Space temperature used for control | Read |
| MV 3 | Fan Speed | Commanded fan speed | Read |
| MV 1 | CurrentAlarm | Highest-priority active alarm | Read |
Enable & remote start
No local/remote switch is described. Network inputs take effect when written: Application Mode Input (MV 9) overrides the room sensor mode switch, Occupancy Override Input (MV 6) and Occupancy Scheduler Input (MV 7) set occupancy, Energy Hold Off (MV 11) forces standby setpoints. These overrides revert to Null after a controller reboot.
Heartbeat & communication loss
Receive Heartbeat (AV 34, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled, v1.1 and later) is the longest a supported override may go without being rewritten before it reverts to its default. Supported points: AV 35, AV 36, AV 38, MV 7, MV 8, MV 9, MV 10, MV 11 and MV 13. Disabling device communication also triggers the revert.
Sensors & values from the BMS
Write the space temperature to Space Temperature Input (AV 36) and the water temperature to Remote Entering Water Temperature (AV 35); the effective values (AV 22, AV 20) use the local sensors unless these hold valid values. Temperature Setpoint Input (AV 37) sets the occupied/standby reference setpoint once local setpoint adjust is disabled with MV 12 = 1. Temperature Setpoint Offset Input (AV 38) shifts the occupied and standby setpoints. Occupancy Sensor Input (MV 8) accepts a network occupancy sensor.
Network setup
- Default device instance is 3101000 plus the MS/TP MAC address (example 3101007); System Minimum Instance (AV 412) sets the base.
- MS/TP baud (9600, 19200, 38400 default, 76800) is set only in the module's serial configuration menu (DB-9 port, 19200 8-N-1, null-modem cable).
- MS/TP MAC address comes from address switch S3; it can only be set from the BAS or menu when S3 is at 255.
- Set MaxMasters to the highest MS/TP master address on the segment.
- Equipment configuration (BV 5) can only be set from the configuration menu, not from the BAS.
Watch out for
- Configuration (cp...) objects are stored in non-volatile memory with a limited write life; do not write them cyclically.
- Network overrides revert to Null on controller reboot, so the BMS must restore them.
- ReinitializeDevice password is McQuay or MicroTech; the password wink makes the unit identify itself.
- Occupancy setpoints must stay in order: unoccupied heat <= standby heat <= occupied heat <= occupied cool <= standby cool <= unoccupied cool.
Daikin Applied MicroTech III Fan Coil Unit Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | LocalSpaceTemp | Local Space Temperature Output | °F | Read | |
| AI | 2 | LocalSetpt | Local Setpoint Adjust Output | °F | Read | |
| AI | 3 | EWT | Local Entering Water Temperature | °F | Read | |
| AI | 4 | DischAirTemp | Discharge Air Temperature | °F | Read | |
| AI | 5 | OutdoorTemp | Outdoor Air Temperature | °F | Read | |
| AV | 1 | cpOccupied_Cool_Setpt | Occupied Cooling Setpoint | °F | Write | |
| AV | 2 | cpStandby_Cool_Setpt | Standby Cool Setpoint | °F | Write | |
| AV | 3 | cpUnoccupied_Cool_Setpt | Unoccupied Cool Setpoint | °F | Write | |
| AV | 4 | cpOccupied_Heat_Setpt | Occupied Heat Setpoint | °F | Write | |
| AV | 5 | cpStandby_Heat_Setpt | Standby Heat Setpoint | °F | Write | |
| AV | 6 | cpUnoccupied_Heat_Setpt | Unoccupied Heat Setpoint | °F | Write | |
| AV | 7 | cpCoolEnDiff | Cooling Enable Differential | °F | Write | |
| AV | 8 | cpCoolIntStgTmr | Cooling Interstage Timer | s | Write | |
| AV | 9 | cpCoolDB | Cooling Valve Deadband | % | Write | |
| AV | 10 | cpCoolVlvStroke | Cooling Valve Stroke Time | s | Write | |
| AV | 11 | cpMaxDASpt | Economizer Maximum Discharge Air Setpoint | °F | Write | |
| AV | 12 | cpMinDASpt | Economizer Minimum Discharge Air Setpoint | °F | Write | |
| AV | 13 | cpEconOaEnDiff | Economizer Outdoor Air Enable Differential | °F | Write | |
| AV | 14 | cpEconOaEn | Economizer Outdoor Air Enable Setpoint | °F | Write | |
| AV | 15 | cpEconLowMin | Economizer Min Position at Fan Low | % | Write | |
| AV | 16 | cpEconMedMin | Economizer Min Position at Fan Med | % | Write | |
| AV | 17 | cpEconHighMin | Economizer Min Position at Fan High | % | Write | |
| AV | 18 | cpEconDB | Economizer Position Deadband | % | Write | |
| AV | 19 | cpEconStroke | Economizer Stroke Time | s | Write | |
| AV | 20 | EffectEWT | Effective Entering Water Temperature | °F | Read | |
| AV | 21 | EffectSetpt | Effective Setpoint Output | °F | Read | |
| AVmin | 22 | EffectSpaceTemp | Effective Space Temperature Output | °F | Read | |
| AV | 23 | cpEWTFlowTmr | Entering Water Temperature Flow Sample Delay Timer | s | Write | |
| AV | 24 | cpEWTSampleTmr | Entering Water Temperature Sample Interval Timer | min | Write | |
| AV | 25 | cpFanMinOffTmr | Fan Minimum OFF Timer | s | Write | |
| AV | 26 | cpFanMinOnTmr | Fan Minimum ON Timer | s | Write | |
| AV | 27 | cpHeatEnDiff | Heating Enable Differential | °F | Write | |
| AV | 28 | cpHeatIntStgTmr | Heating Interstage Timer | s | Write | |
| AV | 29 | cpHeatDB | Heating Valve Deadband | % | Write | |
| AV | 30 | cpHeatVlvStroke | Heating Valve Stroke Time | s | Write | |
| AV | 31 | cpBypassTime | Local Bypass Time Setpoint | min | Write | |
| AV | 32 | SetpointShift | Setpoint Shift Output | °F | Read | |
| AV | 33 | cpOccDiff | Occupied Setpoint Differential | °F | Write | |
| AV | 34 | cpRcvHrtBt | Receive Heartbeat | s | Write | |
| AV | 35 | Network_EWT | Remote Entering Water Temperature | °F | Command | |
| AV | 36 | Network_SpaceTemp | Space Temperature Input | °F | Command | |
| AVmin | 37 | Setpoint | Temperature Setpoint Input | °F | Command | |
| AV | 38 | SetptOffset | Temperature Setpoint Offset Input | °F | Command | |
| AV | 39 | cpUnoccDiff | Unoccupied Setpoint Differential | °F | Write | |
| AV | 40 | TerminalLoad | Terminal Load Output | % | Read | |
| AV | 41 | cpSptAdjMax | Long Range Setpoint Adjust Maximum | °F | Write | |
| AV | 42 | cpSptAdjMin | Long Range Setpoint Adjust Minimum | °F | Write | |
| AV | 43 | cpFltrChangeHrs | Air Filter Change Timer | h | Write | |
| AV | 411 | MacAddress | MAC address; named MacAddressSwitch when address switch is set | Write | ||
| AV | 412 | SystemMinInstance | System Minimum Instance | Write | ||
| BI | 1 | BinaryIn | Binary Input Status | Read | ||
| BVmin | 1 | ClearAlarm | Clear Alarm | Write | 0=Normal, 1=Clear Alarm | |
| BV | 2 | BinaryOut | Binary Output Status | Read | ||
| BV | 3 | UnitAppStatus | Unit Application Status | Read | ||
| BV | 4 | UnitFaults | Unit Faults | Read | ||
| BV | 5 | SoftJumpers | Equipment Configuration (v1.1 and later) | Read | ||
| MI | 1 | FanModeSpdSw | Fan Mode/Speed Status | Read | 1=Off, 2=Low, 3=Med, 4=High, 5=Auto, 6=Null (no switch present) | |
| MI | 2 | HeatCoolAuto | System Mode Switch (Heat/Cool/Auto) Status | Read | 1=Off, 2=Heat, 3=Cool, 4=Auto, 5=Null (no switch present) | |
| MVmin | 1 | CurrentAlarm | Current Alarm | Read | 1=No Alarms, 2=Invalid Equipment Configuration, 3=Emergency Shutdown, 4=Freeze Fault, 5=EWT Sensor Failure, 6=Room Temperature Sensor Failure, 7=IO Expansion Board Com Failure, 8=Condensate Overflow, 9=Outdoor Air Temp Sensor Failure, 10=Discharge Air Temp Sensor Failure, 11=Dirty Air Filter, 12=BB Serial EEPROM Corrupted | |
| MV | 2 | PreviousAlarm | Previous Alarm | Read | 1=No Alarms, 2=Invalid Equipment Configuration, 3=Emergency Shutdown, 4=Freeze Fault, 5=EWT Sensor Failure, 6=Room Temperature Sensor Failure, 7=IO Expansion Board Com Failure, 8=Condensate Overflow, 9=Outdoor Air Temp Sensor Fail, 10=Discharge Air Temp Sensor Fail, 11=Dirty Air Filter, 12=Serial EEPROM Corrupted | |
| MVmin | 3 | Fan Speed | Fan Speed Output | Read | 1=Off, 2=Low, 3=Medium, 4=High, 5=On | |
| MVmin | 4 | McQFcuStatus | McQuay FCU Status | Read | 1=Off Alarm, 2=Off, 3=Start, 4=Fan Only, 5=Heating, 6=Economizer, 7=Cooling, 8=Dehumid, 9=Null | |
| MV | 5 | EffectOccup | Effective Occupancy Output | Read | 1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Null | |
| MVmin | 6 | OccManCmd | Occupancy Override Input | Command | 1=Occupied, 2=Unoccupied, 3=Bypass, 4=Standby, 5=Null | |
| MV | 7 | OccSchedule | Occupancy Scheduler Input | Command | 1=Occupied, 2=Unoccupied, 3=Standby, 4=Null | |
| MV | 8 | OccSensor | Occupancy Sensor Input | Command | 1=Occupied, 2=Unoccupied, 3=Null | |
| MVmin | 9 | ApplicMode | Application Mode Input | Command | 1=Auto, 2=Heat, 3=Cool, 4=Off, 5=Fan Only, 6=Economy, 7=Dehumid, 8=Null | |
| MV | 10 | AuxHeatEnable | Auxiliary Heat Enable Input | Command | 1=Disabled, 2=Enabled, 3=Null | |
| MV | 11 | EnergyHoldOff | Energy Hold Off Input | Command | 1=Normal, 2=Energy Hold Off, 3=Null | |
| MV | 12 | cpLocSpEnable | Room Sensor Setpoint Adjust Enable/Disable | Write | 1=Disabled, 2=Enabled | |
| MV | 13 | EconEnable | Economizer Enable Input | Command | 1=Disabled, 2=Enabled, 3=Null | |
| MV | 14 | Units | Units (English / Metric) | Write | 1=English (E), 2=Metric (M) | |
| LO | 1 | Heat Valve Loop | Heating valve PI loop (output = valve position) | % | Read | |
| LO | 2 | Cool Valve Loop | Cooling valve PI loop (output = valve position) | % | Read | |
| LO | 3 | DASP_Loop | Economizer discharge-air PI loop (output = damper position) | % | Read | |
| LO | 4 | EconPos_Loop | Economizer position PI loop (output = damper position) | % | Read |
No points match these filters.
Object ID lookup: Daikin Applied MicroTech III Fan Coil point IDs by name
AI1LocalSpaceTempAI2LocalSetptAI3EWTAI4DischAirTempAI5OutdoorTempAV1cpOccupied_Cool_SetptAV2cpStandby_Cool_SetptAV3cpUnoccupied_Cool_SetptAV4cpOccupied_Heat_SetptAV5cpStandby_Heat_SetptAV6cpUnoccupied_Heat_SetptAV7cpCoolEnDiffAV8cpCoolIntStgTmrAV9cpCoolDBAV10cpCoolVlvStrokeAV11cpMaxDASptAV12cpMinDASptAV13cpEconOaEnDiffAV14cpEconOaEnAV15cpEconLowMinAV16cpEconMedMinAV17cpEconHighMinAV18cpEconDBAV19cpEconStrokeAV20EffectEWTAV21EffectSetptAV22EffectSpaceTempAV23cpEWTFlowTmrAV24cpEWTSampleTmrAV25cpFanMinOffTmrAV26cpFanMinOnTmrAV27cpHeatEnDiffAV28cpHeatIntStgTmrAV29cpHeatDBAV30cpHeatVlvStrokeAV31cpBypassTimeAV32SetpointShiftAV33cpOccDiffAV34cpRcvHrtBtAV35Network_EWTAV36Network_SpaceTempAV37SetpointAV38SetptOffsetAV39cpUnoccDiffAV40TerminalLoadAV41cpSptAdjMaxAV42cpSptAdjMinAV43cpFltrChangeHrsAV411MacAddressAV412SystemMinInstanceBI1BinaryInBV1ClearAlarmBV2BinaryOutBV3UnitAppStatusBV4UnitFaultsBV5SoftJumpersMI1FanModeSpdSwMI2HeatCoolAutoMV1CurrentAlarmMV2PreviousAlarmMV3Fan SpeedMV4McQFcuStatusMV5EffectOccupMV6OccManCmdMV7OccScheduleMV8OccSensorMV9ApplicModeMV10AuxHeatEnableMV11EnergyHoldOffMV12cpLocSpEnableMV13EconEnableMV14UnitsLO1Heat Valve LoopLO2Cool Valve LoopLO3DASP_LoopLO4EconPos_Loop
Integration notes
- BACnet MS/TP only; the same document also covers a LonWorks module, which is not listed here.
- Configuration (cp...) objects are stored in non-volatile memory with a limited write life; avoid frequent writes.
- BI 1 and BV 2-5 are bit-packed status words; the bits are returned in each object's Description property.
- Loop objects LO 1-4 also expose writable Proportional_Constant and Integral_Constant properties (stored in non-volatile memory).
- MV 9 text in the guide still says Null is 7 in one place; the state list (8 = Null) is the corrected one from revision 6.
- Analog Null (sensor failed or unused) reads 621.806 °F / 327.67 °C.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MicroTech III Fan Coil Unit Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin Applied MicroTech III Fan Coil Unit Controller
How many BACnet points does the Daikin Applied MicroTech III Fan Coil Unit Controller have?
This list has 76 BACnet objects: 5 analog inputs, 45 analog values, 1 binary input, 5 binary values, 4 loops, 2 multi-state inputs, 14 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin Applied MicroTech III Fan Coil Unit Controller BACnet points are writable?
50 of the 76 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin Applied MicroTech III Fan Coil Unit Controller BACnet documentation?
The source is MicroTech III Fan Coil Unit Controller Protocol Information (LonWorks / BACnet MS/TP) (ED 15135-6), revision 2021-01, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/MicroTech%20III%20FCU%20Unit%20Controller%20Protocol%20Information%20Daikin%20ED%2015135-6.pdf.
What are the minimum BACnet points to integrate the Daikin Applied MicroTech III Fan Coil Unit Controller?
Start with MV 6 OccManCmd (Occupancy override from the BMS); MV 9 ApplicMode (Application mode (Auto/Heat/Cool/Off/Fan/Economy/Dehumid)); AV 37 Setpoint (Network reference setpoint); BV 1 ClearAlarm (Clear the current alarm); MV 4 McQFcuStatus (Unit operating status); AV 22 EffectSpaceTemp (Space temperature used for control); MV 3 Fan Speed (Commanded fan speed); MV 1 CurrentAlarm (Highest-priority active alarm).
How do I enable BMS control of the Daikin Applied MicroTech III Fan Coil Unit Controller?
No local/remote switch is described. Network inputs take effect when written: Application Mode Input (MV 9) overrides the room sensor mode switch, Occupancy Override Input (MV 6) and Occupancy Scheduler Input (MV 7) set occupancy, Energy Hold Off (MV 11) forces standby setpoints. These overrides revert to Null after a controller reboot.
Does the Daikin Applied MicroTech III Fan Coil Unit Controller need a BACnet heartbeat or have a communication timeout?
Receive Heartbeat (AV 34, cpRcvHrtBt, 0-6553.4 s, default 0 = disabled, v1.1 and later) is the longest a supported override may go without being rewritten before it reverts to its default. Supported points: AV 35, AV 36, AV 38, MV 7, MV 8, MV 9, MV 10, MV 11 and MV 13. Disabling device communication also triggers the revert.
Can the BMS supply sensor values to the Daikin Applied MicroTech III Fan Coil Unit Controller?
Write the space temperature to Space Temperature Input (AV 36) and the water temperature to Remote Entering Water Temperature (AV 35); the effective values (AV 22, AV 20) use the local sensors unless these hold valid values. Temperature Setpoint Input (AV 37) sets the occupied/standby reference setpoint once local setpoint adjust is disabled with MV 12 = 1. Temperature Setpoint Offset Input (AV 38) shifts the occupied and standby setpoints. Occupancy Sensor Input (MV 8) accepts a network occupancy sensor.
How do I check these points on the real MicroTech III Fan Coil Unit Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin Applied BACnet points lists
- Air handling unit controller
Daikin Applied ADK digital air handler, DSTREAM controls (Daikin Applied Europe)
Daikin Applied Europe ADK digital air handling units (D-AHU) with the MicroTech III or MicroTech 4 controller and DSTREAM control software.
Also known as: ADK, D-AHU, Digital AHU, Daikin D-AHU, DSTREAM, D-EIGOC00108-22_05 - Air handling unit controller
Daikin Applied Airstream ADT air handler (Daikin Applied Europe)
Daikin Applied Europe ADT air handling units with the MicroTech controller and Airstream software, including units paired with ERQ outdoor condensing units.
Also known as: ADT, Airstream, Daikin ADT AHU, D-EIGOC00104-25_01 - Air handling unit controller
Daikin Applied Compact air handler, Fujin Comfort software (Daikin Applied Europe)
Daikin Applied Europe Compact air handling units with the Fujin Comfort controller software, including units with an ERQ condensing unit.
Also known as: Compact, Daikin Compact AHU, Fujin Comfort, D-EIGOC00101-25_00EN - VAV terminal unit controller
Daikin Applied Daikin VAV Controller (BACnet MS/TP)
Pressure-independent VAV terminal units (cooling only, reheat, series and parallel fan-powered) with the Daikin VAV actuator-controller.
Also known as: Daikin VAV controller, VAV Model 250802400, 250802400, BACnet VAV actuator, ED 19157 - Air-cooled screw chiller controller
Daikin Applied EWAD-TZD / EWAH-TZD / EWFD / EWFH air-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWAD-TZD/MZD and EWAH-TZD/MZD air-cooled inverter screw chillers and the EWFD/EWFH free-cooling versions (MicroTech 4, software "ETRA / OMEGA").
Also known as: EWAD-TZD, EWAD-MZD, EWAH-TZD, EWAH-MZD, EWFD-TZD, EWFH-TZD, EWAD TZ, EWAD/H-T/MZD, EWFD/H-T/MZD, ETRA, OMEGA, D-EIGOC00103-23_01 - Air-to-water heat pump / air-cooled chiller controller
Daikin Applied EWAK-CZ / EWYK-CZ air-to-water heat pump and chiller (Daikin Applied Europe)
Daikin Applied Europe EWAK-CZ air-cooled chillers and EWYK-CZ reversible air-to-water heat pumps running the ICARO control software.
Also known as: EWYK-CZ, EWAK-CZ, EWYK CZ, EWAK CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00104 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B air-cooled scroll chillers (MicroTech 4, software "NASH"), including the free-cooling and heat recovery options.
Also known as: EWAT-B, EWAT B, EWAT-B-SS, EWAT-B-SL, EWAT-B-SR, EWAT-B-XS, EWAT-B-XL, EWAT-B-XR, NASH, D-EIGOC00103 - Air-cooled scroll chiller controller
Daikin Applied EWAT-B-C / EWAF-B-C air-cooled chiller (Daikin Applied Europe)
Daikin Applied Europe EWAT-B-C air-cooled scroll chillers and the EWAF-B-C free-cooling version (MicroTech 4, software "ARES").
Also known as: EWA(F)T-B-C, EWAT-B-C, EWAF-B-C, EWAT B-C, EWAF B-C, ARES, D-EIGOC00107-24_04 - Water-cooled chiller controller
Daikin Applied EWWD / EWWH I-, J- and K-series water-cooled chillers (Daikin Applied Europe)
Daikin Applied Europe EWWD and EWWH I-, J- and K-series water-cooled chillers with a MicroTech 4 controller running the EWWD software.
Also known as: EWWD-J, EWWH-J, EWWD-I, EWWD-K, EWWH-K, EWWD/H-IJK, D-EIGOC00102-22EN_EWWD-IJK - Water-cooled chiller controller
Daikin Applied EWWD-DZ / EWWH-DZ water-cooled chiller, VORTEX software (Daikin Applied Europe)
Daikin Applied Europe EWWD-DZ and EWWH-DZ water-cooled chillers running the VORTEX software (up to three compressors).
Also known as: EWWD-DZ, EWWH-DZ, VORTEX, D-EIGOC00103-21EN-DZ - Water-cooled screw chiller controller
Daikin Applied EWWD-VZ water-cooled screw chiller (Daikin Applied Europe)
Daikin Applied Europe EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers (MicroTech, software "Adam").
Also known as: EWWD VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, Adam, D-EIGOC00101 - Water-cooled chiller controller
Daikin Applied EWWQ-KC water-cooled chiller, Nayda software (Daikin Applied Europe)
Daikin Applied Europe EWWQ-KC units with the POL486.65 controller running the Nayda software, including master/slave groups of up to four units.
Also known as: EWWQ-KC, EWWQ-KCW, Nayda, D-EIGOC00101-22_01EN_EWWQ-KC - Water-cooled scroll chiller controller
Daikin Applied EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)
Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.
Also known as: EWWT-Q, EWLT-Q, EWHT-Q, EWWTQ, PROXIMA, D-EIGOC00106, WCZ - Heat pump / chiller controller
Daikin Applied EWYD / EWYH-4Z multipurpose heat pump, EVE software (Daikin Applied Europe)
Daikin Applied Europe EWYD-4Z and EWYH-4Z units with a MicroTech 4 controller running the EVE software.
Also known as: EWYD-4Z, EWYH-4Z, EWYD/H-4Z, EVE, D-EIGOC00102-22 - Air-to-water heat pump controller
Daikin Applied EWYT-B air-to-water heat pump (Daikin Applied Europe)
Daikin Applied Europe EWYT-B reversible air-to-water scroll heat pumps (MicroTech 4, software "NASH_HP").
Also known as: EWYT-B, EWYT B, EWYT-B-SS, EWYT-B-SL, EWYT-B-SR, EWYT-B-XS, EWYT-B-XL, EWYT-B-XR, NASH_HP, D-EIGOC00107-23_01 - Chiller plant manager (multi-chiller sequencer)
Daikin Applied iCM chiller plant manager, option 184 (Daikin Applied Europe)
Daikin Applied Europe chiller plants run by the iCM software (option 184) on the master MicroTech 4 chiller: a master plus up to seven slave chillers, with optional pump (iPM), cooling tower (iCT) and pump group (iSM) management.
Also known as: iCM, Option 184, iCM option 184, Intelligent Chiller Manager, iCM Standard, iCM Advanced, iCM Expanded, iPM, iCT, iSM, D-EIGOC00110-21_03 - Chiller controller
Daikin Applied Magnitude WME C-vintage Chiller (MicroTech WME controller)
Magnitude WME C-vintage magnetic-bearing centrifugal chillers with the MicroTech WME unit controller.
Also known as: WME-C, Magnitude WME, MicroTech WME, ED 19111, WME-D, Magnitude WME D-vintage - Magnetic bearing centrifugal chiller controller
Daikin Applied Magnitude WME single-compressor chiller (2010 McQuay unit controller)
Daikin McQuay Magnitude WME single-compressor magnetic bearing centrifugal chillers with the original (2010) Magnitude chiller unit controller.
Also known as: ED 15117, Magnitude WME, WME, McQuay Magnitude, Magnitude Chiller Unit Controller - Chiller controller
Daikin Applied Magnitude WME-C QUAD Chiller (MicroTech WME controller)
Magnitude WME-C QUAD magnetic-bearing centrifugal chillers (two circuits, four compressors) with the MicroTech WME unit controller.
Also known as: WME-C QUAD, WME QUAD, Magnitude WME, MicroTech WME, ED 19111-4 - Rooftop unit controller
Daikin Applied Maverick I Packaged Rooftop Unit Controller (MPS)
Daikin Applied Maverick I (MPS) packaged rooftop units with the RTU-C unit controller and a BACnet communication module.
Also known as: Maverick I, MPS, Maverick I MPS, RTU-C, ED 15125 - Rooftop unit controller
Daikin Applied Maverick II Packaged Rooftop Unit Controller (MicroTech II MPS)
Daikin McQuay Maverick II (MPS) packaged commercial rooftop units with the MicroTech II MPS unit controller, DAC or SCC control, application software 1.10 and later.
Also known as: Maverick II, MPS, McQuay Maverick II, MicroTech II MPS, ED 15102, MTIIUC_MPS - Variable frequency drive (HVAC)
Daikin Applied MD5 Variable Frequency Drive (embedded BACnet MS/TP)
Daikin Applied MD5 variable frequency drives (Applied Air Systems) on the built-in RS-485 port with native BACnet MS/TP.
Also known as: MD5, MD5 VFD, Daikin MD5, OM 1191, OM 1191-2 - Rooftop unit controller
Daikin Applied MicroTech 4 Rebel Applied Rooftop Unit Controller
Daikin Rebel Applied (DPSA) packaged rooftop units with the MicroTech 4 unit controller.
Also known as: Rebel Applied, DPSA, MicroTech 4 AHU, MT4 AHU, MT4_AHU, ED 19117 - Rooftop unit controller
Daikin Applied MicroTech Applied Air Unit Controller (Rebel DPS R-32, Rebel Applied DPSA, DCSA split, ROC)
Daikin Rebel DPS (R-32) and Rebel Applied DPSA (R-410A or R-32) rooftops, their Refrigeration Only Controls versions, and DCSA air-cooled split condensing systems on the MicroTech 4 controller.
Also known as: Rebel DPS R-32, Rebel Applied DPSA R-32, DCSA, Rebel ROC, Refrigeration Only Controls, MT4 AHU, ED 19117-8 - Chiller controller
Daikin Applied MicroTech Chiller Controller (Trailblazer AGZ-F, Magnitude WMC-E, WMT)
Trailblazer AGZ F-vintage air-cooled scroll chillers and Magnitude WMC-E and WMT magnetic-bearing centrifugal chillers.
Also known as: AGZ-F, Trailblazer AGZ F-vintage, WMC-E, WMT, Magnitude WMT, ED 19131 - Chiller controller
Daikin Applied MicroTech Chiller Unit Controller (Pathfinder, Trailblazer, Magnitude WME-B, Navigator)
Air-cooled scroll (AGZ-D/E, AMZ), air-cooled screw (AWS, AWV, ADS), WME B-vintage magnetic-bearing and WWV water-cooled screw chillers.
Also known as: MicroTech III chiller, Pathfinder AWS, Pathfinder AWV, Trailblazer AGZ, Trailblazer AMZ, ADS, Magnitude WME B-vintage, Navigator WWV, ED 15120 - Water source heat pump DOAS controller
Daikin Applied MicroTech DOAS WSHP Unit Controller
Daikin SmartSource DOAS water source heat pumps with the MicroTech unit controller and its on-board BACnet MS/TP port.
Also known as: SmartSource DOAS, DOAS water source heat pump, MTUC_DOAS WSHP, ED 19118 - Unit ventilator controller (classroom terminal unit)
Daikin Applied MicroTech II AAF-HermanNelson Unit Ventilator Controller
McQuay AAF-HermanNelson unit ventilators with the MicroTech II unit ventilator controller (software models 00-18) and the BACnet MS/TP communication module.
Also known as: ED 15065, AAF-HermanNelson, HermanNelson unit ventilator, MicroTech II UV, UVC, MTII UVUC - Rooftop unit / air handler controller
Daikin Applied MicroTech II Applied Rooftop Unit Controller
Legacy RoofPak rooftop units (RPS/RFS/RCS/RDT), outdoor air handlers (RPR/RPE/RDE) and RDS/RAH/RAR air handlers with the MicroTech II controller.
Also known as: MicroTech II RTUC, MTII RTUC, RoofPak, RPS, RFS, RCS, RDT, RPR, RPE, RDE, RDS, RAH, RAR, McQuay RoofPak, ED 15060 - Chiller controller
Daikin Applied MicroTech II Chiller Unit Controller
Older Daikin Applied (McQuay) chillers with the MicroTech II unit controller: WSC/WDC/WPV/HSC/HDC/TSC/WMC/WCC centrifugals, AGZ/ACZ/WGZ/TGZ scroll and AGS/WGS screw units.
Also known as: MicroTech II chiller, MTII Chiller UC, WSC, WDC, WPV, HSC, HDC, TSC, WMC, WCC, AGZ, ACZ, AGS, WGZ, TGZ, WGS, ED 15062, ED 15100 - Self-contained unit controller
Daikin Applied MicroTech II Vertical Self-Contained Unit Controller (SWP / SWT)
Daikin McQuay SWP self-contained and SWT modular self-contained air conditioning units with the MicroTech II controller (application 1.28), DAC or SCC control.
Also known as: ED 15061, SWP, SWT, MicroTech II self-contained, MTII SCUC, McQuay self-contained - Rooftop unit / AHU controller
Daikin Applied MicroTech III Applied Rooftop and Self-Contained Unit Controller
Rebel (DPS/DPH), Maverick (MPS), RoofPak rooftops and air handlers (RPS, RDT, RFS, RDS, RAH, RPE, RDE) and SWP/SWT self-contained units.
Also known as: MicroTech III AHU, RoofPak, Rebel DPS, Maverick MPS, RPS, RDT, RFS, RDS, RAH, RPE, RDE, SWP, SWT, ED 15112 - Generic I/O controller
Daikin Applied MicroTech III Generic I/O Panel
Daikin MicroTech III Generic I/O Panel used in the Daikin Delivered VAV System (software 2508022100 and later).
Also known as: ED 19014, Generic I/O Panel, MicroTech III GIO, POL904 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - Enfinity Single Stage
Enfinity single-stage compressor water source heat pumps (MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW, VHC/VHF).
Also known as: Enfinity, MHC, MHW, CCH, CCW, VFC, VFW, LVC, LVW, VHC, VHF, MicroTech III water source heat pump, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech III WSHP Controller - SmartSource / Enfinity Large Two Compressor
SmartSource single and two-stage (GSH/GSV, GTH/GTV, GCV/GCH) and Enfinity Large two-compressor (CCH/CCW, LVC/LVW) heat pumps.
Also known as: SmartSource, GSH, GSV, GTH, GTV, GCV, GCH, Enfinity Large, CCH, CCW, LVC, LVW, ED 15103 - Water source heat pump controller
Daikin Applied MicroTech MT2300 WSHP Controller - SmartSource R32 (SCH/SDH, SMH/SNH, SSH/STH)
Daikin SmartSource single/two-stage and two-compressor water source heat pumps with R32 refrigerant and the MicroTech MT2300 controller (models SCH/SDH, SMH/SNH, SSH/STH).
Also known as: MT2300, SmartSource Series2, SmartSource SS2C, SCH, SDH, SMH, SNH, SSH, STH, ED 19129 - Air handler unit controller
Daikin Applied MicroTech PreciseLine Light Air Handler Controller
PreciseLine light commercial air handlers (BCV, BCA, BCH; 600-10,000 CFM) with the MicroTech 4 Lite controller, including R-410A D-Kit and R-32 EV-kit VRV units.
Also known as: PreciseLine, MicroTech 4 Lite, MT4 Lite AHU, PL AHU, BCV, BCA, BCH, ED 19126 - Unit ventilator controller (classroom air handler)
Daikin Applied MicroTech Unit Ventilator Controller
Daikin Applied unit ventilators with the MicroTech UV unit controller and its on-board BACnet MS/TP port.
Also known as: MicroTech UV, MTUC_UV, Daikin unit ventilator, ED 19110 - EC fan array controller (air handler)
Daikin Applied MicroTech Vision / Skyline EC Fan Array Controller
Vision (CAH/CAC) and Skyline (OAH/OAC) air handlers with an EC fan array on the MicroTech 4 fan controller (Premium controls option), up to 20 fans.
Also known as: Vision, Skyline, MT4_DFA_EC, MT4_DFA, CAH, CAC, OAH, OAC, EC fan array, ED 19122 - Air handling unit controller
Daikin Applied Modular Light (ALB) air handler, EvoLVE controls (Daikin Applied Europe)
Daikin Applied Europe Modular Light (ALB) compact air handling units with the MicroTech controller and EvoLVE / Airstream control software.
Also known as: Modular Light, ALB, Daikin Modular Light AHU, EvoLVE, Airstream, D-EIGOC00106-26_00 - Air handling unit controller
Daikin Applied Modular T (ATB) air handler, MODULAR T software (Daikin Applied Europe)
Daikin Applied Europe Modular T (ATB) air handling units with the MODULAR T controller software.
Also known as: Modular T, ATB, MOD T, Daikin Modular T AHU, D-EIGOC0110-23-00EN
Source: MicroTech III Fan Coil Unit Controller Protocol Information (LonWorks / BACnet MS/TP) · ED 15135-6 · rev. 2021-01. Object names, instances and units are reproduced as published; descriptions are our own.