Kitchen hood demand control ventilation (DCV) controller (exhaust and make-up air fans) · BACnet points list
CaptiveAire DCV Package DDC (Protocessor BACnet) BACnet points list
Updated 28 October 2026
CaptiveAire DCV packages start and modulate kitchen hood exhaust and supply fans from temperature, occupancy, buttons, inputs or the BMS. BACnet IP or MS/TP comes from a factory-mounted Protocessor gateway in the electrical control panel, set at the factory for one of the two. The 231 objects are mostly read-only: 32 temperature sensors, zone and HMI readings, VFD frequency/current/power/fault for up to 8 exhaust and 2 supply fans, 'fans on by' and 'lights on by' reason flags, CORE fire-system fault codes, PCU filter monitoring and per-zone faults. Ten writable BVs carry the names of the panel's Prep Time, Fans On, Wash, Lights and Max Air buttons for two zones.
This page lists 231 BACnet objects for the CaptiveAire DCV Package DDC (Protocessor BACnet) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CaptiveAire’s own free documentation, linked below.
- Manufacturer
- CaptiveAire
- Model
- DCV Package DDC (Protocessor BACnet)
- Equipment
- Kitchen hood demand control ventilation (DCV) controller (exhaust and make-up air fans)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 231 (10 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 50000
- Also known as
- CaptiveAire DCV, Demand Control Ventilation, DCV Packages Network, Kitchen hood DCV, CASlink, Protocessor, CN0861
Reference only, provided as-is: verify against CaptiveAire’s current documentation and the live device before use. Not official CaptiveAire information. Terms of use.
BMS integration notes: CaptiveAire DCV Package DDC (Protocessor BACnet)
Most DCV integrations are monitoring: map the zone temperatures, the fan VFD readings, the fans-on-by-BMS flags and the fire, fault and Modbus fault points. The only writable objects are the per-zone button BVs (Prep Time, Fans On, Wash, Lights, Max Air); the guide does not describe their behaviour, so test a write and watch the matching Zone-FansONbyBMS / LightsONbyBMS flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 223 | FansONButtonZone1 | Zone 1 fans button; write effect not described in guide | Write |
| BI 94 | Zone1-FansONbyBMS | Confirms zone 1 fans are on by BMS command | Read |
| AI 33 | Temperature Zone 1 | Zone 1 temperature, °F | Read |
| AI 48 | VFD Frequency Exhaust 1 | Exhaust fan 1 drive speed, Hz | Read |
| AI 56 | VFD Frequency Supply 1 | Supply (make-up air) fan 1 drive speed, Hz | Read |
| BI 189 | DCVFireZone1 | Fire system tripped, zone 1 | Read |
| AI 78 | VFD Fault Exhaust 1 | Exhaust fan 1 drive fault | Read |
| AI 132 | ErrorCOREBoard1 | Fire system fault code; highest-priority fault shown | Read |
| AI 221 | ModbusFaultCode | Modbus fault code; codes not listed in the guide | Read |
Network setup
- Protocessor default device instance 50000, MS/TP MAC 127, 38400 baud, Max Master 127.
- Protocessor default IP 192.168.1.24 /255.255.255.0; web configurator login admin/admin (or the password printed by the Ethernet port).
- The gateway is factory set to either BACnet IP or MS/TP for the job; objects are only reachable on that port.
- Each changed gateway parameter needs its own Submit and a system restart.
Watch out for
- COV is off by default (bac_cov_option = COV_Disable), so poll or enable COV.
- The controller board reboots when some factory settings are changed.
- ErrorCOREBoard AIs show only the highest-priority active fault; Fire wins over all others.
- Temperatures are listed in °F.
CaptiveAire DCV Package DDC (Protocessor BACnet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Temperature Sensor 1 | Temperature sensor 1 reading | °F | Read | |
| AI | 2 | Temperature Sensor 2 | Temperature sensor 2 reading | °F | Read | |
| AI | 3 | Temperature Sensor 3 | Temperature sensor 3 reading | °F | Read | |
| AI | 4 | Temperature Sensor 4 | Temperature sensor 4 reading | °F | Read | |
| AI | 5 | Temperature Sensor 5 | Temperature sensor 5 reading | °F | Read | |
| AI | 6 | Temperature Sensor 6 | Temperature sensor 6 reading | °F | Read | |
| AI | 7 | Temperature Sensor 7 | Temperature sensor 7 reading | °F | Read | |
| AI | 8 | Temperature Sensor 8 | Temperature sensor 8 reading | °F | Read | |
| AI | 9 | Temperature Sensor 9 | Temperature sensor 9 reading | °F | Read | |
| AI | 10 | Temperature Sensor 10 | Temperature sensor 10 reading | °F | Read | |
| AI | 11 | Temperature Sensor 11 | Temperature sensor 11 reading | °F | Read | |
| AI | 12 | Temperature Sensor 12 | Temperature sensor 12 reading | °F | Read | |
| AI | 13 | Temperature Sensor 13 | Temperature sensor 13 reading | °F | Read | |
| AI | 14 | Temperature Sensor 14 | Temperature sensor 14 reading | °F | Read | |
| AI | 15 | Temperature Sensor 15 | Temperature sensor 15 reading | °F | Read | |
| AI | 16 | Temperature Sensor 16 | Temperature sensor 16 reading | °F | Read | |
| AI | 17 | Temperature Sensor 17 | Temperature sensor 17 reading | °F | Read | |
| AI | 18 | Temperature Sensor 18 | Temperature sensor 18 reading | °F | Read | |
| AI | 19 | Temperature Sensor 19 | Temperature sensor 19 reading | °F | Read | |
| AI | 20 | Temperature Sensor 20 | Temperature sensor 20 reading | °F | Read | |
| AI | 21 | Temperature Sensor 21 | Temperature sensor 21 reading | °F | Read | |
| AI | 22 | Temperature Sensor 22 | Temperature sensor 22 reading | °F | Read | |
| AI | 23 | Temperature Sensor 23 | Temperature sensor 23 reading | °F | Read | |
| AI | 24 | Temperature Sensor 24 | Temperature sensor 24 reading | °F | Read | |
| AI | 25 | Temperature Sensor 25 | Temperature sensor 25 reading | °F | Read | |
| AI | 26 | Temperature Sensor 26 | Temperature sensor 26 reading | °F | Read | |
| AI | 27 | Temperature Sensor 27 | Temperature sensor 27 reading | °F | Read | |
| AI | 28 | Temperature Sensor 28 | Temperature sensor 28 reading | °F | Read | |
| AI | 29 | Temperature Sensor 29 | Temperature sensor 29 reading | °F | Read | |
| AI | 30 | Temperature Sensor 30 | Temperature sensor 30 reading | °F | Read | |
| AI | 31 | Temperature Sensor 31 | Temperature sensor 31 reading | °F | Read | |
| AI | 32 | Temperature Sensor 32 | Temperature sensor 32 reading | °F | Read | |
| AImin | 33 | Temperature Zone 1 | Zone 1 temperature | °F | Read | |
| AI | 34 | Temperature Zone 2 | Zone 2 temperature | °F | Read | |
| AI | 35 | Temperature HMI 1 | Temperature at HMI 1 | °F | Read | |
| AI | 36 | Temperature HMI 2 | Temperature at HMI 2 | °F | Read | |
| AI | 37 | Temperature HMI 3 | Temperature at HMI 3 | °F | Read | |
| AI | 38 | Temperature HMI 4 | Temperature at HMI 4 | °F | Read | |
| AI | 39 | Humidity HMI 1 | Relative humidity at HMI 1 | Read | ||
| AI | 40 | Humidity HMI 2 | Relative humidity at HMI 2 | Read | ||
| AI | 41 | Humidity HMI 3 | Relative humidity at HMI 3 | Read | ||
| AI | 42 | Humidity HMI 4 | Relative humidity at HMI 4 | Read | ||
| AI | 43 | ECMOutput1 | ECM fan output 1 | Read | ||
| AI | 44 | ECMOutput2 | ECM fan output 2 | Read | ||
| AI | 45 | ECMOutput3 | ECM fan output 3 | Read | ||
| AI | 46 | ECMOutput4 | ECM fan output 4 | Read | ||
| AI | 47 | VDCOutput | DC voltage output value | Read | ||
| AImin | 48 | VFD Frequency Exhaust 1 | Exhaust fan 1 drive frequency | Hz | Read | |
| AI | 49 | VFD Frequency Exhaust 2 | Exhaust fan 2 drive frequency | Hz | Read | |
| AI | 50 | VFD Frequency Exhaust 3 | Exhaust fan 3 drive frequency | Hz | Read | |
| AI | 51 | VFD Frequency Exhaust 4 | Exhaust fan 4 drive frequency | Hz | Read | |
| AI | 52 | VFD Frequency Exhaust 5 | Exhaust fan 5 drive frequency | Hz | Read | |
| AI | 53 | VFD Frequency Exhaust 6 | Exhaust fan 6 drive frequency | Hz | Read | |
| AI | 54 | VFD Frequency Exhaust 7 | Exhaust fan 7 drive frequency | Hz | Read | |
| AI | 55 | VFD Frequency Exhaust 8 | Exhaust fan 8 drive frequency | Hz | Read | |
| AImin | 56 | VFD Frequency Supply 1 | Supply fan 1 drive frequency | Hz | Read | |
| AI | 57 | VFD Frequency Supply 2 | Supply fan 2 drive frequency | Hz | Read | |
| AI | 58 | VFD Amperage Exhaust 1 | Exhaust fan 1 drive current | A | Read | |
| AI | 59 | VFD Amperage Exhaust 2 | Exhaust fan 2 drive current | A | Read | |
| AI | 60 | VFD Amperage Exhaust 3 | Exhaust fan 3 drive current | A | Read | |
| AI | 61 | VFD Amperage Exhaust 4 | Exhaust fan 4 drive current | A | Read | |
| AI | 62 | VFD Amperage Exhaust 5 | Exhaust fan 5 drive current | A | Read | |
| AI | 63 | VFD Amperage Exhaust 6 | Exhaust fan 6 drive current | A | Read | |
| AI | 64 | VFD Amperage Exhaust 7 | Exhaust fan 7 drive current | A | Read | |
| AI | 65 | VFD Amperage Exhaust 8 | Exhaust fan 8 drive current | A | Read | |
| AI | 66 | VFD Amperage Supply 1 | Supply fan 1 drive current | A | Read | |
| AI | 67 | VFD Amperage Supply 2 | Supply fan 2 drive current | A | Read | |
| AI | 68 | VFD Power Usage Exhaust 1 | Exhaust fan 1 drive power | kW | Read | |
| AI | 69 | VFD Power Usage Exhaust 2 | Exhaust fan 2 drive power | kW | Read | |
| AI | 70 | VFD Power Usage Exhaust 3 | Exhaust fan 3 drive power | kW | Read | |
| AI | 71 | VFD Power Usage Exhaust 4 | Exhaust fan 4 drive power | kW | Read | |
| AI | 72 | VFD Power Usage Exhaust 5 | Exhaust fan 5 drive power | kW | Read | |
| AI | 73 | VFD Power Usage Exhaust 6 | Exhaust fan 6 drive power | kW | Read | |
| AI | 74 | VFD Power Usage Exhaust 7 | Exhaust fan 7 drive power | kW | Read | |
| AI | 75 | VFD Power Usage Exhaust 8 | Exhaust fan 8 drive power | kW | Read | |
| AI | 76 | VFD Power Usage Supply 1 | Supply fan 1 drive power | kW | Read | |
| AI | 77 | VFD Power Usage Supply 2 | Supply fan 2 drive power | kW | Read | |
| AImin | 78 | VFD Fault Exhaust 1 | Exhaust fan 1 drive fault value | Read | ||
| AI | 79 | VFD Fault Exhaust 2 | Exhaust fan 2 drive fault value | Read | ||
| AI | 80 | VFD Fault Exhaust 3 | Exhaust fan 3 drive fault value | Read | ||
| AI | 81 | VFD Fault Exhaust 4 | Exhaust fan 4 drive fault value | Read | ||
| AI | 82 | VFD Fault Exhaust 5 | Exhaust fan 5 drive fault value | Read | ||
| AI | 83 | VFD Fault Exhaust 6 | Exhaust fan 6 drive fault value | Read | ||
| AI | 84 | VFD Fault Exhaust 7 | Exhaust fan 7 drive fault value | Read | ||
| AI | 85 | VFD Fault Exhaust 8 | Exhaust fan 8 drive fault value | Read | ||
| AI | 86 | VFD Fault Supply 1 | Supply fan 1 drive fault value | Read | ||
| AI | 87 | VFD Fault Supply 2 | Supply fan 2 drive fault value | Read | ||
| BI | 88 | Zone1-FansONbyProving | Zone 1 fans on by fan proving | Read | ||
| BI | 89 | Zone1-FansONbyBypass | Zone 1 fans on by bypass | Read | ||
| BI | 90 | Zone1-FansONbyIO1HighSpeed | Zone 1 fans on by IO1 high-speed input | Read | ||
| BI | 91 | Zone1-FansONbyMaxAir | Zone 1 fans on by Max Air | Read | ||
| BI | 92 | Zone1-FansONbyTemperature | Zone 1 fans on by temperature | Read | ||
| BI | 93 | Zone1-FansONbyOccupancy | Zone 1 fans on by occupied schedule | Read | ||
| BImin | 94 | Zone1-FansONbyBMS | Zone 1 fans on by BMS command | Read | ||
| BI | 95 | Zone1-FansONbyIO1 | Zone 1 fans on by IO1 input | Read | ||
| BI | 96 | Zone1-FansONbyButton | Zone 1 fans on by panel button | Read | ||
| BI | 97 | Zone1-FansONbyHRC | Zone 1 fans on by HRC | Read | ||
| BI | 98 | Zone1-FansONbyWash | Zone 1 fans on by wash | Read | ||
| BI | 99 | Zone1-FansONbyBMSPrep | Zone 1 fans on by BMS prep time | Read | ||
| BI | 100 | Zone1-FansONbyButtonPrep | Zone 1 fans on by button prep time | Read | ||
| BI | 101 | Zone1-FansONbyTemperaturePrep | Zone 1 fans on by temperature prep time | Read | ||
| BI | 102 | Zone2-FansONbyProving | Zone 2 fans on by fan proving | Read | ||
| BI | 103 | Zone2-FansONbyBypass | Zone 2 fans on by bypass | Read | ||
| BI | 104 | Zone2-FansONbyIO1HighSpeed | Zone 2 fans on by IO1 high-speed input | Read | ||
| BI | 105 | Zone2-FansONbyMaxAir | Zone 2 fans on by Max Air | Read | ||
| BI | 106 | Zone2-FansONbyTemperature | Zone 2 fans on by temperature | Read | ||
| BI | 107 | Zone2-FansONbyOccupancy | Zone 2 fans on by occupied schedule | Read | ||
| BI | 108 | Zone2-FansONbyBMS | Zone 2 fans on by BMS command | Read | ||
| BI | 109 | Zone2-FansONbyIO1 | Zone 2 fans on by IO1 input | Read | ||
| BI | 110 | Zone2-FansONbyButton | Zone 2 fans on by panel button | Read | ||
| BI | 111 | Zone2-FansONbyHRC | Zone 2 fans on by HRC | Read | ||
| BI | 112 | Zone2-FansONbyWash | Zone 2 fans on by wash | Read | ||
| BI | 113 | Zone2-FansONbyBMSPrep | Zone 2 fans on by BMS prep time | Read | ||
| BI | 114 | Zone2-FansONbyButtonPrep | Zone 2 fans on by button prep time | Read | ||
| BI | 115 | Zone2-FansONbyTemperaturePrep | Zone 2 fans on by temperature prep time | Read | ||
| BI | 116 | Zone1-LightsONbyWash | Zone 1 lights on by wash | Read | ||
| BI | 117 | Zone1-LightsONbyBypass | Zone 1 lights on by bypass | Read | ||
| BI | 118 | Zone1-LightsONbyBMS | Zone 1 lights on by BMS command | Read | ||
| BI | 119 | Zone1-LightsONbyButton | Zone 1 lights on by panel button | Read | ||
| BI | 120 | Zone1-LightsONbyOccupied | Zone 1 lights on by occupied schedule | Read | ||
| BI | 121 | Zone1-LightsONbyIO | Zone 1 lights on by IO input | Read | ||
| BI | 122 | Zone1-LightsONbyFansButton | Zone 1 lights on by fans button | Read | ||
| BI | 123 | Zone1-LightsONbyFansAutomatic | Zone 1 lights on by fans automatic | Read | ||
| BI | 124 | Zone2-LightsONbyWash | Zone 2 lights on by wash | Read | ||
| BI | 125 | Zone2-LightsONbyBypass | Zone 2 lights on by bypass | Read | ||
| BI | 126 | Zone2-LightsONbyBMS | Zone 2 lights on by BMS command | Read | ||
| BI | 127 | Zone2-LightsONbyButton | Zone 2 lights on by panel button | Read | ||
| BI | 128 | Zone2-LightsONbyOccupied | Zone 2 lights on by occupied schedule | Read | ||
| BI | 129 | Zone2-LightsONbyIO | Zone 2 lights on by IO input | Read | ||
| BI | 130 | Zone2-LightsONbyFansButton | Zone 2 lights on by fans button | Read | ||
| BI | 131 | Zone2-LightsONbyAutomatic | Zone 2 lights on by automatic (with fans) | Read | ||
| AImin | 132 | ErrorCOREBoard1 | CORE board 1 fire system fault code | Read | ||
| AI | 133 | ErrorCOREBoard2 | CORE board 2 fire system fault code | Read | ||
| AI | 134 | ErrorCOREBoard3 | CORE board 3 fire system fault code | Read | ||
| AI | 135 | ErrorCOREBoard4 | CORE board 4 fire system fault code | Read | ||
| AI | 136 | ErrorCOREBoard5 | CORE board 5 fire system fault code | Read | ||
| AI | 137 | ErrorCOREBoard6 | CORE board 6 fire system fault code | Read | ||
| AI | 138 | ErrorCOREBoard7 | CORE board 7 fire system fault code | Read | ||
| AI | 139 | ErrorCOREBoard8 | CORE board 8 fire system fault code | Read | ||
| AI | 140 | ErrorCOREBoard9 | CORE board 9 fire system fault code | Read | ||
| AI | 141 | ErrorCOREBoard10 | CORE board 10 fire system fault code | Read | ||
| AI | 142 | ErrorCOREBoard11 | CORE board 11 fire system fault code | Read | ||
| AI | 143 | ErrorCOREBoard12 | CORE board 12 fire system fault code | Read | ||
| AI | 144 | ErrorCOREBoard13 | CORE board 13 fire system fault code | Read | ||
| AI | 145 | ErrorCOREBoard14 | CORE board 14 fire system fault code | Read | ||
| AI | 146 | ErrorCOREBoard15 | CORE board 15 fire system fault code | Read | ||
| AI | 147 | PercentClogged_PCU1_Filter1 | PCU 1 filter 1 percent clogged | Read | ||
| AI | 148 | PercentClogged_PCU1_Filter2 | PCU 1 filter 2 percent clogged | Read | ||
| AI | 149 | PercentClogged_PCU1_Filter3 | PCU 1 filter 3 percent clogged | Read | ||
| AI | 150 | PercentClogged_PCU1_Filter4 | PCU 1 filter 4 percent clogged | Read | ||
| AI | 151 | PercentClogged_PCU1_Filter5 | PCU 1 filter 5 percent clogged | Read | ||
| BI | 152 | CloggedFilter_PCU1 | PCU 1 clogged filter | Read | ||
| BI | 153 | MissingFilter_PCU1 | PCU 1 missing filter | Read | ||
| BI | 154 | 72HourCloggedFilter_PCU1 | PCU 1 filter clogged for 72 hours | Read | ||
| BI | 155 | CloggedPCU_PCU1 | PCU 1 clogged | Read | ||
| BI | 156 | DoorMissing_PCU1 | PCU 1 door missing | Read | ||
| BI | 157 | NeedCalibration_PCU1 | PCU 1 needs calibration | Read | ||
| BI | 158 | 24HourCloggedFilter_PCU1 | PCU 1 filter clogged for 24 hours | Read | ||
| BI | 159 | ESPDoorMissing_PCU1 | PCU 1 ESP door missing | Read | ||
| BI | 160 | ESPDrainClogged_PCU1 | PCU 1 ESP drain clogged | Read | ||
| AI | 161 | PercentClogged_PCU2_Filter1 | PCU 2 filter 1 percent clogged | Read | ||
| AI | 162 | PercentClogged_PCU2_Filter2 | PCU 2 filter 2 percent clogged | Read | ||
| AI | 163 | PercentClogged_PCU2_Filter3 | PCU 2 filter 3 percent clogged | Read | ||
| AI | 164 | PercentClogged_PCU2_Filter4 | PCU 2 filter 4 percent clogged | Read | ||
| AI | 165 | PercentClogged_PCU2_Filter5 | PCU 2 filter 5 percent clogged | Read | ||
| BI | 166 | CloggedFilter_PCU2 | PCU 2 clogged filter | Read | ||
| BI | 167 | MissingFilter_PCU2 | PCU 2 missing filter | Read | ||
| BI | 168 | 72HourCloggedFilter_PCU2 | PCU 2 filter clogged for 72 hours | Read | ||
| BI | 169 | CloggedPCU_PCU2 | PCU 2 clogged | Read | ||
| BI | 170 | DoorMissing_PCU2 | PCU 2 door missing | Read | ||
| BI | 171 | NeedCalibration_PCU2 | PCU 2 needs calibration | Read | ||
| BI | 172 | ESPDoorMissing_PCU2 | PCU 2 ESP door missing | Read | ||
| BI | 173 | ESPDrainClogged_PCU2 | PCU 2 ESP drain clogged | Read | ||
| BI | 174 | 24HourCloggedFilter_PCU2 | PCU 2 filter clogged for 24 hours | Read | ||
| AI | 175 | PercentClogged_PCU3_Filter1 | PCU 3 filter 1 percent clogged | Read | ||
| AI | 176 | PercentClogged_PCU3_Filter2 | PCU 3 filter 2 percent clogged | Read | ||
| AI | 177 | PercentClogged_PCU3_Filter3 | PCU 3 filter 3 percent clogged | Read | ||
| AI | 178 | PercentClogged_PCU3_Filter4 | PCU 3 filter 4 percent clogged | Read | ||
| AI | 179 | PercentClogged_PCU3_Filter5 | PCU 3 filter 5 percent clogged | Read | ||
| BI | 180 | CloggedFilter_PCU3 | PCU 3 clogged filter | Read | ||
| BI | 181 | MissingFilter_PCU3 | PCU 3 missing filter | Read | ||
| BI | 182 | 72HourCloggedFilter_PCU3 | PCU 3 filter clogged for 72 hours | Read | ||
| BI | 183 | CloggedPCU_PCU3 | PCU 3 clogged | Read | ||
| BI | 184 | DoorMissing_PCU3 | PCU 3 door missing | Read | ||
| BI | 185 | NeedCalibration_PCU3 | PCU 3 needs calibration | Read | ||
| BI | 186 | 24HourCloggedFilter_PCU3 | PCU 3 filter clogged for 24 hours | Read | ||
| BI | 187 | ESPDoorMissing_PCU3 | PCU 3 ESP door missing | Read | ||
| BI | 188 | ESPDrainClogged_PCU3 | PCU 3 ESP drain clogged | Read | ||
| BImin | 189 | DCVFireZone1 | Fire system tripped, zone 1 | Read | ||
| BI | 190 | DCVAuxFaultZone1 | Auxiliary input fault, zone 1 | Read | ||
| BI | 191 | DCVFuseFaultZone1 | Board fuse fault, zone 1 | Read | ||
| BI | 192 | DCVKTSZone1 | KTS (kill tamper switch) tripped, zone 1 | Read | ||
| BI | 193 | DCVProvingFaultZone1 | Fan proving fault, zone 1 | Read | ||
| BI | 194 | DCVMUAInterlockErr1Zone1 | MUA interlock error 1, zone 1 | Read | ||
| BI | 195 | DCVMUAInterlockErr2Zone1 | MUA interlock error 2, zone 1 | Read | ||
| BI | 196 | DCVBrokenTempSensorZone1 | Broken temperature sensor, zone 1 | Read | ||
| BI | 197 | DCVMissingTempSensorZone1 | Missing temperature sensor, zone 1 | Read | ||
| BI | 198 | DCVOverloadZone1 | Overload 1 tripped, zone 1 | Read | ||
| BI | 199 | DCVOverload2Zone1 | Overload 2 tripped, zone 1 | Read | ||
| BI | 200 | DCVPCUFaultZone1 | PCU fault, zone 1 | Read | ||
| BI | 201 | DCVLightsEnergizedFaultZone1 | Lights energized fault (power seen when off), zone 1 | Read | ||
| BI | 202 | DCVLightsDeenergizedFaultZone1 | Lights de-energized fault (no power when on), zone 1 | Read | ||
| BI | 203 | DCVSurfactantLowZone1 | Surfactant low, zone 1 | Read | ||
| BI | 204 | DCVCheckAppliancePilotsZone1 | Check appliance pilots, zone 1 | Read | ||
| BI | 205 | DCVFireZone2 | Fire system tripped, zone 2 | Read | ||
| BI | 206 | DCVAuxFaultZone2 | Auxiliary input fault, zone 2 | Read | ||
| BI | 207 | DCVFuseFaultZone2 | Board fuse fault, zone 2 | Read | ||
| BI | 208 | DCVKTSZone2 | KTS (kill tamper switch) tripped, zone 2 | Read | ||
| BI | 209 | DCVProvingFaultZone2 | Fan proving fault, zone 2 | Read | ||
| BI | 210 | DCVMUAInterlockErr1Zone2 | MUA interlock error 1, zone 2 | Read | ||
| BI | 211 | DCVMUAInterlockErr2Zone2 | MUA interlock error 2, zone 2 | Read | ||
| BI | 212 | DCVBrokenTempSensorZone2 | Broken temperature sensor, zone 2 | Read | ||
| BI | 213 | DCVMissingTempSensorZone2 | Missing temperature sensor, zone 2 | Read | ||
| BI | 214 | DCVOverload1Zone2 | Overload 1 tripped, zone 2 | Read | ||
| BI | 215 | DCVOverload2Zone2 | Overload 2 tripped, zone 2 | Read | ||
| BI | 216 | DCVPCUFaultZone2 | PCU fault, zone 2 | Read | ||
| BI | 217 | DCVLightsEnergizedFaultZone2 | Lights energized fault (power seen when off), zone 2 | Read | ||
| BI | 218 | DCVLightsDeenergizedFaultZone2 | Lights de-energized fault (no power when on), zone 2 | Read | ||
| BI | 219 | DCVSurfactantLowZone2 | Surfactant low, zone 2 | Read | ||
| BI | 220 | DCVCheckAppliancePilotsZone2 | Check appliance pilots, zone 2 | Read | ||
| AImin | 221 | ModbusFaultCode | Modbus device communication fault code | Read | ||
| BV | 222 | PrepTimeButtonZone1 | Zone 1 Prep Time button | Write | ||
| BVmin | 223 | FansONButtonZone1 | Zone 1 Fans On button | Write | ||
| BV | 224 | WashButtonZone1 | Zone 1 Wash button | Write | ||
| BV | 225 | LightsButtonZone1 | Zone 1 Lights button | Write | ||
| BV | 226 | MaxAirZone1 | Zone 1 Max Air button | Write | ||
| BV | 227 | PrepTimeButtonZone2 | Zone 2 Prep Time button | Write | ||
| BV | 228 | FansONButtonZone2 | Zone 2 Fans On button | Write | ||
| BV | 229 | WashButtonZone2 | Zone 2 Wash button | Write | ||
| BV | 230 | LightsButtonZone2 | Zone 2 Lights button | Write | ||
| BV | 231 | MaxAirZone2 | Zone 2 Max Air button | Write |
No points match these filters.
Object ID lookup: CaptiveAire DCV Package DDC point IDs by name
AI1Temperature Sensor 1AI2Temperature Sensor 2AI3Temperature Sensor 3AI4Temperature Sensor 4AI5Temperature Sensor 5AI6Temperature Sensor 6AI7Temperature Sensor 7AI8Temperature Sensor 8AI9Temperature Sensor 9AI10Temperature Sensor 10AI11Temperature Sensor 11AI12Temperature Sensor 12AI13Temperature Sensor 13AI14Temperature Sensor 14AI15Temperature Sensor 15AI16Temperature Sensor 16AI17Temperature Sensor 17AI18Temperature Sensor 18AI19Temperature Sensor 19AI20Temperature Sensor 20AI21Temperature Sensor 21AI22Temperature Sensor 22AI23Temperature Sensor 23AI24Temperature Sensor 24AI25Temperature Sensor 25AI26Temperature Sensor 26AI27Temperature Sensor 27AI28Temperature Sensor 28AI29Temperature Sensor 29AI30Temperature Sensor 30AI31Temperature Sensor 31AI32Temperature Sensor 32AI33Temperature Zone 1AI34Temperature Zone 2AI35Temperature HMI 1AI36Temperature HMI 2AI37Temperature HMI 3AI38Temperature HMI 4AI39Humidity HMI 1AI40Humidity HMI 2AI41Humidity HMI 3AI42Humidity HMI 4AI43ECMOutput1AI44ECMOutput2AI45ECMOutput3AI46ECMOutput4AI47VDCOutputAI48VFD Frequency Exhaust 1AI49VFD Frequency Exhaust 2AI50VFD Frequency Exhaust 3AI51VFD Frequency Exhaust 4AI52VFD Frequency Exhaust 5AI53VFD Frequency Exhaust 6AI54VFD Frequency Exhaust 7AI55VFD Frequency Exhaust 8AI56VFD Frequency Supply 1AI57VFD Frequency Supply 2AI58VFD Amperage Exhaust 1AI59VFD Amperage Exhaust 2AI60VFD Amperage Exhaust 3AI61VFD Amperage Exhaust 4AI62VFD Amperage Exhaust 5AI63VFD Amperage Exhaust 6AI64VFD Amperage Exhaust 7AI65VFD Amperage Exhaust 8AI66VFD Amperage Supply 1AI67VFD Amperage Supply 2AI68VFD Power Usage Exhaust 1AI69VFD Power Usage Exhaust 2AI70VFD Power Usage Exhaust 3AI71VFD Power Usage Exhaust 4AI72VFD Power Usage Exhaust 5AI73VFD Power Usage Exhaust 6AI74VFD Power Usage Exhaust 7AI75VFD Power Usage Exhaust 8AI76VFD Power Usage Supply 1AI77VFD Power Usage Supply 2AI78VFD Fault Exhaust 1AI79VFD Fault Exhaust 2AI80VFD Fault Exhaust 3AI81VFD Fault Exhaust 4AI82VFD Fault Exhaust 5AI83VFD Fault Exhaust 6AI84VFD Fault Exhaust 7AI85VFD Fault Exhaust 8AI86VFD Fault Supply 1AI87VFD Fault Supply 2BI88Zone1-FansONbyProvingBI89Zone1-FansONbyBypassBI90Zone1-FansONbyIO1HighSpeedBI91Zone1-FansONbyMaxAirBI92Zone1-FansONbyTemperatureBI93Zone1-FansONbyOccupancyBI94Zone1-FansONbyBMSBI95Zone1-FansONbyIO1BI96Zone1-FansONbyButtonBI97Zone1-FansONbyHRCBI98Zone1-FansONbyWashBI99Zone1-FansONbyBMSPrepBI100Zone1-FansONbyButtonPrepBI101Zone1-FansONbyTemperaturePrepBI102Zone2-FansONbyProvingBI103Zone2-FansONbyBypassBI104Zone2-FansONbyIO1HighSpeedBI105Zone2-FansONbyMaxAirBI106Zone2-FansONbyTemperatureBI107Zone2-FansONbyOccupancyBI108Zone2-FansONbyBMSBI109Zone2-FansONbyIO1BI110Zone2-FansONbyButtonBI111Zone2-FansONbyHRCBI112Zone2-FansONbyWashBI113Zone2-FansONbyBMSPrepBI114Zone2-FansONbyButtonPrepBI115Zone2-FansONbyTemperaturePrepBI116Zone1-LightsONbyWashBI117Zone1-LightsONbyBypassBI118Zone1-LightsONbyBMSBI119Zone1-LightsONbyButtonBI120Zone1-LightsONbyOccupiedBI121Zone1-LightsONbyIOBI122Zone1-LightsONbyFansButtonBI123Zone1-LightsONbyFansAutomaticBI124Zone2-LightsONbyWashBI125Zone2-LightsONbyBypassBI126Zone2-LightsONbyBMSBI127Zone2-LightsONbyButtonBI128Zone2-LightsONbyOccupiedBI129Zone2-LightsONbyIOBI130Zone2-LightsONbyFansButtonBI131Zone2-LightsONbyAutomaticAI132ErrorCOREBoard1AI133ErrorCOREBoard2AI134ErrorCOREBoard3AI135ErrorCOREBoard4AI136ErrorCOREBoard5AI137ErrorCOREBoard6AI138ErrorCOREBoard7AI139ErrorCOREBoard8AI140ErrorCOREBoard9AI141ErrorCOREBoard10AI142ErrorCOREBoard11AI143ErrorCOREBoard12AI144ErrorCOREBoard13AI145ErrorCOREBoard14AI146ErrorCOREBoard15AI147PercentClogged_PCU1_Filter1AI148PercentClogged_PCU1_Filter2AI149PercentClogged_PCU1_Filter3AI150PercentClogged_PCU1_Filter4AI151PercentClogged_PCU1_Filter5BI152CloggedFilter_PCU1BI153MissingFilter_PCU1BI15472HourCloggedFilter_PCU1BI155CloggedPCU_PCU1BI156DoorMissing_PCU1BI157NeedCalibration_PCU1BI15824HourCloggedFilter_PCU1BI159ESPDoorMissing_PCU1BI160ESPDrainClogged_PCU1AI161PercentClogged_PCU2_Filter1AI162PercentClogged_PCU2_Filter2AI163PercentClogged_PCU2_Filter3AI164PercentClogged_PCU2_Filter4AI165PercentClogged_PCU2_Filter5BI166CloggedFilter_PCU2BI167MissingFilter_PCU2BI16872HourCloggedFilter_PCU2BI169CloggedPCU_PCU2BI170DoorMissing_PCU2BI171NeedCalibration_PCU2BI172ESPDoorMissing_PCU2BI173ESPDrainClogged_PCU2BI17424HourCloggedFilter_PCU2AI175PercentClogged_PCU3_Filter1AI176PercentClogged_PCU3_Filter2AI177PercentClogged_PCU3_Filter3AI178PercentClogged_PCU3_Filter4AI179PercentClogged_PCU3_Filter5BI180CloggedFilter_PCU3BI181MissingFilter_PCU3BI18272HourCloggedFilter_PCU3BI183CloggedPCU_PCU3BI184DoorMissing_PCU3BI185NeedCalibration_PCU3BI18624HourCloggedFilter_PCU3BI187ESPDoorMissing_PCU3BI188ESPDrainClogged_PCU3BI189DCVFireZone1BI190DCVAuxFaultZone1BI191DCVFuseFaultZone1BI192DCVKTSZone1BI193DCVProvingFaultZone1BI194DCVMUAInterlockErr1Zone1BI195DCVMUAInterlockErr2Zone1BI196DCVBrokenTempSensorZone1BI197DCVMissingTempSensorZone1BI198DCVOverloadZone1BI199DCVOverload2Zone1BI200DCVPCUFaultZone1BI201DCVLightsEnergizedFaultZone1BI202DCVLightsDeenergizedFaultZone1BI203DCVSurfactantLowZone1BI204DCVCheckAppliancePilotsZone1BI205DCVFireZone2BI206DCVAuxFaultZone2BI207DCVFuseFaultZone2BI208DCVKTSZone2BI209DCVProvingFaultZone2BI210DCVMUAInterlockErr1Zone2BI211DCVMUAInterlockErr2Zone2BI212DCVBrokenTempSensorZone2BI213DCVMissingTempSensorZone2BI214DCVOverload1Zone2BI215DCVOverload2Zone2BI216DCVPCUFaultZone2BI217DCVLightsEnergizedFaultZone2BI218DCVLightsDeenergizedFaultZone2BI219DCVSurfactantLowZone2BI220DCVCheckAppliancePilotsZone2AI221ModbusFaultCodeBV222PrepTimeButtonZone1BV223FansONButtonZone1BV224WashButtonZone1BV225LightsButtonZone1BV226MaxAirZone1BV227PrepTimeButtonZone2BV228FansONButtonZone2BV229WashButtonZone2BV230LightsButtonZone2BV231MaxAirZone2
Integration notes
- Protocessor defaults: device instance 50000, MS/TP MAC 127, 38400 baud, Max Master 127, IP 192.168.1.24; COV is disabled by default.
- Access comes from the guide's Function column: the ten button BVs (222-231) are Monitor/Control, everything else Monitor. The guide does not say what writing them does.
- The guide does not expand KTS (BI 192/208); CaptiveAire's SCS panel manual (A0017476) uses KTS for its Kill Tamper Switch input.
- ErrorCOREBoard1-15 (AI 132-146) report the highest-priority fault code (1-23) of each CORE fire-system board, Fire first.
- Humidity, ECM and VDC outputs and the fault AIs are listed with no units.
- Points depend on the package: unused sensors, fans, zones and PCUs read zero or are meaningless.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DCV Package DDC (Protocessor BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the CaptiveAire DCV Package DDC (Protocessor BACnet)
How many BACnet points does the CaptiveAire DCV Package DDC (Protocessor BACnet) have?
This list has 231 BACnet objects: 118 analog inputs, 103 binary inputs, 10 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which CaptiveAire DCV Package DDC (Protocessor BACnet) BACnet points are writable?
10 of the 231 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official CaptiveAire DCV Package DDC (Protocessor BACnet) BACnet documentation?
The source is Direct Digital Controls (DDC) Application Guide: Demand Control Ventilation (DCV) Packages Network, published free by CaptiveAire at https://www.captiveaire.com/catalogcontent/electriccontrols/doc/dcv-ddc.pdf.
What are the minimum BACnet points to integrate the CaptiveAire DCV Package DDC (Protocessor BACnet)?
Start with BV 223 FansONButtonZone1 (Zone 1 fans button; write effect not described in guide); BI 94 Zone1-FansONbyBMS (Confirms zone 1 fans are on by BMS command); AI 33 Temperature Zone 1 (Zone 1 temperature, °F); AI 48 VFD Frequency Exhaust 1 (Exhaust fan 1 drive speed, Hz); AI 56 VFD Frequency Supply 1 (Supply (make-up air) fan 1 drive speed, Hz); BI 189 DCVFireZone1 (Fire system tripped, zone 1); AI 78 VFD Fault Exhaust 1 (Exhaust fan 1 drive fault); AI 132 ErrorCOREBoard1 (Fire system fault code; highest-priority fault shown); AI 221 ModbusFaultCode (Modbus fault code; codes not listed in the guide).
How do I check these points on the real DCV Package DDC (Protocessor BACnet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More CaptiveAire BACnet points lists
- Make-up air heater / tempered air unit DDC controller
CaptiveAire Direct Digital Controls (DDC) Heater Controller
CaptiveAire heater (make-up air) units shipped with the factory Direct Digital Controls (DDC) controller covered by IOM A0020659.
Also known as: A0020659, CaptiveAire DDC, DDC controller, ctrl_source - DOAS rooftop unit
CaptiveAire DOAS RTU Series packaged rooftop unit, legacy IBT controls (Protocessor BACnet)
CaptiveAire DOAS RTU Series packaged rooftop units built with the older IBT-based unit controls (listed as 'Paragon - IBT Controls (Legacy)').
Also known as: A0026936, CaptiveAire DOAS RTU, Paragon IBT controls (legacy), DOAS RTU Series, CaptiveAire DOAS, Protocessor - Kitchen hood exhaust / make-up air fan controller (demand control)
CaptiveAire EMSplus Kitchen Hood Exhaust Controls (BACnet IP)
CaptiveAire EMSplus kitchen ventilation control panels ordered with the BACnet IP communication option.
Also known as: EMSplus, EMS Plus, EMS+, A0017802, CaptiveAire EMSplus - HVLS / ventilation fan control panel (up to 10 fans)
CaptiveAire HVLS and General Ventilation Fan Control (ECPM03, Protocessor BACnet)
CaptiveAire HVLS and general ventilation fan control packages with the ECPM03 board and the factory Protocessor BACnet gateway.
Also known as: A0025729, CaptiveAire HVLS, HVLS fan control, High Volume Low Speed fan, ECPM03, CASlink HVLS, Protocessor - Lighting control panel (8 zones)
CaptiveAire Lighting Control System (ECPM03, Protocessor BACnet)
CaptiveAire Lighting Control System panels with the ECPM03 board and the factory Protocessor BACnet gateway.
Also known as: A0027767, Lighting Control System, ECPM03, CASlink lighting, CaptiveAire lighting control panel, Protocessor - Make-up air unit (indirect gas-fired heater)
CaptiveAire Modular Indirect Fired Heater (IBT controls, Protocessor BACnet)
CaptiveAire modular indirect-fired make-up air heaters, modules and furnace inserts run by the IBT controller with the optional Protocessor BACnet gateway.
Also known as: A0016988, IBT heater, IBT board, Indirect Fired Bent Tube, Modular Indirect Fired Heater, Indirect Fired Module, Indirect Fired Furnace, Protocessor - Make-up air unit controller
CaptiveAire MUA Heater DDC (Protocessor BACnet)
CaptiveAire make-up air heater units (including direct-fired) with the factory DDC/BMS package.
Also known as: CaptiveAire make-up air, Direct fired MUA, Tempered make-up air, DDC Application Guide MUA - Rooftop unit / DOAS controller
CaptiveAire Paragon RTU / DOAS DDC (Protocessor BACnet)
CaptiveAire Paragon HVAC series packaged rooftop units and dedicated outdoor air systems with the factory DDC package.
Also known as: Paragon, CaptiveAire DOAS, CaptiveAire RTU, Protocessor, CN0861, RTU DDC Points - Kitchen hood self-cleaning wash system control panel
CaptiveAire Self Cleaning System (SCS) Control Panel
CaptiveAire Self Cleaning System panels that hot-water wash or cold-water mist kitchen exhaust hoods and plenums, and can also run the hood's fan and light zones.
Also known as: CaptiveAire SCS, Self Cleaning System, Hood wash panel, Hot Water Wash, Cold Water Mist, ECPM03, Protocessor
Source: Direct Digital Controls (DDC) Application Guide: Demand Control Ventilation (DCV) Packages Network. Object names, instances and units are reproduced as published; descriptions are our own.