Multi-brand VRF / split AC BACnet gateway · BACnet points list
CoolAutomation CoolMasterNet BACnet (indoor unit objects) BACnet points list
Updated 28 October 2026
CoolMasterNet and the CooLink family connect to the AC manufacturer's indoor-unit bus and serve every indoor unit as the same 16 BACnet objects, over BACnet MS/TP and/or BACnet IP. Instance numbers are built from the unit's virtual address (VA): instance = VA x 256 + object index. Configuration is done with text commands on the gateway's ASCII interface.
This page lists 16 BACnet objects for the CoolAutomation CoolMasterNet BACnet (indoor unit objects) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.
- Manufacturer
- CoolAutomation
- Model
- CoolMasterNet BACnet (indoor unit objects)
- Equipment
- Multi-brand VRF / split AC BACnet gateway
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 16 (12 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 64
- Also known as
- CoolMasterNet, CooLinkNet, CooLinkHub, CooLinkBridge, CoolAutomation BACnet, LG VRF BACnet gateway, Daikin VRV BACnet gateway, Mitsubishi Electric BACnet gateway, Samsung BACnet gateway, Gree GMV BACnet gateway
Instance calculator. This list prints one unit; the other units follow a formula. CoolAutomation CoolMasterNet / CooLink instance calculator →
Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.
BMS integration notes: CoolAutomation CoolMasterNet BACnet (indoor unit objects)
Enable BACnet MS/TP on line L3 and/or BACnet IP, run 'va auto' so each indoor unit gets a virtual address, then map each unit's block of objects at VA x 256. Command BV ON/OFF, MV Operation Mode, AV Set Temperature and MV Fan Speed, and read AI Room Temperature and BI HVAC Failure Indication.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 256 | ON/OFF | Start/stop the indoor unit | Write |
| MV 257 | Operation Mode | Cool/heat/auto/dry/fan mode command | Write |
| AV 256 | Set Temperature | Indoor unit setpoint, °C | Write |
| MV 256 | Fan Speed | Fan speed command (low/medium/high/auto) | Write |
| AI 256 | Room Temperature | Room temp reported by the indoor unit, °C | Read |
| BI 256 | HVAC Failure Indication | Unit alarm (code in Active_Text) | Read |
Enable & remote start
BACnet must be enabled on the gateway ('line type L3 BAC' for MS/TP, 'bacnet IP enable' for IP); no BMS enable object is documented.
Network setup
- BACnet MS/TP: activate on line L3 with 'line type L3 BAC' (L4-L7 also possible on CoolMasterNet); default frame 9600 8N1, change with 'line baud L3 <rate>_8N1'; MAC (TS) default 0x40 = 64, change with 'line myid L3 <hex>'. Reboot after each change.
- BACnet IP: enable with 'bacnet IP enable'; UDP port 47808 by default ('bacnet port <n>'). The server starts only once Ethernet is up with an IP address.
- Default device instance 64 (0x40); change with 'bacnet instance <n>'.
- Allocate virtual addresses with 'va auto' (one VA per detected indoor unit) or 'va + L1.102 0004'; list them with 'va'.
- One MS/TP and one BACnet IP connection can run at the same time.
Watch out for
- Running 'va auto' again deletes and re-allocates all VAs, which renumbers every object; only run it once all indoor units are connected.
- Every configuration command needs a reboot to take effect.
- Additional MS/TP connections are not supported even if more RS-485 lines exist.
- The guide's MS/TP example output shows TS 64 and device instance 64 by default; set unique values for each gateway.
CoolAutomation CoolMasterNet BACnet (indoor unit objects) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 256 | Room Temperature | Room temperature reported by the indoor unit | °C | Read | |
| AVmin | 256 | Set Temperature | Indoor unit setpoint | °C | Write | |
| BImin | 256 | HVAC Failure Indication | Unit failure; Active_Text carries the failure code | Read | 0=No Failure, 1=Failure | |
| BI | 257 | Demand State (Therm_ON) | Thermostat demand (thermo-on) | Read | ||
| BI | 258 | External Terminals Status | State of the unit external terminals input | Read | ||
| BVmin | 256 | ON/OFF | Start/stop the indoor unit | Write | 0=Off, 1=On | |
| BV | 257 | Filter Sign | Filter-clean indication | Write | ||
| BV | 258 | Lock (prohibit) ON/OFF change from WRC | Block on/off changes from the wired remote | Write | ||
| BV | 259 | Lock (prohibit) Operation Mode change from WRC | Block mode changes from the wired remote | Write | ||
| BV | 260 | Lock (prohibit) Set Temperature change from WRC | Block setpoint changes from the wired remote | Write | ||
| BV | 261 | Global Lock (prohibit) | Block all wired-remote operation | Write | ||
| MVmin | 256 | Fan Speed | Fan speed | Write | 1=Low, 2=Medium, 3=High, 4=Auto, 5=Top, 6=Very Low, 7=Super High, 8=HRV Super High, 9=HRV Low FreshUp, 10=HRV High FreshUP | |
| MVmin | 257 | Operation Mode | Operating mode | Write | 1=Cool, 2=Heat, 3=Auto, 4=Dry, 5=HAUX, 6=Fan, 7=Heat+HAUX, 9=HRV Auto, 10=HRV Bypass, 11=HRV Heat Exchange, 12=HRV Normal | |
| MV | 258 | Louver | Louver position | Write | 1=Vertical, 2=30 deg, 3=45 deg, 4=60 deg, 5=Horizontal, 6=Auto (Swing), 7=Off, 8=No Louver Control | |
| PIV | 256 | Set Temperature low limit | Lowest setpoint allowed | °C | Write | |
| PIV | 257 | Set Temperature high limit | Highest setpoint allowed | °C | Write |
No points match these filters.
Object ID lookup: CoolAutomation CoolMasterNet BACnet, Indoor Units point IDs by name
AI256Room TemperatureAV256Set TemperatureBI256HVAC Failure IndicationBI257Demand State (Therm_ON)BI258External Terminals StatusBV256ON/OFFBV257Filter SignBV258Lock (prohibit) ON/OFF change from WRCBV259Lock (prohibit) Operation Mode change from WRCBV260Lock (prohibit) Set Temperature change from WRCBV261Global Lock (prohibit)MV256Fan SpeedMV257Operation ModeMV258LouverPIV256Set Temperature low limitPIV257Set Temperature high limit
Integration notes
- Points shown for virtual address VA 1 (instances 256-258); add 256 for each further VA.
- The object identifier's instance field is VA in bits 21-8 and object index in bits 7-0.
- Access follows the guide's object-type table: BV, AV, MV and PIV read/write; BI, AI and CSV read-only.
- Object names are not printed in the guide; the object descriptions are used as names.
- Fan speed, mode and louver states that a given unit does not support are simply not used.
- Operation Mode state 8 is not printed in the guide.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet BACnet (indoor unit objects) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the CoolAutomation CoolMasterNet BACnet (indoor unit objects)
How many BACnet points does the CoolAutomation CoolMasterNet BACnet (indoor unit objects) have?
This list has 16 BACnet objects: 1 analog input, 1 analog value, 3 binary inputs, 6 binary values, 3 multi-state values, 2 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which CoolAutomation CoolMasterNet BACnet (indoor unit objects) BACnet points are writable?
12 of the 16 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official CoolAutomation CoolMasterNet BACnet (indoor unit objects) BACnet documentation?
The source is BACnet Integration Guidelines - CoolMasterNet, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 0.5, 2019-04-29, published free by CoolAutomation at https://coolautomation.com/Lib/doc/CoolMasterNet/manual/CoolMasterNet-BACnet-guidelines.pdf.
What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet BACnet (indoor unit objects)?
Start with BV 256 ON/OFF (Start/stop the indoor unit); MV 257 Operation Mode (Cool/heat/auto/dry/fan mode command); AV 256 Set Temperature (Indoor unit setpoint, °C); MV 256 Fan Speed (Fan speed command (low/medium/high/auto)); AI 256 Room Temperature (Room temp reported by the indoor unit, °C); BI 256 HVAC Failure Indication (Unit alarm (code in Active_Text)).
How do I enable BMS control of the CoolAutomation CoolMasterNet BACnet (indoor unit objects)?
BACnet must be enabled on the gateway ('line type L3 BAC' for MS/TP, 'bacnet IP enable' for IP); no BMS enable object is documented.
How do I check these points on the real CoolMasterNet BACnet (indoor unit objects)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More CoolAutomation BACnet points lists
- VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - EXL (RSLYJ355-560)
Daikin EXL outdoor systems RSLYJ355-560 (KA/KC; printed "KA_KC") read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, EXL, RSLYJ355-560 - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - RXTA-A
Daikin RXTA-A outdoor systems read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, RXTA-A - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - Ve-up3Q (RQYP140-900A)
Daikin Ve-up3Q outdoor systems (RQYP140-900A) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, Ve-up3Q, RQYP140-900A - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1)
Daikin VRV PLUS outdoor systems (RSEYP16-30KJY1) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV_PLUS, VRV Plus, RSEYP16-30KJY1 - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ)
Daikin VRV-K outdoor systems (RSEYP8-10KJ) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-K, RSEYP8-10KJ - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L)
Daikin VRV-L outdoor systems RSXYP5-10L (JY1/Y1/YL) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-L, RSXYP5-10L - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor system (PRO) objects - VRV-3R, VRV3C
Daikin VRV outdoor systems (VRV-3R, VRV3C, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-3R, VRV3C - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor system (PRO) objects - VRV-4R
Daikin VRV outdoor systems (VRV-4R, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-4R - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor system (PRO) objects - VRV-M (REYQ8-48M)
Daikin VRV outdoor systems (VRV-M (REYQ8-48M), as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-M (REYQ8-48M) - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor system (PRO) objects - VRV4S1, VRV4S2, mini-VRV, VRV-3S, VRV-M, VRV-3P
Daikin VRV outdoor systems (VRV4S1, VRV4S2, mini-VRV, VRV-3S, VRV-M, VRV-3P, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV4S1, VRV4S2, mini-VRV, VRV-3S, VRV-M, VRV-3P - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor system (PRO) objects - VRV4S3, VRVX, VRV4-EU
Daikin VRV outdoor systems (VRV4S3, VRVX, VRV4-EU, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV4S3, VRVX, VRV4-EU - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - mini-VRV, VRV-M
Daikin VRV outdoor units (mini-VRV, VRV-M, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, mini-VRV, VRV-M - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - Ve-up3Q (RQYP140-900A)
Daikin Ve-up3Q outdoor units (RQYP140-900A) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, Ve-up3Q, RQYP140-900A - VRF water-cooled outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1)
Daikin water-cooled VRV units VRV-2-WATER (RWEYQ10-30MY1) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV W BACnet, CoolMasterNet Daikin, Daikin water cooled VRV BACnet, VRV-2-WATER, RWEYQ10-30MY1 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA
Daikin VRV outdoor units of the series CoolAutomation calls VRV-2MA, read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, VRV-2MA - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3R, VRV3C
Daikin VRV outdoor units (VRV-3R, VRV3C, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, VRV-3R, VRV3C - VRF water-cooled outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER
Daikin water-cooled VRV units VRV-3W-WATER (RWEYQ8-30P), VRV3C2-WATER (RWEYP***PCTJ), VRV-3Wx-WATER (RWEYQ8-30P) and VRV-4W-WATER (RWEYQ8-10T7Y1B) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV W BACnet, CoolMasterNet Daikin, Daikin water cooled VRV BACnet, VRV-3W-WATER, RWEYQ8-30P, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER, RWEYQ8-10T7Y1B - VRF water-cooled outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-4W3-WATER (RWEYQ8-14T9Y1B)
Daikin water-cooled VRV units VRV-4W3-WATER (RWEYQ8-14T9Y1B) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV W BACnet, CoolMasterNet Daikin, Daikin water cooled VRV BACnet, VRV-4W3-WATER, RWEYQ8-14T9Y1B - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-M (REYQ8-48M)
Daikin VRV outdoor units (VRV-M (REYQ8-48M), as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, VRV-M (REYQ8-48M) - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV4S1, VRV4S2, VRV-3S, VRV-3P
Daikin VRV outdoor units (VRV4S1, VRV4S2, VRV-3S, VRV-3P, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, VRV4S1, VRV4S2, VRV-3S, VRV-3P - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Fujitsu AJ*GALH outdoor unit (PRO) objects
Fujitsu outdoor units AJHuGALH, AJHGALH, AOULBV, AJHGALBH, AJYGALBH, AJQGALAH, AJTuGALH, AJTGALH, AJTGBLH, AJYuGALH, AJYGALH, AJYGALDH and AJHGALDH (model codes exactly as printed by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Fujitsu VRF BACnet, CoolMasterNet Fujitsu, AJHGALH, AOULBV, AJHGALBH, AJYGALBH, AJQGALAH, AJTGALH, AJTGBLH, AJYGALH, AJYGALDH, AJHGALDH - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Fujitsu AJ*LALBH outdoor unit (PRO) objects
Fujitsu outdoor units AJY[72/90/108/126/144/162]LALBH, AOULBV1, AJGLNLBH, AJHLALBH, AJHLATBH, AJHLNLBH, AJHLNTBH, AJHLNTCH, AJHLALCH, AJQLALBH, AJYLATBH, AJYLNLBH, AJYLNTBH, AJYLNTCH, AJYLALCH, AJHLALDH and AJYLALDH (model codes as printed by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Fujitsu VRF BACnet, CoolMasterNet Fujitsu, AJY LALBH, AOULBV1, AJGLNLBH, AJHLALBH, AJHLATBH, AJHLNLBH, AJHLNTBH, AJHLNTCH, AJHLALCH, AJQLALBH, AJYLATBH, AJYLNLBH, AJYLNTBH, AJYLNTCH, AJYLALCH, AJHLALDH, AJYLALDH - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Fujitsu AJ*LCLAH outdoor unit (PRO) objects
Fujitsu outdoor units AJT[40/45/54]LCLAH, AJY[40/45/54]LCLAH, AJCLCTAH, AJHLCLAH, AJQLCLAH, AOURLAVS, AJYLCLDH and AJHLCLDH (model codes as printed by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Fujitsu VRF BACnet, CoolMasterNet Fujitsu, AJY LCLAH, AJT LCLAH, AJCLCTAH, AJHLCLAH, AJQLCLAH, AOURLAVS, AJYLCLDH, AJHLCLDH - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Fujitsu AJ*NLAH outdoor unit (PRO) objects
Fujitsu outdoor units AJHLNLAH, AJHLNLAHU, AJHLNTAH, AJQLBLH, AJYLNLAH, AJYLNTAH and AOUuRLBV (model codes as printed by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Fujitsu VRF BACnet, CoolMasterNet Fujitsu, AJHLNLAH, AJHLNLAHU, AJHLNTAH, AJQLBLH, AJYLNLAH, AJYLNTAH, AOUuRLBV - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree GMV5 HR (heat recovery) outdoor unit (PRO) objects
Gree GMV5 HR (heat recovery) VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree GMV5 BACnet, CoolMasterNet Gree, Gree outdoor unit BACnet, GMV5 HR - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects
Gree GMV5 mini VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree GMV5 mini BACnet, CoolMasterNet Gree, GMV5 mini - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects
Gree GMV5 VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree GMV5 BACnet, CoolMasterNet Gree, Gree outdoor unit BACnet, GMV5 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree GMV5C outdoor unit (PRO) objects
Gree GMV5C VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree GMV5C BACnet, CoolMasterNet Gree, GMV5C - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree GMV6 mini U.H. outdoor unit (PRO) objects
Gree GMV6 mini U.H. VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree GMV6 mini BACnet, CoolMasterNet Gree, GMV6 mini U.H. - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects
Gree VRF6 HR (heat recovery) VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree VRF6 HR BACnet, Gree VRF6 heat recovery BACnet, CoolMasterNet Gree, VRF6 HR - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects
Gree VRF6 (heat pump) VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree VRF6 BACnet, Gree GMV6 BACnet, CoolMasterNet Gree, VRF6 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects
LG Multi V III heat recovery VRF outdoor units (master unit) read through a CoolAutomation gateway with PRO functionality (LGMV section of the guide).
Also known as: LG Multi V III heat recovery BACnet, CoolMasterNet LG, MultiV III HR Master, LGMV - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG Multi V III master outdoor unit (PRO) objects
LG Multi V III VRF outdoor units (master unit) read through a CoolAutomation gateway with PRO functionality (LGMV section of the guide).
Also known as: LG Multi V III BACnet, CoolMasterNet LG, MultiV III Master, LGMV - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG MULTIV_S master outdoor unit (PRO) objects
LG Multi V S VRF outdoor units (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: LG Multi V S BACnet, LG MULTIV_S BACnet, CoolMasterNet LG, MULTIV_S Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG SUPER5 master outdoor unit (PRO) objects
LG VRF outdoor units of the SUPER5 type (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: LG Multi V 5 BACnet, LG SUPER5 BACnet, CoolMasterNet LG, SUPER5 Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG VRF outdoor unit (PRO) objects
LG VRF outdoor units read through a CoolAutomation gateway with PRO (service data) functionality.
Also known as: LG VRF BACnet, LG BACnet points list, LG outdoor unit BACnet, CoolMasterNet LG - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG WATER5 master outdoor unit (PRO) objects
LG water-source VRF outdoor units of the WATER5 type (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: LG Multi V Water 5 BACnet, LG WATER5 BACnet, CoolMasterNet LG, WATER5 Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Midea CR-HP master outdoor unit (PRO) objects
Midea VRF heat pump outdoor units of the CR-HP type (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Midea CR-HP VRF BACnet, CoolMasterNet Midea, CR-HP Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Midea CR-HR master outdoor unit (PRO) objects
Midea VRF heat recovery outdoor units of the CR-HR type (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Midea CR-HR VRF BACnet, Midea heat recovery VRF BACnet, CoolMasterNet Midea, CR-HR Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects
Midea V6 VRF outdoor units (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Midea V6 VRF BACnet, CoolMasterNet Midea, V6 Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Midea V8 master outdoor unit (PRO) objects
Midea V8 VRF outdoor units (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Midea V8 VRF BACnet, CoolMasterNet Midea, V8 Master - VRF branch controller monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric BC controller (JA/KA) (PRO) objects
Mitsubishi Electric City Multi BC controllers of the types CoolAutomation calls BC(JA) and BC(KA), read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BC controller BACnet, CoolMasterNet Mitsubishi Electric, BC(JA), BC(KA) - Air-to-water heat pump monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric CAHV heat pump (PRO) objects
Mitsubishi Electric CAHV units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi CAHV BACnet, CoolMasterNet Mitsubishi Electric, CAHV - VRF branch controller monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects
Mitsubishi Electric CMB-WP [capacity] V-GA1 and CMB-WM [capacity] V-AA branch controllers read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Hybrid City Multi BACnet, CoolMasterNet Mitsubishi Electric, CMB-WP V-GA1, CMB-WM V-AA - Multi-split outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric MXZ series outdoor unit (PRO) objects
Mitsubishi Electric MXZ series multi-split outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi MXZ BACnet, CoolMasterNet Mitsubishi Electric, MXZ series, PUMY series - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects
Mitsubishi Electric PUHV-P [capacity] CM-E outdoor units (the guide heading ends in "CM-E/..." without naming the other suffixes) read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PUHV-P CM-E - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-M YNW-A1 outdoor unit (PRO) objects
Mitsubishi Electric City Multi PUHY-M [capacity] YNW-A1 outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PUHY-M YNW-A1 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P CM-E(1) outdoor unit (PRO) objects
Mitsubishi Electric City Multi PUHY-P [capacity] CM-E(1) outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PUHY-P CM-E, PUHY-P CM-E1 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects
Mitsubishi Electric City Multi PUHY-P [capacity] TGMU-A outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PUHY-P TGMU-A - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects
Mitsubishi Electric City Multi PURY-M [capacity] YNW-A/A1 outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PURY-M YNW-A, PURY-M YNW-A1 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects
Mitsubishi Electric City Multi PURY-P [capacity] ZKMU-A outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PURY-P ZKMU-A - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Heavy Industries JL4C outdoor unit (PRO) objects
Mitsubishi Heavy Industries VRF outdoor units of the series CoolAutomation calls JL4C, read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Heavy VRF BACnet, MHI KX BACnet, CoolMasterNet MH, JL4C - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Heavy Industries K1RC outdoor unit (PRO) objects
Mitsubishi Heavy Industries VRF outdoor units of the series CoolAutomation calls K1RC, read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Heavy VRF BACnet, MHI KX BACnet, CoolMasterNet MH, K1RC - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Heavy Industries KV1C outdoor unit (PRO) objects
Mitsubishi Heavy Industries VRF outdoor units of the series CoolAutomation calls KV1C, read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Heavy VRF BACnet, MHI KX BACnet, CoolMasterNet MH, KV1C - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Heavy Industries KV2C outdoor unit (PRO) objects
Mitsubishi Heavy Industries VRF outdoor units of the series CoolAutomation calls KV2C, read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Heavy VRF BACnet, MHI KX BACnet, CoolMasterNet MH, KV2C - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Heavy Industries L3SC / KYWC outdoor unit (PRO) objects
Mitsubishi Heavy Industries single-compressor VRF outdoor units of the series CoolAutomation calls L3SC and KYWC, read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Heavy VRF BACnet, MHI KX BACnet, CoolMasterNet MH, L3SC, KYWC - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Samsung DVM S Eco 4/5/6 HP outdoor unit (PRO) objects
Samsung DVM S Eco 4, 5 and 6 HP VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Samsung DVM S Eco BACnet, CoolMasterNet Samsung, DVM-S Eco 4/5/6HP - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects
Samsung DVM S Eco 7, 8 and 9 HP VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Samsung DVM S Eco BACnet, CoolMasterNet Samsung, DVM-S Eco 7/8/9HP - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects
Samsung DVM S VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Samsung DVM S BACnet, CoolMasterNet Samsung, Samsung outdoor unit BACnet, DVM-S - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects
Samsung DVM S Water heat recovery (water-source) VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Samsung DVM S Water BACnet, CoolMasterNet Samsung, DVM-S Water HR - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Samsung FJM outdoor unit (PRO) objects
Samsung FJM (free joint multi) outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Samsung FJM BACnet, Samsung free joint multi BACnet, CoolMasterNet Samsung, FJM - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects
Toshiba SMMS VRF outdoor units (header unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Toshiba SMMS BACnet, Toshiba VRF BACnet, CoolMasterNet Toshiba, SMMS Header - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects
Toshiba Mini-SMMS VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Toshiba SMMS Mini BACnet, Toshiba Mini-SMMS BACnet, CoolMasterNet Toshiba, SMMS-Mini - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects
Toshiba SMMSe VRF outdoor units (header unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Toshiba SMMSe BACnet, Toshiba VRF BACnet, CoolMasterNet Toshiba, SMMSe Header - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects
Toshiba SMMSu (SMMS-u) VRF outdoor units read through a CoolAutomation gateway with PRO functionality (SMMSu outdoor section of the guide).
Also known as: Toshiba SMMSu BACnet, Toshiba SMMS-u BACnet, CoolMasterNet Toshiba, SMMSu
Source: BACnet Integration Guidelines - CoolMasterNet, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 0.5, 2019-04-29. Object names, instances and units are reproduced as published; descriptions are our own.