 "manufacturer": "Condair",
 "manufacturer_slug": "condair",
 "model": "Condair RS",
 "model_slug": "rs",
 "aliases": [
  "Condair RS II",
  "RS resistive steam humidifier",
  "Nortec RS"
 ],
 "equipment_type": "Electric resistive steam humidifier",
 "applies_to": "Condair RS / RS II single and dual cylinder (A/B) resistive steam humidifiers.",
 "summary": "The Condair RS is an electric heating-element steam humidifier with one or two cylinders. The Integrated Controller exposes BACnet IP and MS/TP on-board. Objects report per-cylinder status, level, capacity, maintenance countdowns and safety chain inputs, plus two-channel setpoints and writable demand inputs for main and limiter signals.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": 1001,
 "access_inferred": false,
 "notes": [
  "BACnet is built into the Integrated Controller (RJ45 for BACnet IP, RS485 for MS/TP master or slave); it ships with the BACnet protocol set to Off.",
  "Factory Node ID (device instance) is 1001 and the MS/TP MAC is 127; BACnet IP uses UDP 47808 and supports registering with a BBMD.",
  "To command the unit over BACnet set Controls > Signal Settings > Source to BACnet; the demand/humidity AO must then be rewritten within the Signal Timeout (default 300 s) or the unit stops with warning W35.",
  "Points marked optional only report when that option is fitted; capacity, pressure and temperature units follow the controller's Metric/Imperial setting.",
  "Cylinder B objects only apply to dual-cylinder units; channel 2 is used for a limiter (e.g. supply-air high limit) when dual signal control is enabled.",
  "BI 28 is Furnace Fan on UL units and External Pipe Flush on CE units."
 ],
 "source": {
  "title": "BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita)",
  "doc_number": "2603582-F",
  "revision_date": "2026-07",
  "url": "https://www.condair.co.uk/consense/bms-communication-ic-2.0/am_bms_interface_bacnet_on_board_2603582_en.pdf"
 },
 "integration": {
  "summary": "Enable BACnet in the Integrated Controller, set the signal source to BACnet, and write demand or RH to AO 15012 (and a limiter value to AO 15014 if dual signal control is used) within the signal timeout. Read cylinder A/B status, the error status and code, and actual capacity.",
  "minimum_points": [
   {
    "ref": "AO 15012",
    "name": "RH or Demand CH1 via BACnet",
    "why": "Channel 1 demand or RH from the BMS"
   },
   {
    "ref": "AO 15014",
    "name": "RH or Demand CH2 via BACnet",
    "why": "Channel 2 limiter signal (dual signal control)"
   },
   {
    "ref": "AV 15094",
    "name": "Setpoint CH1",
    "why": "Channel 1 humidity setpoint used in RH P/PI mode"
   },
   {
    "ref": "MI 5109",
    "name": "Device Status Cyl. A",
    "why": "Cylinder A status"
   },
   {
    "ref": "MI 5110",
    "name": "Device Status Cyl. B",
    "why": "Cylinder B status (dual units)"
   },
   {
    "ref": "AI 10225",
    "name": "Actual Hum. Capacity",
    "why": "Actual steam output"
   },
   {
    "ref": "MI 5159",
    "name": "Error Status",
    "why": "Maintenance/error status"
   },
   {
    "ref": "AI 10020",
    "name": "ErrorWarning Code",
    "why": "Active error or warning code"
   }
  ],
  "enable": "Set Menu > password 8808 > Controls > Signal Settings > Source to BACnet and pick the Control Mode (Demand, RH P or RH PI; On/Off also exists). With Source left at Analog the unit ignores BACnet control values.",
  "heartbeat": "When the signal source is not Analog, the demand/humidity value written over BACnet must be refreshed within the Signal Timeout (1-300 s, default 300 s). If it is not, warning W35 Signal Timeout is raised and the unit stops until a new value arrives, so the BMS must keep rewriting the AO.",
  "remote_sensors": "In Demand mode the BMS writes the required output (0-100 %) to the RH/Demand AO. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used. Channel 2 (AO 15014) is only active with dual signal control, typically a supply-air high limit.",
  "setup": [
   "BACnet settings are under Menu > password 8808 > Network > BACnet Settings; the BACnet Protocol parameter ships Off (options MS/TP Master, MS/TP Slave, BACnet/IP) and the controller restarts after changing it.",
   "Node ID (device instance) defaults to 1001 (range 1-4194303); BACnet IP port defaults to 47808.",
   "IP addressing defaults to DHCP; if no DHCP server answers the controller falls back to an APIPA 169.254.x.x address.",
   "Foreign Device registration to a BBMD is Off by default; BBMD port 47808 and re-register time 10 are the factory values.",
   "MS/TP: MAC defaults to 127 (0-127 master, 0-254 slave), baud 9600 (up to 115200); fit jumper JP6 only on the first and last device, remove JP8, and tie GND between all devices."
  ],
  "gotchas": [
   "Cylinder B objects only mean something on dual-cylinder units.",
   "BI 28 is Remote Furnace/Fan on UL units and External Pipe Flush on CE units.",
   "RS Drain AVs: write 1 to start, 0 to stop; a read of 100 means off.",
   "Capacity units follow the Metric/Imperial setting."
  ]
 },
 "points": [
  {
   "type": "DEV",
   "instance": 1001,
   "name": "Condair Controller",
   "description": "Humidifier",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 1,
   "name": "Network Port IPv4",
   "description": "Network-Port for BACnet IPv4 Communication",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 5109,
   "name": "Device Status Cyl. A",
   "description": "Actual device status cylinder A",
   "units": "",
   "access": "R",
   "states": "1=Initializing, 2=Diagnostic, 3=Stopped, 4=Break, 5=Level Test, 6=Standby, 7=Humidifying, 8=Filling, 9=Idle, 10=Draining, 11=Remote Off, 12=Keep Warm"
  },
  {
   "type": "MI",
   "instance": 5110,
   "name": "Device Status Cyl. B",
   "description": "Actual device status cylinder B",
   "units": "",
   "access": "R",
   "states": "1=Initializing, 2=Diagnostic, 3=Stopped, 4=Break, 5=Level Test, 6=Standby, 7=Humidifying, 8=Filling, 9=Idle, 10=Draining, 11=Remote Off, 12=Keep Warm"
  },
  {
   "type": "MI",
   "instance": 5159,
   "name": "Error Status",
   "description": "Maintenance and error status",
   "units": "",
   "access": "R",
   "states": "1=Service Info, 2=Warning, 3=RO Service, 4=Extended Maintenance, 5=Small Maintenance, 6=Activation Code, 7=Error"
  },
  {
   "type": "MI",
   "instance": 5123,
   "name": "Nominal Voltage",
   "description": "Nominal voltage device",
   "units": "",
   "access": "R",
   "states": "1=200 V, 2=208 V, 3=230 V, 4=240 V, 5=380V, 6=400 V, 7=415 V, 8=440 V, 9=460 V, 10=480 V, 11=500 V, 12=550 V, 13=600 V"
  },
  {
   "type": "AI",
   "instance": 15044,
   "name": "Level Cyl. A",
   "description": "Water level cylinder A",
   "units": "",
   "access": "R",
   "states": "1=no level, 2=low, 3=low-mid, 4=mid, 5=mid-high, 6=high"
  },
  {
   "type": "AI",
   "instance": 15045,
   "name": "Level Cyl. B",
   "description": "Water level cylinder B",
   "units": "",
   "access": "R",
   "states": "1=no level, 2=low, 3=low-mid, 4=mid, 5=mid-high, 6=high"
  },
  {
   "type": "AI",
   "instance": 10020,
   "name": "ErrorWarning Code",
   "description": "Code of the latest pending error or warning",
   "units": "",
   "access": "R",
   "states": "0=No error"
  },
  {
   "type": "AI",
   "instance": 10219,
   "name": "Operating Hours",
   "description": "Total hours of operation since commissioning",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15124,
   "name": "Operating Hours Cyl. A",
   "description": "Total hours of operation since commissioning of cylinder A",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15125,
   "name": "Operating Hours Cyl. B",
   "description": "Total hours of operation since commissioning of cylinder B",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10221,
   "name": "System Demand",
   "description": "Actual demand of the system",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15103,
   "name": "Control CH1",
   "description": "Actual humidity or demand signal CH1",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15104,
   "name": "Control CH2",
   "description": "Actual humidity or demand signal CH2",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10216,
   "name": "Max Hum. Capacity",
   "description": "Maximum humidifying capacity",
   "units": "kg/h or lb/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15117,
   "name": "Max Hum. Capacity Cyl. A",
   "description": "Maximum humidifying capacity cylinder A",
   "units": "kg/h or lb/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15118,
   "name": "Max Hum. Capacity Cyl. B",
   "description": "Maximum humidifying capacity cylinder B",
   "units": "kg/h or lb/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10225,
   "name": "Actual Hum. Capacity",
   "description": "Actual humidifying capacity",
   "units": "kg/h or lb/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15025,
   "name": "Actual Hum. Capacity Cyl. A",
   "description": "Actual humidifying capacity cylinder A",
   "units": "kg/h or lb/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15026,
   "name": "Actual Hum. Capacity Cyl. B",
   "description": "Actual humidifying capacity cylinder B",
   "units": "kg/h or lb/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15120,
   "name": "Next Small Maintenance Cyl. A",
   "description": "Due date of next small maintenance cylinder A",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15121,
   "name": "Next Small Maintenance Cyl. B",
   "description": "Due date of next small maintenance cylinder B",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15122,
   "name": "Next Extended Maint. Cyl. A",
   "description": "Due date of next extended maintenance cylinder A",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15123,
   "name": "Next Extended Maint. Cyl. B",
   "description": "Due date of next extended maintenance cylinder B",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15094,
   "name": "Setpoint CH1",
   "description": "Setpoint humidity channel 1",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15095,
   "name": "Setpoint CH2",
   "description": "Setpoint humidity channel 2",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15096,
   "name": "P-Band CH1",
   "description": "Proportional band humidity channel 1",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15097,
   "name": "P-Band CH2",
   "description": "Proportional band humidity channel 2",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15098,
   "name": "I-Time CH1",
   "description": "Integral time humidity channel 1",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15099,
   "name": "I-Time CH2",
   "description": "Integral time humidity channel 2",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15102,
   "name": "Capacity Limitation",
   "description": "Limitation of the maximum possible ouput",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30504,
   "name": "RS Drain",
   "description": "Remote RS drain",
   "units": "%",
   "access": "W",
   "states": "Read: 100=Off, 0 - 99=Progress draining in %, Write: 0=Stop draining, 1=Start draining cylinder A + B"
  },
  {
   "type": "AV",
   "instance": 30502,
   "name": "RS Drain Cyl. A",
   "description": "Remote RS drain cylinder A",
   "units": "%",
   "access": "W",
   "states": "Read: 100=Off, 0 - 99=Progress draining in %, Write: 0=Stop draining, 1=Start draining cylinder A"
  },
  {
   "type": "AV",
   "instance": 30503,
   "name": "RS Drain Cyl. B",
   "description": "Remote RS drain cylinder B",
   "units": "%",
   "access": "W",
   "states": "Read: 100=Off, 0 - 99=Progress draining in %, Write: 0=Stop draining, 1=Start draining cylinder B"
  },
  {
   "type": "AO",
   "instance": 15012,
   "name": "RH or Demand CH1 via BACnet",
   "description": "Actual humidity or demand via BACnet channel 1",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 15014,
   "name": "RH or Demand CH2 via BACnet",
   "description": "Actual humidity or demand via BACnet channel 2",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5011,
   "name": "Overheat Switch Cyl. A",
   "description": "Overheat switch cylinder A",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed (=ok)"
  },
  {
   "type": "BI",
   "instance": 5012,
   "name": "Overheat Switch Cyl. B",
   "description": "Overheat switch cylinder B",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed (=ok)"
  },
  {
   "type": "BI",
   "instance": 5017,
   "name": "Safety Loop Cyl. A",
   "description": "External safety loop cylinder A",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed (=ok)"
  },
  {
   "type": "BI",
   "instance": 5018,
   "name": "Safety Loop Cyl. B",
   "description": "External safety loop cylinder B",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed (=ok)"
  },
  {
   "type": "BI",
   "instance": 5013,
   "name": "Security Floater Cyl. A",
   "description": "Security floater cylinder A",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed (=ok)"
  },
  {
   "type": "BI",
   "instance": 5014,
   "name": "Security Floater Cyl. B",
   "description": "Security floater cylinder B",
   "units": "",
   "access": "R",
   "states": "0=Open, 1=Closed (=ok)"
  },
  {
   "type": "BI",
   "instance": 5015,
   "name": "Heating Voltage Cyl. A",
   "description": "Heating voltage cylinder A",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 5016,
   "name": "Heating Voltage Cyl. B",
   "description": "Heating voltage cylinder B",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 5021,
   "name": "Blower Pack Cyl. A",
   "description": "Blower pack ready cylinder A",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On (ready)"
  },
  {
   "type": "BI",
   "instance": 5022,
   "name": "Blower Pack Cyl. B",
   "description": "Blower pack ready cylinder B",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On (ready)"
  },
  {
   "type": "BI",
   "instance": 5027,
   "name": "Main Contactor Cyl. A",
   "description": "Main contactor cylinder A",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 5028,
   "name": "Main Contactor Cyl. B",
   "description": "Main contactor cylinder B",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 5029,
   "name": "Relay Pump Cyl. A",
   "description": "Relay pump cylinder A",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 5030,
   "name": "Relay Pump Cyl. B",
   "description": "Relay pump cylinder B",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 5089,
   "name": "Inlet Valve 1 Cyl. A",
   "description": "Inlet valve 1 cylinder A",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 5090,
   "name": "Inlet Valve 1 Cyl. B",
   "description": "Inlet valve 1 cylinder B",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 5091,
   "name": "Inlet Valve 2 Cyl. A",
   "description": "Inlet valve 2 cylinder A",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 5092,
   "name": "Inlet Valve 2 Cyl. B",
   "description": "Inlet valve 2 cylinder B",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 5093,
   "name": "Drain Cooling Valve Cyl. A",
   "description": "Drain cooling valve cylinder A",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 5094,
   "name": "Drain Cooling Valve Cyl. B",
   "description": "Drain cooling valve cylinder B",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 5095,
   "name": "Complete Drain Valve Cyl. A",
   "description": "Complete drain valve cylinder A (optional)",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 5096,
   "name": "Complete Drain Valve Cyl. B",
   "description": "Complete drain valve cylinder B (optional)",
   "units": "",
   "access": "R",
   "states": "0=Closed, 1=Open"
  },
  {
   "type": "BI",
   "instance": 5009,
   "name": "Leakage Sensor",
   "description": "Leakage Sensor (optional)",
   "units": "",
   "access": "R",
   "states": "0=Leak, 1=OK"
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "Furnace Fan",
   "description": "UL units: remote furnace/fan (optional)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "Ext. Pipe Flush",
   "description": "CE units: external pipe flush (shares BI 28 with Furnace Fan) (optional)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  }
 ],
 "short_model": "RS (on-board BACnet)",
 "page": "https://easybacnet.com/bacnet-points-lists/condair/rs",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}