 "manufacturer": "Bosch",
 "manufacturer_slug": "bosch",
 "model": "Control Air 5600 - Water to Air (WAZ software)",
 "model_slug": "control-air-5600-water-to-air",
 "aliases": [
  "Control Air 5600",
  "WAZ 1.03",
  "Bosch WSHP DDC",
  "Bosch water source heat pump BACnet",
  "Bosch TT Water to Air"
 ],
 "equipment_type": "Water-source heat pump controller",
 "applies_to": "Bosch water-to-air (water source) heat pumps fitted with the Control Air 5600 DDC controller running WAZ zone software.",
 "summary": "The Control Air 5600 is Bosch's factory-mounted DDC controller for water-source heat pumps. It speaks BACnet MS/TP (or BACnet over ARC156, Modbus, N2 and Lon) and exposes occupancy, mode, setpoint, sensor, configuration and alarm points as AV/BV/MSV objects. The same point list also documents Modbus registers and N2/LON equivalents.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet ARC156"
 ],
 "firmware": "WAZ.1.03",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Object names end in _1 as printed in the points list.",
  "Two names were split across lines in the PDF and were re-joined here: eq_temp_1 (AV 1902) and zs_sen_combo_sel_1 (AV 40).",
  "Many AV points are configuration selectors (input/output assignments); several only matter when that option (economizer, hot gas reheat, VFD, CO2, damper) is installed.",
  "Writable points are those not marked read-only in the list."
 ],
 "source": {
  "title": "Bosch TT - Water to Air Network Integration Points List",
  "doc_number": "WAZ.1.03",
  "revision_date": null,
  "url": "https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ipl_waz_1_03.pdf"
 },
 "integration": {
  "summary": "Leave Control Source at its default (BAS Occupancy Command), then command occupied/unoccupied with occupancy_cmd_1 and set the occupied cooling/heating setpoints. Choose the zone temperature source (ZS sensor, remote sensor or BAS value) and, if the BMS supplies the temperature, write bas_sen_val_1. Monitor current_alarm_1, alm_status_1 and the effective zone temperature.",
  "minimum_points": [
   {
    "ref": "BV 1",
    "name": "occupancy_cmd_1",
    "why": "BAS occupied command; 1 enables unit operation"
   },
   {
    "ref": "AV 15",
    "name": "ctrl_source_1",
    "why": "Occupancy source; 2 = BAS occupancy command (default)"
   },
   {
    "ref": "MV 3",
    "name": "zone_mode_1",
    "why": "Auto / heat / cool / off"
   },
   {
    "ref": "AV 4",
    "name": "occ_clg_stpt_1",
    "why": "Occupied cooling setpoint"
   },
   {
    "ref": "AV 2",
    "name": "occ_htg_stpt_1",
    "why": "Occupied heating setpoint"
   },
   {
    "ref": "AV 16",
    "name": "sys_status_1",
    "why": "Unoccupied / occupied / fan only / heating / cooling state"
   },
   {
    "ref": "AV 7",
    "name": "eff_zone_temp_1",
    "why": "Zone temperature in use"
   },
   {
    "ref": "AV 17",
    "name": "current_alarm_1",
    "why": "Active alarm code"
   },
   {
    "ref": "BV 24",
    "name": "alm_status_1",
    "why": "Alarm present flag"
   }
  ],
  "enable": "Set ctrl_source_1 (AV 15) to 2 = BAS Occupancy Command (factory default) and write occupancy_cmd_1 (BV 1) = 1 to occupy the unit. Other sources are a digital input enable, keypad schedule or manual on. The BAS loop enable point (loop_enabled_1, BV 23) must be 1 to allow heating/cooling; it defaults to 1.",
  "heartbeat": "No communication timeout is described. If the BAS temperature source is used and nothing is ever written, the zone temperature defaults to 74 °F; after that the last written value is used indefinitely.",
  "remote_sensors": "Set the compressor control mode (comp_mode_1, AV 64) to 2 = Zone Control - BAS Sensor and write the zone temperature to bas_sen_val_1 (AV 19). BAS humidity goes to bas_rh_sen_val_1 (AV 56) with rh_bas_sel_1 (AV 51); BAS CO2 to bas_co2_val_1 (AV 49) with co2_bas_ena_1 (AV 106); mixed air to bas_mat_1 (AV 86); outdoor air to effective_oat_1 (AV 29).",
  "setup": [
   "BACnet MS/TP runs on the EIA-485 port; the BAS Port Settings DIP switches select the protocol (BACnet MS/TP, N2, Modbus) and baud rate (9.6 to 76.8 kbps), the same for every controller on the trunk.",
   "The two rotary dials set the MAC address (tens and ones); the controller only reads them at power-up, so change them with power off.",
   "A Communication jumper selects EIA-485 (MS/TP, N2, Modbus, Lon) or BACnet over ARC156 at 156 kbps.",
   "Setpoints and configuration can also be changed locally with a BACview terminal or Virtual BACview."
  ],
  "gotchas": [
   "With a ZS or remote sensor selected, the controller looks for it during the first 30 s after power-up; if missing, the unit stays unoccupied, alarms and shows -60 °F.",
   "Writing bas_smoke_1 = 1 shuts the supply fan, compressors and reheat valve off.",
   "The input/output configuration AVs (in1/in2/ao/bo cfg) change how hardware I/O is used; treat them as commissioning settings, not operating points.",
   "There is a 1-minute delay when the unit changes between heating and cooling."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 15,
   "name": "ctrl_source_1",
   "description": "Control Source",
   "units": "",
   "access": "W",
   "states": "0 = Digital Input Enable (e.g. Room Occupancy Sensor) 1 = Keypad Schedule 2 = BAS Occupancy Command (Default) 3 = Factory Use Only 4 = Manual On-Continuous"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "occupancy_cmd_1",
   "description": "Occupancy Command (BAS)",
   "units": "",
   "access": "W",
   "states": "0 = Unoccupied (Default) 1 = Occupied (Enables Unit Operation)"
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "bas_smoke_1",
   "description": "BAS Smoke Input / Emergency Shutdown",
   "units": "",
   "access": "W",
   "states": "0 = Normal (Default)"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "zone_mode_stat_1",
   "description": "Zone Mode Status",
   "units": "",
   "access": "R",
   "states": "1 = Auto (Default) 2 = Heat 3 = Cool 5 = Off"
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "mode_status_1",
   "description": "Unit Mode Status",
   "units": "",
   "access": "R",
   "states": "0 = Straight Cool 2 = Heat pump (Default)"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "zone_mode_1",
   "description": "Set Zone Mode",
   "units": "",
   "access": "W",
   "states": "1 = Auto (Default) 2 = Heat 3 = Cool 5 = Off"
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "comp_mode_1",
   "description": "Compressor Control Mode",
   "units": "",
   "access": "W",
   "states": "0 = Zone Control - ZS (Default) 1 = Discharge Air Control 2 = Zone Control - BAS Sensor 3 = Zone Control - Remote Sensor"
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "ao3_cfg_sel_1",
   "description": "Analog Output 3 Options Configuration",
   "units": "",
   "access": "W",
   "states": "0 = Not Used (Default) 1 = Modulating Outdoor Air Damper Control"
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "ao2_cfg_sel_1",
   "description": "Analog Output 2 Options Configuration",
   "units": "",
   "access": "W",
   "states": "0 = Not Used (Default) 1 = Modulating Hot Gas Reheat Valve Control"
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "ao1_cfg_sel_1",
   "description": "Analog Output 1 Options Configuration",
   "units": "",
   "access": "W",
   "states": "0 = Not Used (Default) 1 =Variable Frequence Drive Signal Control 2 =Mixed Air SCR Preheat Control 3 =SCR Controlled Aux Electric Heat"
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "bo5_cfg_sel_1",
   "description": "Output 5 Options Configuration",
   "units": "",
   "access": "W",
   "states": "0 = Not Used (Default) 1 = Hot Gas Reheat for Humidity Control 2 = Auxiliary Electric Heat Control 3 = Fresh Air Damper Control 4 = Condenser Water Valve (Loop Valve) Control 6 = Water-Side Economizer Control 7 = Boilerless Electric Heat Control"
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "bo4_cfg_sel_1",
   "description": "Output 4 Options Configuration",
   "units": "",
   "access": "W",
   "states": "155 = \"1\" 0 = Not Used (Default) 1 = Economizer Valve 2 = Boilerless Control 3 = Fresh Air Damper Control"
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "in1_cfg_sel_1",
   "description": "Input 1 Configuration",
   "units": "",
   "access": "W",
   "states": "0 = Not Used (Default) 2 = Digital Input Enable (e.g. Room Occupancy Sensor) 3 = RH Probe Sensor"
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "in2_cfg_sel_1",
   "description": "Input 2 Configuration",
   "units": "",
   "access": "W",
   "states": "0 = Not Used 1 = Zone Remote Sensor 2 = Outdoor Air Temperature Sensor 3 = Entering Water Temperature Sensor (Default) 4 = Mixed Air Temperature Sensor 5 = Relative Humidity Sensor (Probe) 6 = Digital Enable (e.g. Room Occupancy Sensor) 7 = Return Air Temperature Sensor"
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "di5_mode_1",
   "description": "DI5 Mode (Digital Input 5)",
   "units": "",
   "access": "W",
   "states": "0 = Dirty Filter Switch 1 = Entering Water Temp Sensor - Economizer/Boilerless 2 = Differential Pressure Switch 3 = Secondary Condensate Pan 4 = Fan Status Switch 5 = Valve End Switch 6 = Damper End Switch 7 = Smoke Detector Switch 8 = Pump Status Switch 9 = MIxed Air Temp Sensor - Mixed Air Control 10 = Input Expansion Module (IEM) 11 = Not Used (Default)"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "lckout_resp_1",
   "description": "Fan Response for Comp Lockout",
   "units": "",
   "access": "W",
   "states": "0 = Do not lock fan upon compressor lockout (Default) 1 = Lock fan upon compressor lockout"
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "zs_sensor_en_1",
   "description": "ZS Sensor Enable",
   "units": "",
   "access": "W",
   "states": "0 = No ZS Sensors 1 = ZS Sensors Enabled (Default)"
  },
  {
   "type": "AV",
   "instance": 1904,
   "name": "eq_rh_1",
   "description": "Equipment Touch RH",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1902,
   "name": "eq_temp_1",
   "description": "Equipment Touch Temp",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "zs_sen_combo_sel_1",
   "description": "ZS Sensor Combo Selector",
   "units": "",
   "access": "W",
   "states": "0 = Temp Only 1 = RH Only 2 = CO2 Only 3 = Temp + RH 4 = Temp + CO2 5 = RH + CO2 6 = Temp + RH + CO2 (Default) 7 = No ZS Sensor"
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "stpt_adj_lim_1",
   "description": "ZS Sensor Setpoint Adjustment Limit",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 95,
   "name": "enable_push_button_1",
   "description": "Sensor Override Enable/Disable",
   "units": "",
   "access": "W",
   "states": "0 = ZS Sensor Override NOT Allowed 1 = ZS Sensor Override Allowed (Default)"
  },
  {
   "type": "BV",
   "instance": 94,
   "name": "override_status_1",
   "description": "Override Status",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = ZS Sensor in Override Mode"
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "tlo_rem_1",
   "description": "Override Time Remaining",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "occ_clg_stpt_1",
   "description": "Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "occ_htg_stpt_1",
   "description": "Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "unocc_clg_stpt_1",
   "description": "Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "unocc_htg_stpt_1",
   "description": "Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "eff_clg_stpt_1",
   "description": "Effective Cooling Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "eff_htg_stpt_1",
   "description": "Effective Heating Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "eff_zone_temp_1",
   "description": "Zone Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "nsb_status_1",
   "description": "Night Setback (NSB) Status",
   "units": "",
   "access": "R",
   "states": "0 = Night Setback disabled 1 = Night Setback enabled"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "ztmp_hi_1",
   "description": "High ZS Zone Sensor Temperature Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Zone Temperature(Default: 10 °F Above Setpoint)"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "ztmp_lo_1",
   "description": "Low ZS Zone Sensor Temperature Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low Zone Temperature(Default: 10 °F Below Setpoint)"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "zone_sen_1",
   "description": "ZS Zone Sensor Hardware Failure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check: ZS Sensor Hardware)"
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "eff_remzone_temp_1",
   "description": "Effect Zone Remote Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "zone_rem_sen_val_1",
   "description": "Remote Temp or Return Air Temp Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "sys_status_1",
   "description": "System Status",
   "units": "",
   "access": "R",
   "states": "0 = Unoccupied 1 = Occupied 2 = Fan Only 3 = Heating 4 = Cooling 5 = Transition to Cool 6 = Transition to Heat 7 = Air Economizer 8 = Unit Locked 9 = Aux Heat 10 = Re-Heat 11 = Manual Re-Heat 12 = Transition to Re-Heat 13 = Free Cooling 14 = Transition to Free Cooling 15 = Water-Side Economizer"
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "clg_pct_1",
   "description": "Cooling Demand Percentage",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "htg_pct_1",
   "description": "Heating Demand Percentage",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "eff_lwt_1",
   "description": "Leaving Water Temperature (LWT)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "eff_dat_1",
   "description": "Effect Disch Air Temp",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "eff_oat_1",
   "description": "Outdoor Air Temperature (OAT)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "dat_stpt_1",
   "description": "Discharged Air Temperature Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "rst_temp_source_1",
   "description": "Temperature Reset Source",
   "units": "",
   "access": "W",
   "states": "0 = Outside Air Temperature Reset (Default) 1 = Mixed Air (or Return Air) Temperature Reset"
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "oat_sel_sta_1",
   "description": "Outside Air Temperature Sensor Source Status",
   "units": "",
   "access": "R",
   "states": "1 = BAS OAT Sensor 2 = Hard-Wired OAT Sensor (Default)"
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "oat_rst_mode_1",
   "description": "Temperature Reset Mode",
   "units": "",
   "access": "W",
   "states": "0 = Single 1 = Multiple (Default)"
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "oat_reset1_1",
   "description": "Single Reset/Free Cooling Reset Temperature",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "oat_reset2_1",
   "description": "Part Cool Reset Temperature",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "oat_reset3_1",
   "description": "Full Cool Reset Temperature",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "oat_reset_ht_1",
   "description": "Heating Reset Temperature",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "oat_sel_1",
   "description": "Outside Air Temperature Sensor",
   "units": "",
   "access": "W",
   "states": "1 = BAS OAT Sensor 2 = Hard-Wired OAT Sensor (Default)"
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "oat_sen_1",
   "description": "Outside Air Temperature Sensor Failure",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Hardware"
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "eff_hgr_mod_vlv1_1",
   "description": "Hot Gas Reheat Modulating Valve Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "enabled_clstages_1",
   "description": "Compressor Enabled Stages",
   "units": "",
   "access": "R",
   "states": "0 = No Stages Enabled 1 = 1 Stage Enabled 2 = 2 Stages Enabled"
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "dat_stpt_diff_1",
   "description": "Supply Air Setpoint Differential",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "sat_hi_trip_1",
   "description": "Supply Air High Differential Trip",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "sat_lo_trip_1",
   "description": "Supply Air Low Differential Trip",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 86,
   "name": "csat_hi_1",
   "description": "High Cooling Supply Air Temperature in DAC",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm Active"
  },
  {
   "type": "BV",
   "instance": 149,
   "name": "hsat_lo_1",
   "description": "Low Heating Supply Air Temperature in DAC",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active (Default: <80 °F)"
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "eff_dat_stpt_1",
   "description": "Effective Discharge Air Temperature Setpoint",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "zt_reset_1",
   "description": "Effective ZS Sensor Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "occ_status_1",
   "description": "Occupancy Status",
   "units": "",
   "access": "R",
   "states": "0 = Unoccupied 1 = Occupied"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "fan_cmd_1",
   "description": "Fan Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Fan Output Off 1 = Fan Output On"
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "rev_vlv_cmd_1",
   "description": "Reversing Valve Output Status",
   "units": "",
   "access": "R",
   "states": "0 = Reversing Valve De-energized 1 = Reversing Valve Energized"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "cmp_stg1_cmd_1",
   "description": "Comp Stage1 Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Compressor 1 Off 1 = Compressor 1 On"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "cmp_stg2_cmd_1",
   "description": "Comp Stage2 Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Compressor 2 Off 1 = Compressor 2 On"
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "cmp_stgs_1",
   "description": "Compressor Stages",
   "units": "",
   "access": "R",
   "states": "1 = 1 Compressor 1 Stage 2 = 2 Compressor 2 Stages 5 = 1 Compressor 2 Stages"
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "comp_state_1",
   "description": "Compressor Status",
   "units": "",
   "access": "R",
   "states": "0 = Normal/Off 1 = Compressor Locked 2 = Compressor Overriden \"ON\" 3 = Compressor Shutdown/Alarm"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "alm_status_1",
   "description": "Alarm Status",
   "units": "",
   "access": "R",
   "states": "0 = System Normal 1 = System in Alarm"
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "current_alarm_1",
   "description": "Current Alarm Condition Status",
   "units": "",
   "access": "R",
   "states": "0 = No Alarm, 1-10 = UPM Fault Code (See UPM Alarms below) 20 = Output Overridden via Keypad 30 = Sensor Failure 40 = Leaving Water Temp Alarm 50 = Zone Temp Alarm 60 = Discharge Air Temperature Alarm 70 = Filter Alarm/Compressors 1 & 2 Runtime 80 = Zone Humidity Alarm 90 = High CO2 Level Alarm 100 = Differential Pressure Switch (DPS) Alarm"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "lvg_hi_1",
   "description": "High Leaving Water Temperature",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm (Default: >135 °F)"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "lvg_lo_1",
   "description": "Low Leaving Water Temperature",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm (Default: <40 °F)"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "dat_hi_1",
   "description": "High Discharge Air Temperature",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm (Default: >70 °F)"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "dat_lo_1",
   "description": "Discharge Air Temperature Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low DAT Alarm (Default: <75 °F)"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "hp1_2st_1",
   "description": "UPM Safety - High Pressure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Pressure Alarm (UPM-I code = 1; UPM-II codes = 1,3)"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "lp1_2st_1",
   "description": "UPM Safety - Low Pressure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low Pressure Alarm (UPM-I code = 2; UPM-II codes = 2,4)"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "frz_2st_1",
   "description": "UPM Safety - Condenser Coil Freeze Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Condenser Freeze Alarm(UPM-I code = 3; UPM-II codes = 5,9)"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "con_2st_1",
   "description": "UPM Safety - High Condensate Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Condensate Overflow Alarm(UPM-I code = 4; UPM-II code = 6)"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "brn_2st_1",
   "description": "UPM Safety - Brownout Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Brownout Alarm (UPM-I code = 5; UPM-II code = 7)"
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "frz_evap_2st_1",
   "description": "UPM Safety - Evaporator Coil Freeze Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Evaporator Freeze Alarm (UPM-I code = 6; UPM-II codes = 8,10)"
  },
  {
   "type": "BV",
   "instance": 104,
   "name": "a2l_2st_1",
   "description": "UPM Safety - A2L Alarm",
   "units": "",
   "access": "W",
   "states": "0 = Normal 1 = A2L Alarm (UPM-I code = 7; UPM-II codes = 11)"
  },
  {
   "type": "BV",
   "instance": 106,
   "name": "comm_2st_1",
   "description": "UPM Safety - Communication Alarm",
   "units": "",
   "access": "W",
   "states": "0 = Normal 1 = Communication Alarm (UPM-II codes = 12)"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "upm_rst_1",
   "description": "UPM Reset",
   "units": "",
   "access": "W",
   "states": "0 = Reset Off (Default) 1 = Reset On"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "upm_input_1",
   "description": "UPM Input Alarm",
   "units": "",
   "access": "R",
   "states": "0 = UPM Connected 1 = UPM Connection Failure(Check Alarm Hardware Configuration)"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "lvg_sen_1",
   "description": "Leaving Water Temperature Sensor Failure",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Hardware"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "da_sen_1",
   "description": "Discharge Air Temperature Sensor",
   "units": "",
   "access": "R",
   "states": "0 = Sensor Normal 1 = Sensor Failure Alarm (Check Sensor Hardware Configuration)"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "do_lock_1",
   "description": "Digital Override Lock Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Digital Override Enabled Alarm"
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "input_lock_1",
   "description": "Inputs Override Status",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Software Lock Enabled"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "dup_in12_1",
   "description": "Duplicate Input 1&2 Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm (Check input configuration for conflicts)"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "comp1_rntm_1",
   "description": "Compressor 1 Runtime",
   "units": "",
   "access": "R",
   "states": "1 = Auto (cycle with compressor) 4 = On (Default)"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "comp2_rntm_1",
   "description": "Compressor 2 Runtime",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Timer Has Expired (Default: >8760 Hours)"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "cmp1_rntm_rst_1",
   "description": "Compressor 1 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "0 = Reset Off (Default) 1 = Reset On"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "cmp2_rntm_rst_1",
   "description": "Compressor 2 Runtime Reset",
   "units": "",
   "access": "W",
   "states": "0 = Reset Off (Default) 1 = Reset On"
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "zrem_hi_1",
   "description": "High Remote Temperature Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Zone Temperature(Default: 10 °F Above Setpoint)"
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "zrem_lo_1",
   "description": "Low Remote Temperature Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low Zone Temperature(Default: 10 °F Below Setpoint)"
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "zrem_sen_1",
   "description": "Remote Temperature Sensor Hardware Failure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Remote Sensor Hardware)"
  },
  {
   "type": "BV",
   "instance": 80,
   "name": "ewt_sen_1",
   "description": "Entering Water Temperature Sensor Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure Alarm (Check Hardware)"
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "aecon_status_1",
   "description": "Air Economizer Status",
   "units": "",
   "access": "R",
   "states": "0 = Inactive 1 = Active"
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "oat_hi_lim_aecon_1",
   "description": "OAT high limit for Air Econ",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "oat_lo_lim_aecon_1",
   "description": "OAT low limit for Air Econ",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "rh_hi_lim_aecon_1",
   "description": "Outdoor RH high limit for Air Econ",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "rh_lo_lim_aecon_1",
   "description": "Outdoor RH low limit for Air Econ",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "htg_econ_1",
   "description": "Boilerless Status",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = On (Electric Heating)"
  },
  {
   "type": "BV",
   "instance": 92,
   "name": "clg_econ_1",
   "description": "Economizer Cooling Command",
   "units": "",
   "access": "R",
   "states": "0 = On 1 = Off"
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "eff_ewt_1",
   "description": "Entering Water Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 79,
   "name": "cwv_cmd_1",
   "description": "Condenser Water Valve Output",
   "units": "",
   "access": "R",
   "states": "0 = Closed 1 = Open"
  },
  {
   "type": "BV",
   "instance": 68,
   "name": "ves_status_1",
   "description": "Valve End Switch Status",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Valve End Switch Detected"
  },
  {
   "type": "BV",
   "instance": 150,
   "name": "ves_hand_1",
   "description": "Valve Switch Hand",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 151,
   "name": "ves_fail_1",
   "description": "Valve End Switch Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active"
  },
  {
   "type": "BV",
   "instance": 77,
   "name": "dps_alarm_1",
   "description": "Differential Pressure Switch (DPS) Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "aux_htg_cmd_1",
   "description": "Aux Heat Output Cmd",
   "units": "",
   "access": "R",
   "states": "0 = Aux Heat Off 1 = Aux Heat On"
  },
  {
   "type": "AV",
   "instance": 175,
   "name": "pre_htg_ovrde_1",
   "description": "Pre-Heat Output Override",
   "units": "",
   "access": "W",
   "states": "0 = Do not allow override (Default) 1 = allow override"
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "mat_pid_1",
   "description": "SCR Electric Heat Output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "filter_1",
   "description": "Filter Service Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Service Filter Alarm"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "fan_rntm_rst_1",
   "description": "Reset Fan Runtime",
   "units": "",
   "access": "W",
   "states": "0 = Reset Off (Default) 1 = Reset On"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "fan_mode_1",
   "description": "Set Fan Mode",
   "units": "",
   "access": "W",
   "states": "1 = Auto (Cycel with Compressor) 4 = On (Default)"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "fan_mode_stat_1",
   "description": "Fan Mode Status",
   "units": "",
   "access": "R",
   "states": "1 = Auto (Cycel with Compressor) 4 = On (Default)"
  },
  {
   "type": "BV",
   "instance": 66,
   "name": "fan_status_1",
   "description": "Fan Running Status",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = On - Fan Running"
  },
  {
   "type": "BV",
   "instance": 83,
   "name": "saf_hand_1",
   "description": "Fan Hand Mode Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 82,
   "name": "saf_switch_fail_1",
   "description": "Supply Air Fan Switch Failure",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm (Check Fan Hardware)"
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "eff_zone_humid_1",
   "description": "Zone Humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "occ_zhumid_stpt_1",
   "description": "Occupied Zone Humidity Setpoint",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "zhumid_stpt_diff_1",
   "description": "Zone Humidity Setpoint Differential",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "eff_hgrv_cmd_1",
   "description": "Hot Gas ReHeat Valve Status",
   "units": "",
   "access": "R",
   "states": "0 = Valve Off 1 = Valve On"
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "zhumid_hi_1",
   "description": "High Humidity Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Humidity (Default: 10% above Setpoint)"
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "zhumid_lo_1",
   "description": "Low Humidity Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Low Humidity (Default: 30% below Setpoint)"
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "zhumid_sen_1",
   "description": "Humidity Sensor Hardware Failure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check RH Sensor Hardware Configuration)"
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "iem_mode_1",
   "description": "Input Expansion Module Mode",
   "units": "",
   "access": "W",
   "states": "0 = Dirty Filter Switch, Fan Status Switch, Valve End Switch (Default) 1 = Smoke Detector Switch, Fan Status Switch, Valve End Switch 2 = Dirty Filter Switch, Fan Status Switch, Differential Pressure Switch 3 = Smoke Detector Switch, Fan Status Switch, Dirty Filter Switch 4 = Dirty Filter Switch, Fan Status Switch, Damper End Switch 5 = Smoke Detector Switch, Fan Status Switch, Secondary Drain Pan 6 = Dirty Filter Switch, Fan Status Switch, Pump Status"
  },
  {
   "type": "BV",
   "instance": 67,
   "name": "allow_fan_alrm_1",
   "description": "Enable/Disable Fan Status Switch in IEM",
   "units": "",
   "access": "W",
   "states": "0 = FSS on IEM disabled (Default)"
  },
  {
   "type": "BV",
   "instance": 69,
   "name": "allow_ves_alrm_1",
   "description": "Enable/Disable Valve Switch in IEM",
   "units": "",
   "access": "W",
   "states": "0 = VES on IEM disabled (Default)"
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "smoke_alrm_enable_1",
   "description": "Smoke Alarm Enable/Disable",
   "units": "",
   "access": "W",
   "states": "0 = SDS on IEM disabled (Default) 1 = SDS on IEM Enabled"
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "eff_mat_1",
   "description": "Mixed Air Temperature (MAT)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "mat_sel_status_1",
   "description": "Mix Air Temperature Source Status",
   "units": "",
   "access": "R",
   "states": "0 = BAS MAT 1 = Wired MAT"
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "mat_sel_1",
   "description": "Mixed Air Temperature Sensor",
   "units": "",
   "access": "W",
   "states": "0 = BAS MAT Sensor 1 = Hard-Wired MAT Sensor (Default)"
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "mat_stpt_1",
   "description": "Mixed Air Temperature Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "ma_preheat_1",
   "description": "Electric Preheat Output",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "mat_low_1",
   "description": "Low Mixed Air Temperature",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm (Default: <38 °F)"
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "mat_sen_1",
   "description": "Mix Air Temperature Sensor Failure",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Sensor Hardware"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "pump_cmd_1",
   "description": "Circulation Pump Output Command",
   "units": "",
   "access": "R",
   "states": "0 = Pump Running 1 = Pump Off"
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "pss_fail_1",
   "description": "Circulation Pump Switch Failure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Active"
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "pump_status_1",
   "description": "Pump Switch Status",
   "units": "",
   "access": "R",
   "states": "0 = Off 1 = Pump Switch Detected"
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "pss_hand_1",
   "description": "Circulation Pump Switch In Hand Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "conpump_1",
   "description": "Secondary Condensate Pump Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm Active"
  },
  {
   "type": "BV",
   "instance": 81,
   "name": "smoke_1",
   "description": "Smoke Event Alarm Notification",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Alarm"
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "smoke_status_1",
   "description": "Smoke Event Status",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Smoke Detector Active"
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "eff_zn_co2_lev_1",
   "description": "Zone CO2 Level",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "zn_co2_hi_trip_1",
   "description": "Zone CO2 High Trip",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "zn_co2_fail_1",
   "description": "CO2 Hardware Failure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check CO2 Hardware Configuration)"
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "zn_co2_hi_1",
   "description": "High CO2 Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High CO2 Level (Default: >1200 PPM)"
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "dmp_opt_sel_1",
   "description": "Damper Option Selection",
   "units": "",
   "access": "W",
   "states": "0 = Damper Opens when Fan Runs (Default) 1 = Damper Opens when Occupied 2 = Damper Opens for Free Cooling (Air Economizer)"
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "damper_cmd_1",
   "description": "Damper Command",
   "units": "",
   "access": "R",
   "states": "0 = Closed 1 = Open"
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "des_status_1",
   "description": "Damper End Switch",
   "units": "",
   "access": "R",
   "states": "0 = Damper Closed 1 = Damper Open"
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "eff_dpr_pos_screen_1",
   "description": "Modulating Damper Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "min_mdpr_pos_1",
   "description": "Minimum Damper Position",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "mdpr_occ_sel_1",
   "description": "Damper Occupancy Selection",
   "units": "",
   "access": "W",
   "states": "0 = Disabled 1 = Occupied (Default) 2 = Unoccupied 3 = Any Occupancy"
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "eff_sa_fan_speed_1",
   "description": "Static Air Fan Speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "eff_sa_sta_press_1",
   "description": "Supply Air Duct Static Pressure",
   "units": "in. W.C.",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "sta_press_stpt_1",
   "description": "Static Press Setpoint",
   "units": "in. W.C.",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "saf_min_speed_1",
   "description": "Supply Air Fan Minimum Speed",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "sa_sta_hi_trip_1",
   "description": "Supply Air Static Pressure High Trip",
   "units": "in. W.C.",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 65,
   "name": "sas_sen_1",
   "description": "Static Air Pressure Sensor Hardware Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = Sensor Failure (Check Static Pressure Hardware Configuration)"
  },
  {
   "type": "BV",
   "instance": 64,
   "name": "sas_hi_1",
   "description": "High Static Pressure Alarm",
   "units": "",
   "access": "R",
   "states": "0 = Normal 1 = High Static Pressure (Default: > 2.75\" H20)"
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "unit_mode_1",
   "description": "Unit Mode",
   "units": "",
   "access": "W",
   "states": "0 = Cooling only 2 = Heat Pump (Default)"
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "stages_1",
   "description": "Compressor Stages Selection",
   "units": "",
   "access": "W",
   "states": "1 = 1 Compressor 1 Stage (UPM-I Alarm Codes Used) 2 = 2 Compressor 2 Stages (UPM-II Alarm Codes Used) 5 = 1 Compressor 2 Stages (UPM-I Alarm Codes Used) (Default)"
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "coil_cfg_1",
   "description": "Evaporator Coil Configuration Selection",
   "units": "",
   "access": "W",
   "states": "0 = Parallel (Default) 1 = Series"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "loop_enabled_1",
   "description": "BAS Loop Enable/Disable",
   "units": "",
   "access": "W",
   "states": "0 = Disable Heat/Cool 1 = Allow Heat/Cool Operation (Default)"
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "rh_bas_sel_1",
   "description": "BAS Relative Humidity Enable/Disable",
   "units": "",
   "access": "W",
   "states": "0 = BAS RH Sensor 1 = Hard-Wired RH Sensor (Default)"
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "co2_bas_ena_1",
   "description": "CO2 BAS Enable/Disable",
   "units": "",
   "access": "W",
   "states": "0 = BAS CO2 Sensor 1 = Hard-Wired CO2 Sensor (Default)"
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "bas_co2_val_1",
   "description": "BAS CO2 Sensor Value",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "bas_mat_1",
   "description": "BAS Mixed Air Temp",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "effective_oat_1",
   "description": "BAS Outside Air Temperature",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "bas_rh_sen_val_1",
   "description": "BAS RH Sensor Value",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "bas_sen_val_1",
   "description": "BAS Temperature Sensor Value",
   "units": "°F",
   "access": "W",
   "states": ""
  }
 ],
 "short_model": "Control Air 5600 Water-to-Air",
 "page": "https://easybacnet.com/bacnet-points-lists/bosch/control-air-5600-water-to-air",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}