- MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)
Water-source heat pump controller · BACnet points list
ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) BACnet points list
Updated 11 November 2026
The MPC is ClimateMaster's add-on DDC controller for water-source heat pumps. It sits on top of the CXM2/DXM2.6 unit board, acts as a thermostat with a wall sensor, and talks BACnet MS/TP, BACnet over ARC156, N2 or Modbus. The BMS commands occupancy, writes occupied and unoccupied heating and cooling setpoints (in °F or °C objects), can shut the unit down, and reads compressor, fan and temperature status plus fault counters and the lockout state. Units can share one wall sensor in a leader/follower setup.
This page lists 123 BACnet objects for the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) — 68 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from ClimateMaster’s own free documentation, linked below.
- Manufacturer
- ClimateMaster
- Model
- MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)
- Equipment
- Water-source heat pump controller
- Equipment type
- Heat pumps
- BACnet objects
- 123 (68 writable)
- Transport
- BACnet MS/TP, BACnet ARC156
- Firmware
- Gen 7 and newer (some points Gen 8 only)
- Default device instance
- Auto-generated; last two digits = rotary address
- Also known as
- MPC, ClimateMaster MPC, 97B0031N01, Multi-Protocol Controller, CXM2, DXM2.6
Reference only, provided as-is: verify against ClimateMaster’s current documentation and the live device before use. Not official ClimateMaster information. Terms of use.
BMS integration notes: ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)
Address the MPC with the rotary switches and set the MS/TP baud with the DIP switches. Command occupancy with BV 12 (or a BMS schedule on BV 14) and write the occupied cooling and heating setpoints. Use BV 8 for an emergency stop and BV 4 to clear a lockout. Monitor fan and compressor status, space temperature, the Alarm State and the Fault text.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 12 | Occupied Mode | Occupancy command (ON = occupied) | Write |
| BV 8 | Emergency Shutdown | Emergency stop; ON turns Y1, Y2, G and W off | Write |
| AV 3 | Occupied CL SP/ Fahrenheit | Occupied cooling setpoint, °F | Write |
| AV 21 | Occupied HT Setpoint | Occupied heating setpoint, °F (DB Mode off) | Write |
| BV 4 | System Reset | Lockout reset; set ON then back OFF | Write |
| BV 10 | SF Status | Supply fan running | Read |
| BV 3 | C1 Status | Compressor 1 running | Read |
| AV 34 | Zone Temp Status | Space temperature | Read |
| BV 1 | Alarm State | Lockout condition (ON = lockout) | Read |
| MV 1 | Fault | Current alarm as text | Read |
Enable & remote start
Stand-alone, the MPC defaults to occupied. BV 12 Occupied Mode (default ON) sets occupied/unoccupied from the BMS; BV 14 Work Schedule can take a BMS schedule instead. BV 8 Emergency Shutdown turns the Y1, Y2, G and W outputs off. BV 53 Compressor Shutdown disables both compressors, and BV 61/BV 54 disable heating or cooling.
Sensors & values from the BMS
For units sharing one wall sensor, set BV 16 M/S Switch ON on each follower and map the leader's Zone Temp Status (AV 34), Actual HT/CL setpoints (AV 2, AV 1) and Occupied Status (BV 11) to the follower's Master ZT (AV 4), Subordinate HT/CL SP (AV 9, AV 10) and Occupied Mode (BV 12).
Network setup
- MAC address comes from two rotary switches (00-99); ClimateMaster suggests 02 for heat pump 1 and HP number + 1 for the rest.
- BACnet MS/TP on RS-485 at 9.6, 19.2, 38.4 or 76.8 kbps is set with DIP switches SW1-SW4; the Communications Selection jumper picks RS-485 or BACnet over ARC156 (156 kbps).
- The device instance is auto-generated with the address as its last two digits; for more than 99 units turn off 'Auto Generate Device ID' in the Equipment Touch tool and enter it there.
- The same port can run N2 or Modbus instead of BACnet; the protocol is chosen with the same switches.
Watch out for
- Heating setpoint objects (AV 21-24) only apply with DB Mode (BV 48) OFF.
- System Reset (BV 4) is not momentary; write ON, then OFF.
- Manual BVs (28-32) only act while Test Mode (BV 34) is on, which times out after 60 minutes.
- RNet Mode (BV 44) must match the wall sensor type and the W3 jumper.
ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | Actual CL Setpoint | Cooling setpoint in use (occupancy, adjust, units applied) | °F / °C | Read | |
| AV | 2 | Actual HT Setpoint | Heating setpoint in use (occupancy, adjust, units applied) | °F / °C | Read | |
| AVmin | 3 | Occupied CL SP/ Fahrenheit | Occupied cooling setpoint, °F | °F | Write | |
| AV | 4 | Master ZT/ Fahrenheit | Shared zone temperature for follower units, °F | °F | Write | |
| AV | 5 | Occupied Deadband/ Fahrenheit | Occupied heat/cool deadband in DB mode, min 2 °F | °F | Write | |
| AV | 6 | Pulse Signal Value | Last fault code from the CXM2/DXM2.6 board | Read | ||
| AV | 7 | Unoccupied CL SP/ Fahrenheit | Unoccupied cooling setpoint, °F | °F | Write | |
| AV | 8 | Override Time Remaining | Obsolete (Gen 3 and Gen 4 only) | Read | ||
| AV | 9 | Subordinate HT SP/ Fahrenheit | Heating setpoint from the leader unit, °F | °F | Write | |
| AV | 10 | Subordinate CL SP/ Fahrenheit | Cooling setpoint from the leader unit, °F | °F | Write | |
| AV | 11 | HP Fault Counter | High pressure faults since start or reset | Read | ||
| AV | 12 | LP Fault Counter | Low pressure faults since start or reset | Read | ||
| AV | 13 | LT1 Fault Counter | Liquid temperature 1 faults since start or reset | Read | ||
| AV | 14 | LT2 Fault Counter | Liquid temperature 2 faults since start or reset | Read | ||
| AV | 15 | CO Fault Counter | Condensate overflow faults since start or reset | Read | ||
| AV | 16 | Over/Under Voltage Fault Counter | Over/under voltage faults since start or reset | Read | ||
| AV | 17 | UPS Fault Counter | UPS faults since start or reset | Read | ||
| AV | 18 | Swapped LT1/LT2 Fault Counter | Swapped LT1/LT2 faults since start or reset | Read | ||
| AV | 19 | C1 Cycle Counter | Times C1 cycled over 6 times in an hour | Read | ||
| AV | 20 | C2 Cycle Counter | Times C2 cycled over 6 times in an hour | Read | ||
| AVmin | 21 | Occupied HT Setpoint | Occupied heating setpoint, °F | °F | Write | |
| AV | 22 | Occupied HT Setpoint Celsius | Occupied heating setpoint, °C | °C | Write | |
| AV | 23 | Unoccupied HT Setpoint | Unoccupied heating setpoint, °F | °F | Write | |
| AV | 24 | Unoccupied HT Setpoint Celsius | Unoccupied heating setpoint, °C | °C | Write | |
| AV | 28 | HT PID | Heating PID output | % | Read | |
| AV | 29 | CL PID | Cooling PID output | % | Read | |
| AV | 30 | Dirty Filter Interval | Fan hours before the dirty filter alarm; default 1500 | h | Write | |
| AV | 31 | AUX CFG | AUX (W) output function code | Write | ||
| AV | 32 | TSTAT Mode | Temperature control method (Gen 3 hardware) | Write | ||
| AV | 33 | SF CFG | Supply fan configuration | Write | ||
| AVmin | 34 | Zone Temp Status | Space temperature | °F / °C | Read | |
| AV | 35 | LVG Air Temp Status | Leaving air temperature | °F / °C | Read | |
| AV | 36 | LVG Water Temp Status | Leaving water temperature | °F / °C | Read | |
| AV | 37 | Manual SP Adjust | Setpoint adjust range at the wall sensor, °F | °F | Write | |
| AV | 38 | Master ZT Celsius | Shared zone temperature for follower units, °C | °C | Write | |
| AV | 39 | Unoccupied CL SP Celsius | Unoccupied cooling setpoint, °C | °C | Write | |
| AV | 40 | Occupied Deadband Celsius | Occupied heat/cool deadband in DB mode, °C | °C | Write | |
| AV | 41 | Subordinate CL Setpoint Celsius | Cooling setpoint from the leader unit, °C | °C | Write | |
| AV | 42 | Subordinate HT Setpoint Celsius | Heating setpoint from the leader unit, °C | °C | Write | |
| AV | 43 | Occupied CL SP Celsius | Occupied cooling setpoint, °C | °C | Write | |
| AV | 44 | Manual Setpoint Adj Celsius | Setpoint adjust range at the wall sensor, °C | °C | Write | |
| AV | 45 | Unoccupied Deadband | Unoccupied heat/cool deadband in DB mode, °F | °F | Write | |
| AV | 46 | Unoccupied Deadband Celsius | Unoccupied heat/cool deadband in DB mode, °C | °C | Write | |
| AV | 47 | Relative Humidity Setpoint | RH above which AUX turns on (AUX CFG 12) | % | Write | |
| AV | 48 | Relative Humidity Deadband | RH deadband for humidity control (AUX CFG 12) | % | Write | |
| AV | 49 | Relative Humidity Status | Space relative humidity | % | Read | |
| AV | 50 | Aux 5 Temp | Auxiliary input 5 temperature (RNet mode) | °F / °C | Read | |
| AV | 51 | Aux 6 Temp | Auxiliary input 6 temperature (RNet mode) | °F / °C | Read | |
| AV | 52 | CO2 Status | Space CO2 | ppm | Read | |
| AV | 53 | VOC Status | Space VOC level | ppm | Read | |
| AV | 54 | CO2 Trip point | CO2 level that turns AUX on (AUX CFG 13) | ppm | Write | |
| AV | 55 | VCO Trip point | VOC level that turns AUX on (AUX CFG 14) | ppm | Write | |
| AV | 56 | FAN Speed Trigger | PID level that switches AUX high fan (AUX CFG 5) | % | Write | |
| AV | 57 | Airflow Fault Counter | Airflow faults since start or reset | Read | ||
| AV | 58 | Pump Fault Counter | Pump faults since start or reset | Read | ||
| AV | 59 | Load Balance Select Mode | Compressor sequencing / runtime balancing mode | Write | ||
| AV | 99 | Application Type | Factory use only | Read | ||
| BVmin | 1 | Alarm State | Lockout condition present | Read | OFF=Normal, ON=Lockout | |
| BV | 2 | C1 Reset | Reset the C1 runtime alarm | Write | ||
| BVmin | 3 | C1 Status | Compressor 1 on/off | Read | ||
| BVmin | 4 | System Reset | Lockout reset; set ON then OFF | Write | ||
| BV | 5 | C2 Reset | Reset the C2 runtime alarm | Write | ||
| BV | 6 | C2 Status | Compressor 2 on/off | Read | ||
| BV | 7 | Dirty Filter Reset | Reset the dirty filter alarm | Write | ||
| BVmin | 8 | Emergency Shutdown | Emergency stop: Y1, Y2, G and W relays off | Write | OFF=Normal, ON=Shutdown | |
| BV | 9 | Supply Fan Operational Mode | Fan auto/on (Gen 2-4 only) | Read | OFF=Auto, ON=On | |
| BVmin | 10 | SF Status | Supply fan on/off | Read | ||
| BV | 11 | Occupied Status | Occupied state | Read | OFF=Unoccupied, ON=Occupied | |
| BVmin | 12 | Occupied Mode | Occupancy command; default ON | Write | OFF=Unoccupied, ON=Occupied | |
| BV | 13 | RV Status | Reversing valve on/off | Read | ||
| BV | 14 | Work Schedule | Schedule from the BMS sets occupied/unoccupied | Write | OFF=Unoccupied, ON=Occupied | |
| BV | 15 | UPS Signal | UPS mode on/off (see CXM2/DXM2.6 manual) | Read | ||
| BV | 16 | M/S Switch | Leader (OFF) or follower sharing a sensor (ON) | Write | OFF=Leader, ON=Follower | |
| BV | 17 | C1 Runtime Alarm | C1 run hours over 5000; reset with BV 2 | Read | ||
| BV | 18 | C2 Runtime Alarm | C2 run hours over 5000; reset with BV 5 | Read | ||
| BV | 19 | Dirty Filter Alarm | Fan hours past the dirty filter interval | Read | ||
| BV | 20 | Valid Sensor Alarm | No valid room sensor connected | Read | ||
| BV | 21 | C1 Cycle Reset | Reset the C1 cycle counter | Write | ||
| BV | 22 | C2 Cycle Reset | Reset the C2 cycle counter | Write | ||
| BV | 23 | Lockout Alarm | CXM2/DXM2.6 board in lockout | Read | ||
| BV | 24 | Fault Counter Reset | Reset all fault counters | Write | ||
| BV | 25 | C1 Cycle Alarm | C1 cycled more than 5 times in an hour | Read | ||
| BV | 26 | C2 Cycle Alarm | C2 cycled more than 5 times in an hour | Read | ||
| BV | 27 | AUX Status | AUX (W) output on/off | Read | ||
| BV | 28 | SF Manual | Supply fan on/off in test mode | Write | ||
| BV | 29 | RV Manual | Reversing valve on/off in test mode | Write | ||
| BV | 30 | C1 Manual | Compressor 1 on/off in test mode | Write | ||
| BV | 31 | C2 Manual | Compressor 2 on/off in test mode | Write | ||
| BV | 32 | AUX Manual | AUX (W) output on/off in test mode | Write | ||
| BV | 33 | TStat Reset | Obsolete (Gen 5 only) | Write | ||
| BV | 34 | Test Mode | Manual test mode, 60 min maximum | Write | ||
| BV | 38 | Test Mode Alarm | Unit still in test mode after the timer | Read | ||
| BV | 39 | Metric | Engineering units for inputs and outputs | Write | OFF=Fahrenheit, ON=Celsius | |
| BV | 40 | AUX Toggle | Switch AUX output when AUX CFG = 11 | Write | ||
| BV | 41 | Air Duct Mode | Control on return duct temperature (Aux 5) | Write | ||
| BV | 42 | AUX5 | Aux input 5 binary state (RNet mode) | Read | ||
| BV | 43 | AUX6 | Aux input 6 binary state (RNet mode) | Read | ||
| BV | 44 | RNet Mode | Communicating (ON) or LStat (OFF) wall sensors | Write | OFF=LStat, ON=RNet | |
| BV | 45 | Humidity Occupancy | Enable humidity control when AUX CFG = 12 | Write | ||
| BV | 46 | Aux 5 Config | Aux input 5 type | Write | OFF=Binary, ON=Temperature | |
| BV | 47 | Aux 6 Config | Aux input 6 type | Write | OFF=Binary, ON=Temperature | |
| BV | 48 | DB Mode | Deadband setpoint mode | Write | OFF=Separate setpoints, ON=Cooling SP + deadband | |
| BV | 49 | CO2 Alarm | CO2 above the trip point | Read | ||
| BV | 50 | VOC Alarm | VOC above the trip point | Read | ||
| BV | 51 | Fan Speed Enable | High fan via AUX when AUX CFG = 5 | Write | ||
| BV | 53 | Compressor Shutdown | Disable both compressors | Write | OFF=Enabled, ON=Disabled | |
| BV | 54 | Cooling Mode | Cooling enable | Write | OFF=Disabled, ON=Enabled | |
| BV | 57 | Electric Heat Mode | Full-time electric heat via AUX | Read | OFF=Heat pump, ON=Electric heat | |
| BV | 58 | Electric Heat Demand | Heat demand in full-time electric heat mode | Read | ||
| BV | 59 | Ext Occ/Dirty Filt Sens | BI 8 use: motion sensor or filter switch | Read | OCC=Occupancy, DFS=Dirty filter sense | |
| BV | 60 | Dirty Filter Mode | Dirty filter by time or pressure switch | Write | TIME, DFS | |
| BV | 61 | Heating Mode | Heating enable | Write | OFF=Disabled, ON=Enabled | |
| BV | 62 | Archive Enable | Archive the current control program | Write | ||
| BV | 63 | RNet Sensor 1 Enable | Expect RNet sensor 1 (enables its alarm) | Write | ||
| BV | 64 | RNet Sensor 2 Enable | Expect RNet sensor 2 (enables its alarm) | Write | ||
| BV | 65 | RNet Sensor 3 Enable | Expect RNet sensor 3 (enables its alarm) | Write | ||
| BV | 66 | RNet Sensor 4 Enable | Expect RNet sensor 4 (enables its alarm) | Write | ||
| BV | 67 | RNet Sensor 5 Enable | Expect RNet sensor 5 (enables its alarm) | Write | ||
| BV | 68 | EQ Touch Temp Enable | Use Equipment Touch sensor for space temperature | Write | ||
| MVmin | 1 | Fault | Current alarm as text | Read | ||
| MV | 2 | AUX Config Status | AUX output configuration as text | Read | ||
| MV | 3 | Zone Mode Status | Current operating mode as text | Read | ||
| MV | 10 | Archive Status | Status of the program archive process | Read |
No points match these filters.
Object ID lookup: ClimateMaster MPC Water-to-Air point IDs by name
AV1Actual CL SetpointAV2Actual HT SetpointAV3Occupied CL SP/ FahrenheitAV4Master ZT/ FahrenheitAV5Occupied Deadband/ FahrenheitAV6Pulse Signal ValueAV7Unoccupied CL SP/ FahrenheitAV8Override Time RemainingAV9Subordinate HT SP/ FahrenheitAV10Subordinate CL SP/ FahrenheitAV11HP Fault CounterAV12LP Fault CounterAV13LT1 Fault CounterAV14LT2 Fault CounterAV15CO Fault CounterAV16Over/Under Voltage Fault CounterAV17UPS Fault CounterAV18Swapped LT1/LT2 Fault CounterAV19C1 Cycle CounterAV20C2 Cycle CounterAV21Occupied HT SetpointAV22Occupied HT Setpoint CelsiusAV23Unoccupied HT SetpointAV24Unoccupied HT Setpoint CelsiusAV28HT PIDAV29CL PIDAV30Dirty Filter IntervalAV31AUX CFGAV32TSTAT ModeAV33SF CFGAV34Zone Temp StatusAV35LVG Air Temp StatusAV36LVG Water Temp StatusAV37Manual SP AdjustAV38Master ZT CelsiusAV39Unoccupied CL SP CelsiusAV40Occupied Deadband CelsiusAV41Subordinate CL Setpoint CelsiusAV42Subordinate HT Setpoint CelsiusAV43Occupied CL SP CelsiusAV44Manual Setpoint Adj CelsiusAV45Unoccupied DeadbandAV46Unoccupied Deadband CelsiusAV47Relative Humidity SetpointAV48Relative Humidity DeadbandAV49Relative Humidity StatusAV50Aux 5 TempAV51Aux 6 TempAV52CO2 StatusAV53VOC StatusAV54CO2 Trip pointAV55VCO Trip pointAV56FAN Speed TriggerAV57Airflow Fault CounterAV58Pump Fault CounterAV59Load Balance Select ModeAV99Application TypeBV1Alarm StateBV2C1 ResetBV3C1 StatusBV4System ResetBV5C2 ResetBV6C2 StatusBV7Dirty Filter ResetBV8Emergency ShutdownBV9Supply Fan Operational ModeBV10SF StatusBV11Occupied StatusBV12Occupied ModeBV13RV StatusBV14Work ScheduleBV15UPS SignalBV16M/S SwitchBV17C1 Runtime AlarmBV18C2 Runtime AlarmBV19Dirty Filter AlarmBV20Valid Sensor AlarmBV21C1 Cycle ResetBV22C2 Cycle ResetBV23Lockout AlarmBV24Fault Counter ResetBV25C1 Cycle AlarmBV26C2 Cycle AlarmBV27AUX StatusBV28SF ManualBV29RV ManualBV30C1 ManualBV31C2 ManualBV32AUX ManualBV33TStat ResetBV34Test ModeBV38Test Mode AlarmBV39MetricBV40AUX ToggleBV41Air Duct ModeBV42AUX5BV43AUX6BV44RNet ModeBV45Humidity OccupancyBV46Aux 5 ConfigBV47Aux 6 ConfigBV48DB ModeBV49CO2 AlarmBV50VOC AlarmBV51Fan Speed EnableBV53Compressor ShutdownBV54Cooling ModeBV57Electric Heat ModeBV58Electric Heat DemandBV59Ext Occ/Dirty Filt SensBV60Dirty Filter ModeBV61Heating ModeBV62Archive EnableBV63RNet Sensor 1 EnableBV64RNet Sensor 2 EnableBV65RNet Sensor 3 EnableBV66RNet Sensor 4 EnableBV67RNet Sensor 5 EnableBV68EQ Touch Temp EnableMV1FaultMV2AUX Config StatusMV3Zone Mode StatusMV10Archive Status
Integration notes
- Points list from the MPC manual's points matrix; the same table also gives Modbus registers and N2 IDs.
- Temperatures follow BV 39 Metric (OFF = °F); some setpoints have separate °F and °C objects.
- Heating setpoints AV 21-24 apply when DB Mode (BV 48) is OFF; with DB Mode ON the heating setpoint is the cooling setpoint minus the deadband (AV 5/40/45/46).
- Several points are obsolete (AV 8, BV 33) or only for older generations (AV 32, BV 9).
- BV 9 and BV 59 have no access marked in the source; they are listed here as read-only.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)
How many BACnet points does the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) have?
This list has 123 BACnet objects: 57 analog values, 62 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) BACnet points are writable?
68 of the 123 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer) BACnet documentation?
The source is MPC Multi-Protocol DDC Controls - Application, Operation & Maintenance Manual (97B0031N01), revision 2025-12-11, published free by ClimateMaster at https://files.climatemaster.com/97b0031n01-climatemaster-mpc-multiprotocol-ddc-controls-water-source-heat-pump-application-manual.pdf.
What are the minimum BACnet points to integrate the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)?
Start with BV 12 Occupied Mode (Occupancy command (ON = occupied)); BV 8 Emergency Shutdown (Emergency stop; ON turns Y1, Y2, G and W off); AV 3 Occupied CL SP/ Fahrenheit (Occupied cooling setpoint, °F); AV 21 Occupied HT Setpoint (Occupied heating setpoint, °F (DB Mode off)); BV 4 System Reset (Lockout reset; set ON then back OFF); BV 10 SF Status (Supply fan running); BV 3 C1 Status (Compressor 1 running); AV 34 Zone Temp Status (Space temperature); BV 1 Alarm State (Lockout condition (ON = lockout)); MV 1 Fault (Current alarm as text).
How do I enable BMS control of the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)?
Stand-alone, the MPC defaults to occupied. BV 12 Occupied Mode (default ON) sets occupied/unoccupied from the BMS; BV 14 Work Schedule can take a BMS schedule instead. BV 8 Emergency Shutdown turns the Y1, Y2, G and W outputs off. BV 53 Compressor Shutdown disables both compressors, and BV 61/BV 54 disable heating or cooling.
Can the BMS supply sensor values to the ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)?
For units sharing one wall sensor, set BV 16 M/S Switch ON on each follower and map the leader's Zone Temp Status (AV 34), Actual HT/CL setpoints (AV 2, AV 1) and Occupied Status (BV 11) to the follower's Master ZT (AV 4), Subordinate HT/CL SP (AV 9, AV 10) and Occupied Mode (BV 12).
How do I check these points on the real MPC Multi-Protocol DDC Controller - Water-to-Air (Gen 7 and newer)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More ClimateMaster BACnet points lists
- DOAS (dedicated outdoor air system) controller
ClimateMaster Commercial DOAS with CM3500 controller
ClimateMaster commercial dedicated outdoor air units with the CM3500 controller, program version 3.2.0 and later.
Also known as: CM3500, ClimateMaster DOAS, DOAS CM3500 Controller, 97B0065N01 - Water-to-water heat pump controller
ClimateMaster MPC Multi-Protocol DDC Controller - Water-to-Water (Gen 8 and newer)
ClimateMaster water-to-water heat pumps with the MPC controller, Gen 8 and newer.
Also known as: MPC, ClimateMaster MPC, 97B0031N01, Multi-Protocol Controller, CXM2, DXM2.6 - Modular water-to-water heat pump
ClimateMaster Tranquility Large Water-to-Water (SWT) 20-80 ton
ClimateMaster Tranquility Large Water-to-Water (SWT) modules, 20-80 tons, R-454B, with the factory module controller.
Also known as: SWT, Tranquility SWT, ClimateMaster SWT R-454B, ClimateMaster large water-to-water BACnet, C97B0004N07 - Modular water-to-water heat pump
ClimateMaster Tranquility Large Water-to-Water (TMW) 360-840
ClimateMaster Tranquility Large Water-to-Water (TMW) modules, models 360-840, with the factory IO FLEX6126 + EX8160 controller.
Also known as: TMW, TMW360, TMW600, TMW840, Tranquility TMW, ClimateMaster modular water-to-water BACnet, IO FLEX6126, 97B0090N01
Source: MPC Multi-Protocol DDC Controls - Application, Operation & Maintenance Manual · 97B0031N01 · rev. 2025-12-11. Object names, instances and units are reproduced as published; descriptions are our own.