- MCA 109 Advanced BACnet Option (FC-102)
Pump variable frequency drive BACnet option card · BACnet points list
Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) BACnet points list
Updated 28 October 2026
The MCA 109 option card adds a fuller BACnet MS/TP interface to the FC-102 drive used on Bell & Gossett pumps. Besides drive I/O, commands and readings, it exposes three extended PID controllers and individual binary values for every drive warning and alarm, which makes fault reporting to the BAS much more detailed than the embedded interface.
This page lists 297 BACnet objects for the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) — 81 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Bell & Gossett’s own free documentation, linked below.
- Manufacturer
- Bell & Gossett
- Model
- MCA 109 Advanced BACnet Option (FC-102)
- Equipment
- Pump variable frequency drive BACnet option card
- Equipment type
- VFDs & pumps
- BACnet objects
- 297 (81 writable)
- Transport
- BACnet MS/TP
- Firmware
- 3.90 and above
- Also known as
- MCA109, MCA 109, FC-102 BACnet option, VLT BACnet option
Reference only, provided as-is: verify against Bell & Gossett’s current documentation and the live device before use. Not official Bell & Gossett information. Terms of use.
BMS integration notes: Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)
The MCA 109 option card list gives start, coast, direction, jog and reset commands, references and setpoints, three extended PID controllers, and one binary value per drive warning and alarm. A typical integration writes BV 1 and a reference or setpoint, then reads status, speed, power and the warning/alarm bits it cares about.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | Start | Start/stop the drive from the BMS | Write |
| AV 0 | Reference | Speed reference from the BMS (open-loop control) | Write |
| AV 46 | Setpoint 1 | Process setpoint 1 (when the drive runs its own PID) | Write |
| BV 5 | Reset | Reset a tripped drive | Write |
| BV 10 | Drive Ready | Ready to run when given a start | Read |
| BV 16 | Motor running | Running status | Read |
| BV 13 | Bus control | Drive is under bus control | Read |
| AV 50 | Frequency | Output frequency | Read |
| AV 15 | Power [KW] | Drive output power | Read |
| BV 14 | Trip | Any active drive fault | Read |
Enable & remote start
BV 1 Start, BV 2 Coasting, BV 3 CW/CCW and BV 4 Jog are writable commands, and BV 13 shows whether the drive is under bus control. The point list does not explain how bus control is set up on the drive.
Sensors & values from the BMS
AV 2-4 Bus Feedback1-3 and the Ext. 1-3 setpoint/feedback values are writable; the point list does not describe how the drive uses them.
Network setup
- The point list applies to drive firmware 3.90 and above.
Watch out for
- Binary values prefixed "W:" are warning bits and "A:" are alarm bits.
- Many rows in the list are Reserved or NA and are not included here.
Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Analog Input 53 | Drive analog input terminal 53 value | Read | ||
| AI | 1 | Analog Input 54 | Drive analog input terminal 54 value | Read | ||
| AI | 2 | Analog Input X30/11 | Drive analog input terminal X30/11 value | Read | ||
| AI | 3 | Analog Input X30/12 | Drive analog input terminal X30/12 value | Read | ||
| AI | 4 | Analog Input X42/1 | Drive analog input terminal X42/1 value | Read | ||
| AI | 5 | Analog Input X42/3 | Drive analog input terminal X42/3 value | Read | ||
| AI | 6 | Analog Input X42/5 | Drive analog input terminal X42/5 value | Read | ||
| AO | 0 | Terminal 42 Output Bus Control | Analog or pulse output written over the bus | Write | ||
| AO | 1 | Pulse out #27 Bus Control | Analog or pulse output written over the bus | Write | ||
| AO | 2 | Pulse out #29 Bus Control | Analog or pulse output written over the bus | Write | ||
| AO | 3 | Analogue Out X30/8 [mA] | Analog or pulse output written over the bus | Write | ||
| AO | 4 | Analogue Out X42/7 [V] | Analog or pulse output written over the bus | Write | ||
| AO | 5 | Analogue Out X42/9 [V] | Analog or pulse output written over the bus | Write | ||
| AO | 6 | Analogue Out X42/11 [V] | Analog or pulse output written over the bus | Write | ||
| AVmin | 0 | Reference | Speed / process reference from the bus | Write | ||
| AV | 1 | Speed Act Value | Actual speed value | Write | ||
| AV | 2 | Bus Feedback1 | Feedback value 1 written by the BAS | Write | ||
| AV | 3 | Bus Feedback2 | Feedback value 2 written by the BAS | Write | ||
| AV | 4 | Bus Feedback3 | Feedback value 3 written by the BAS | Write | ||
| AV | 5 | Motor Voltage | Motor voltage | Read | ||
| AV | 6 | Motor Current | Motor current | Read | ||
| AV | 7 | Torque [%] | Motor torque in percent | Read | ||
| AV | 8 | DC Link Voltage | DC link voltage | Read | ||
| AV | 9 | Motor Thermal | Motor thermal load | Read | ||
| AV | 10 | Heatsink Temp. | Drive heatsink temperature | Read | ||
| AV | 11 | Inverter Thermal | Inverter thermal load | Read | ||
| AV | 12 | Operating Hours | Drive powered-on hours | Read | ||
| AV | 13 | Running Hours | Motor running hours | Read | ||
| AV | 14 | KWh Counter | Energy counter | Read | ||
| AVmin | 15 | Power [KW] | Drive output power | Read | ||
| AV | 16 | PID Start Speed [Hz] | Process PID: Start Speed [Hz] | Write | ||
| AV | 17 | PID Proportional Gain | Process PID: Proportional Gain | Write | ||
| AV | 18 | PID Integral Time | Process PID: Integral Time | Write | ||
| AV | 19 | PID Differential Time | Process PID: Differential Time | Write | ||
| AV | 20 | PID Dif. Gain Limit | Process PID: Dif. Gain Limit | Write | ||
| AV | 21 | On Reference Bandwith | On-reference bandwidth | Write | ||
| AV | 22 | Ext. 1 Setpoint | Extended PID controller 1: Setpoint | Write | ||
| AV | 23 | Ext. 1 Reference [Unit] | Extended PID controller 1: Reference [Unit] | Write | ||
| AV | 24 | Ext. 1 Feedback [Unit] | Extended PID controller 1: Feedback [Unit] | Write | ||
| AV | 25 | Ext. 1 Propotional Gain | Extended PID controller 1: Propotional Gain | Write | ||
| AV | 27 | Ext. 1 Integral Time | Extended PID controller 1: Integral Time | Write | ||
| AV | 28 | Ext. 1 Differential Time | Extended PID controller 1: Differential Time | Write | ||
| AV | 29 | Ext. 1 Dif. Gain Limit | Extended PID controller 1: Dif. Gain Limit | Write | ||
| AV | 31 | Ext. 2 Setpoint | Extended PID controller 2: Setpoint | Write | ||
| AV | 32 | Ext. 2 reference [Unit] | Extended PID controller 2: reference [Unit] | Write | ||
| AV | 33 | Ext. 2 Feedback [Unit] | Extended PID controller 2: Feedback [Unit] | Write | ||
| AV | 34 | Ext. 2 Proportional Gain | Extended PID controller 2: Proportional Gain | Write | ||
| AV | 35 | Ext. 2 Integral Time | Extended PID controller 2: Integral Time | Write | ||
| AV | 36 | Ext. 2 Differential Time | Extended PID controller 2: Differential Time | Write | ||
| AV | 37 | Ext. 2 Dif. Gain | Extended PID controller 2: Dif. Gain | Write | ||
| AV | 38 | Ext. 3 Setpoint | Extended PID controller 3: Setpoint | Write | ||
| AV | 39 | Ext. 3 Reference [Unit] | Extended PID controller 3: Reference [Unit] | Write | ||
| AV | 40 | Ext. 3 Feedback [Unit] | Extended PID controller 3: Feedback [Unit] | Write | ||
| AV | 41 | Ext. 3 Proportional Gain | Extended PID controller 3: Proportional Gain | Write | ||
| AV | 42 | Ext. 3 Integral Time | Extended PID controller 3: Integral Time | Write | ||
| AV | 43 | Ext. 3 Differential Time | Extended PID controller 3: Differential Time | Write | ||
| AV | 44 | Ext. 3 Dif. Gain Limit | Extended PID controller 3: Dif. Gain Limit | Write | ||
| AV | 45 | Running Bypass | Running in bypass | Read | ||
| AVmin | 46 | Setpoint 1 | Process setpoint 1 | Write | ||
| AV | 47 | Setpoint 2 | Process setpoint 2 | Write | ||
| AV | 48 | Setpoint 3 | Process setpoint 3 | Write | ||
| AVmin | 50 | Frequency | Output frequency | Read | ||
| AV | 51 | Feedback [Unit] | Process feedback | Read | ||
| AV | 58 | Sensorless Readout | Sensorless pump flow/pressure readout | Read | ||
| BI | 0 | Digital input 33 | Drive digital input state | Read | ||
| BI | 1 | Digital input 32 | Drive digital input state | Read | ||
| BI | 2 | Digital input 29 | Drive digital input state | Read | ||
| BI | 3 | Digital input 27 | Drive digital input state | Read | ||
| BI | 4 | Digital input 19 | Drive digital input state | Read | ||
| BI | 5 | Digital input 18 | Drive digital input state | Read | ||
| BI | 6 | Digital input 37 | Drive digital input state | Read | ||
| BI | 7 | Digital Input X30/2 | Drive digital input state | Read | ||
| BI | 8 | Digital Input X30/3 | Drive digital input state | Read | ||
| BI | 9 | Digital Input X30/4 | Drive digital input state | Read | ||
| BI | 10 | Digital input P1660/10 | Drive digital input state | Read | ||
| BI | 11 | Digital input P1660/11 | Drive digital input state | Read | ||
| BI | 12 | Digital input P1660/12 | Drive digital input state | Read | ||
| BI | 13 | Digital input P1660/13 | Drive digital input state | Read | ||
| BI | 14 | Digital input P1660/14 | Drive digital input state | Read | ||
| BI | 15 | Digital input P1660/15 | Drive digital input state | Read | ||
| BO | 0 | Digital output 27 | Digital or relay output written over the bus | Write | ||
| BO | 1 | Digital output 29 | Digital or relay output written over the bus | Write | ||
| BO | 2 | GPIO Output Term X30/6 | Digital or relay output written over the bus | Write | ||
| BO | 3 | GPIO Output Term X30/7 | Digital or relay output written over the bus | Write | ||
| BO | 4 | Relay 1 output | Digital or relay output written over the bus | Write | ||
| BO | 5 | Relay 2 output | Digital or relay output written over the bus | Write | ||
| BO | 6 | Option B Relay 1 Output | Digital or relay output written over the bus | Write | ||
| BO | 7 | Option B Relay 2 Output | Digital or relay output written over the bus | Write | ||
| BO | 8 | Option B Relay 3 Output | Digital or relay output written over the bus | Write | ||
| BO | 9 | Reserved output P590/09 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 10 | Reserved output P590/10 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 11 | Reserved output P590/11 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 12 | Reserved output P590/12 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 13 | Reserved output P590/13 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 14 | Reserved output P590/14 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 15 | Reserved output P590/15 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 16 | Option C Relay 1 Output | Digital or relay output written over the bus | Write | ||
| BO | 17 | Option C Relay 2 Output | Digital or relay output written over the bus | Write | ||
| BO | 18 | Option C Relay 3 Output | Digital or relay output written over the bus | Write | ||
| BO | 19 | Option C Relay 4 Output | Digital or relay output written over the bus | Write | ||
| BO | 20 | Option C Relay 5 Output | Digital or relay output written over the bus | Write | ||
| BO | 21 | Option C Relay 6 Output | Digital or relay output written over the bus | Write | ||
| BO | 22 | Option C Relay 7 Output | Digital or relay output written over the bus | Write | ||
| BO | 23 | Option C Relay 8 Output | Digital or relay output written over the bus | Write | ||
| BO | 24 | Reserved output P590/24 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 25 | Reserved output P590/25 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 26 | Reserved output P590/26 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 27 | Reserved output P590/27 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 28 | Reserved output P590/28 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 29 | Reserved output P590/29 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BO | 30 | Reserved output P590/30 | Reserved digital output (parameter 5-90 bit) | Write | ||
| BV | 0 | Com. Fault | Communication fault | Read | ||
| BVmin | 1 | Start | Start command | Write | ||
| BV | 2 | Coasting | Coast stop command | Write | ||
| BV | 3 | CW/CCW | Rotation direction command | Write | ||
| BV | 4 | Jog | Jog command | Write | ||
| BVmin | 5 | Reset | Reset command | Write | ||
| BV | 6 | Reset KwH Counter | Reset command | Write | ||
| BV | 7 | Reset Running Hour Counter | Reset command | Write | ||
| BVmin | 10 | Drive Ready | Drive ready | Read | ||
| BV | 12 | Speed = reference | Speed equals reference | Read | ||
| BVmin | 13 | Bus control | Drive under bus control | Read | ||
| BVmin | 14 | Trip | Drive tripped | Read | ||
| BV | 15 | Trip Lock | Drive trip-locked | Read | ||
| BVmin | 16 | Motor running | Motor running | Read | ||
| BV | 17 | Warning | Drive warning active | Read | ||
| BV | 21 | ECB Test Mode | Electronically controlled bypass: Test Mode | Read | ||
| BV | 22 | ECB Drivemode | Electronically controlled bypass: Drivemode | Read | ||
| BV | 23 | ECB Aut. Bypass Enable | Electronically controlled bypass: Aut. Bypass Enable | Read | ||
| BV | 24 | ECB Bypass Mode | Electronically controlled bypass: Bypass Mode | Read | ||
| BV | 25 | ECB State | Electronically controlled bypass: State | Read | ||
| BV | 26 | ECB Overload Trip | Electronically controlled bypass: Overload Trip | Read | ||
| BV | 27 | M2 Fault | Bypass motor M2 fault | Read | ||
| BV | 28 | M3 Fault | Bypass motor M3 fault | Read | ||
| BV | 29 | ECB External Interlock | Electronically controlled bypass: External Interlock | Read | ||
| BV | 30 | ECB Manual Override | Electronically controlled bypass: Manual Override | Read | ||
| BV | 40 | A: Brake check | Drive alarm flag: Brake check | Read | ||
| BV | 41 | A: Pwr. Card Temp | Drive alarm flag: Pwr. Card Temp | Read | ||
| BV | 42 | A: Earth Fault | Drive alarm flag: Earth Fault | Read | ||
| BV | 43 | A: Ctrl.Card Temp | Drive alarm flag: Ctrl.Card Temp | Read | ||
| BV | 44 | A: Ctrl. Word TO | Drive alarm flag: Ctrl. Word TO | Read | ||
| BV | 45 | A: Over Current | Drive alarm flag: Over Current | Read | ||
| BV | 46 | A: Torque Limit | Drive alarm flag: Torque Limit | Read | ||
| BV | 47 | A: Motor TH Over | Drive alarm flag: Motor TH Over | Read | ||
| BV | 48 | A: Motor ETR Over | Drive alarm flag: Motor ETR Over | Read | ||
| BV | 49 | A: Inverter Overld. | Drive alarm flag: Inverter Overld. | Read | ||
| BV | 50 | A: DC under Volt | Drive alarm flag: DC under Volt | Read | ||
| BV | 51 | A: DC over Volt | Drive alarm flag: DC over Volt | Read | ||
| BV | 52 | A: Short Circuit | Drive alarm flag: Short Circuit | Read | ||
| BV | 53 | A: Inrush Fault | Drive alarm flag: Inrush Fault | Read | ||
| BV | 54 | A: Mains Fault | Drive alarm flag: Mains Fault | Read | ||
| BV | 55 | A: AMA Not OK | Drive alarm flag: AMA Not OK | Read | ||
| BV | 56 | A: Live Zero Error | Drive alarm flag: Live Zero Error | Read | ||
| BV | 57 | A: Internal Fault | Drive alarm flag: Internal Fault | Read | ||
| BV | 58 | A: Brake Overload | Drive alarm flag: Brake Overload | Read | ||
| BV | 59 | A: U Phase Loss | Drive alarm flag: U Phase Loss | Read | ||
| BV | 60 | A: V Phase Loss | Drive alarm flag: V Phase Loss | Read | ||
| BV | 61 | A: W Phase Loss | Drive alarm flag: W Phase Loss | Read | ||
| BV | 62 | A: Fieldbus Fault | Drive alarm flag: Fieldbus Fault | Read | ||
| BV | 63 | A: 24 V Supply Low | Drive alarm flag: 24 V Supply Low | Read | ||
| BV | 64 | A: Mains fault | Drive alarm flag: Mains fault | Read | ||
| BV | 65 | A: 1.8V supply low | Drive alarm flag: 1.8V supply low | Read | ||
| BV | 66 | A: Brake Failure | Drive alarm flag: Brake Failure | Read | ||
| BV | 67 | A: Brake IGBT | Drive alarm flag: Brake IGBT | Read | ||
| BV | 68 | A: Option Changed | Drive alarm flag: Option Changed | Read | ||
| BV | 69 | A: Drive Initialised | Drive alarm flag: Drive Initialised | Read | ||
| BV | 70 | A: Safe Stop | Drive alarm flag: Safe Stop | Read | ||
| BV | 71 | A: Alarm: Brake low | Drive alarm flag: Alarm: Brake low | Read | ||
| BV | 72 | A: Service trip 1691/0 | Drive alarm flag: Service trip 1691/0 | Read | ||
| BV | 73 | A: Service trip 1691/1 | Drive alarm flag: Service trip 1691/1 | Read | ||
| BV | 74 | A: Service trip 1691/2 | Drive alarm flag: Service trip 1691/2 | Read | ||
| BV | 75 | A: Service trip 1691/3 | Drive alarm flag: Service trip 1691/3 | Read | ||
| BV | 76 | A: Service trip 1691/4 | Drive alarm flag: Service trip 1691/4 | Read | ||
| BV | 77 | A: No flow | Drive alarm flag: No flow | Read | ||
| BV | 78 | A: Dry Pump | Drive alarm flag: Dry Pump | Read | ||
| BV | 79 | A: Curve end | Drive alarm flag: Curve end | Read | ||
| BV | 80 | A: Broken Belt | Drive alarm flag: Broken Belt | Read | ||
| BV | 81 | A: Discharge High | Drive alarm flag: Discharge High | Read | ||
| BV | 82 | A: Start fault | Drive alarm flag: Start fault | Read | ||
| BV | 83 | A: Speed limit | Drive alarm flag: Speed limit | Read | ||
| BV | 84 | A: State fault 1691/12 | Drive alarm flag: State fault 1691/12 | Read | ||
| BV | 85 | A: State fault 1691/13 | Drive alarm flag: State fault 1691/13 | Read | ||
| BV | 86 | A: State fault 1691/14 | Drive alarm flag: State fault 1691/14 | Read | ||
| BV | 87 | A: State fault 1691/15 | Drive alarm flag: State fault 1691/15 | Read | ||
| BV | 88 | A: KTY Temparture error | Drive alarm flag: KTY Temparture error | Read | ||
| BV | 89 | A: Drive Fan error | Drive alarm flag: Drive Fan error | Read | ||
| BV | 90 | A: ECB error | Drive alarm flag: ECB error | Read | ||
| BV | 91 | A: Alarm 1691/19 | Drive alarm flag: Alarm 1691/19 | Read | ||
| BV | 92 | A: Alarm 1691/20 | Drive alarm flag: Alarm 1691/20 | Read | ||
| BV | 93 | A: Alarm 1691/21 | Drive alarm flag: Alarm 1691/21 | Read | ||
| BV | 94 | A: Alarm 1691/22 | Drive alarm flag: Alarm 1691/22 | Read | ||
| BV | 95 | A: Alarm 1691/23 | Drive alarm flag: Alarm 1691/23 | Read | ||
| BV | 96 | A: Alarm 1691/24 | Drive alarm flag: Alarm 1691/24 | Read | ||
| BV | 97 | A: Alarm 1691/25 | Drive alarm flag: Alarm 1691/25 | Read | ||
| BV | 98 | A: Alarm 1691/26 | Drive alarm flag: Alarm 1691/26 | Read | ||
| BV | 99 | A: Alarm P1691/27 | Drive alarm flag: Alarm P1691/27 | Read | ||
| BV | 100 | A: Alarm 1691/28 | Drive alarm flag: Alarm 1691/28 | Read | ||
| BV | 101 | A: Alarm 1691/29 | Drive alarm flag: Alarm 1691/29 | Read | ||
| BV | 102 | A: Alarm 1691/30 | Drive alarm flag: Alarm 1691/30 | Read | ||
| BV | 103 | A: Alarm 1691/31 | Drive alarm flag: Alarm 1691/31 | Read | ||
| BV | 104 | W: Brake Check | Drive warning flag: Brake Check | Read | ||
| BV | 105 | W: Pwr. Card Temp | Drive warning flag: Pwr. Card Temp | Read | ||
| BV | 106 | W: Earth Fault | Drive warning flag: Earth Fault | Read | ||
| BV | 107 | W: Ctrl. Card Temp | Drive warning flag: Ctrl. Card Temp | Read | ||
| BV | 108 | W: Crtl. Word TO | Drive warning flag: Crtl. Word TO | Read | ||
| BV | 109 | W: Over Current | Drive warning flag: Over Current | Read | ||
| BV | 110 | W: Torque Limit | Drive warning flag: Torque Limit | Read | ||
| BV | 111 | W: Motor Th Over | Drive warning flag: Motor Th Over | Read | ||
| BV | 112 | W: Motor ETR Over | Drive warning flag: Motor ETR Over | Read | ||
| BV | 113 | W: Inverter overld. | Drive warning flag: Inverter overld. | Read | ||
| BV | 114 | W: DC under Volt | Drive warning flag: DC under Volt | Read | ||
| BV | 115 | W: DC over Volt | Drive warning flag: DC over Volt | Read | ||
| BV | 116 | W: DC Voltage Low | Drive warning flag: DC Voltage Low | Read | ||
| BV | 117 | W: DC Voltage high | Drive warning flag: DC Voltage high | Read | ||
| BV | 118 | W: Mains Ph. Loss | Drive warning flag: Mains Ph. Loss | Read | ||
| BV | 119 | W: No Motor | Drive warning flag: No Motor | Read | ||
| BV | 120 | W: Live Zero Error | Drive warning flag: Live Zero Error | Read | ||
| BV | 121 | W: 10V low | Drive warning flag: 10V low | Read | ||
| BV | 122 | W: Brake Overload | Drive warning flag: Brake Overload | Read | ||
| BV | 123 | W: Brake Resistor | Drive warning flag: Brake Resistor | Read | ||
| BV | 124 | W: Brake IGBT | Drive warning flag: Brake IGBT | Read | ||
| BV | 125 | W: Speed Limit | Drive warning flag: Speed Limit | Read | ||
| BV | 126 | W: Fieldbus Fault | Drive warning flag: Fieldbus Fault | Read | ||
| BV | 127 | W: 24V Supply Low | Drive warning flag: 24V Supply Low | Read | ||
| BV | 128 | W: Mains Failure | Drive warning flag: Mains Failure | Read | ||
| BV | 129 | W: Current Limit | Drive warning flag: Current Limit | Read | ||
| BV | 130 | W: Low Temp | Drive warning flag: Low Temp | Read | ||
| BV | 131 | W: Voltage Limit | Drive warning flag: Voltage Limit | Read | ||
| BV | 132 | W: Encoder loss | Drive warning flag: Encoder loss | Read | ||
| BV | 133 | W: Output Freq. limit | Drive warning flag: Output Freq. limit | Read | ||
| BV | 134 | W: Safe stop | Drive warning flag: Safe stop | Read | ||
| BV | 135 | W: Ext. Status | Drive warning flag: Ext. Status | Read | ||
| BV | 136 | W: Start delayed | Drive warning flag: Start delayed | Read | ||
| BV | 137 | W: Stop delayed | Drive warning flag: Stop delayed | Read | ||
| BV | 138 | W: Clock failure | Drive warning flag: Clock failure | Read | ||
| BV | 139 | W: Fire mode was active | Drive warning flag: Fire mode was active | Read | ||
| BV | 140 | W: Reserved - P1693/04 | Drive warning flag: Reserved - P1693/04 | Read | ||
| BV | 141 | W: No Flow | Drive warning flag: No Flow | Read | ||
| BV | 142 | W: Dry Pump | Drive warning flag: Dry Pump | Read | ||
| BV | 143 | W: End of Curve | Drive warning flag: End of Curve | Read | ||
| BV | 144 | W: Belt Broken | Drive warning flag: Belt Broken | Read | ||
| BV | 145 | W: Discharge High | Drive warning flag: Discharge High | Read | ||
| BV | 146 | W: Reserved - P1693/10 | Drive warning flag: Reserved - P1693/10 | Read | ||
| BV | 147 | W: Reserved - P1693/11 | Drive warning flag: Reserved - P1693/11 | Read | ||
| BV | 148 | W: Reserved - P1693/12 | Drive warning flag: Reserved - P1693/12 | Read | ||
| BV | 149 | W: Reserved - P1693/13 | Drive warning flag: Reserved - P1693/13 | Read | ||
| BV | 150 | W: Reserved - P1693/14 | Drive warning flag: Reserved - P1693/14 | Read | ||
| BV | 151 | W: Reserved - P1693/15 | Drive warning flag: Reserved - P1693/15 | Read | ||
| BV | 152 | W: Reserved - P1693/16 | Drive warning flag: Reserved - P1693/16 | Read | ||
| BV | 153 | W: KTY Temperature | Drive warning flag: KTY Temperature | Read | ||
| BV | 154 | W: Drive Fan failure | Drive warning flag: Drive Fan failure | Read | ||
| BV | 155 | W: ECB failure | Drive warning flag: ECB failure | Read | ||
| BV | 156 | W: Reserved - P1693/20 | Drive warning flag: Reserved - P1693/20 | Read | ||
| BV | 157 | W: Reserved - P1693/21 | Drive warning flag: Reserved - P1693/21 | Read | ||
| BV | 158 | W: Reserved - P1693/22 | Drive warning flag: Reserved - P1693/22 | Read | ||
| BV | 159 | W: Reserved - P1693/23 | Drive warning flag: Reserved - P1693/23 | Read | ||
| BV | 160 | W: Reserved - P1693/24 | Drive warning flag: Reserved - P1693/24 | Read | ||
| BV | 161 | W: Reserved - P1693/25 | Drive warning flag: Reserved - P1693/25 | Read | ||
| BV | 162 | W: Reserved - P1693/26 | Drive warning flag: Reserved - P1693/26 | Read | ||
| BV | 163 | W: Reserved - P1693/27 | Drive warning flag: Reserved - P1693/27 | Read | ||
| BV | 164 | W: Reserved - P1693/28 | Drive warning flag: Reserved - P1693/28 | Read | ||
| BV | 165 | W: Reserved - P1693/29 | Drive warning flag: Reserved - P1693/29 | Read | ||
| BV | 166 | W: PTC Temperature | Drive warning flag: PTC Temperature | Read | ||
| BV | 167 | W: Reserved - P1693/31 | Drive warning flag: Reserved - P1693/31 | Read | ||
| BV | 168 | Ramping active | Drive status flag | Read | ||
| BV | 169 | AMA Running | Drive status flag | Read | ||
| BV | 170 | Start CW/CCW | Drive status flag | Read | ||
| BV | 171 | Slowdown | Drive status flag | Read | ||
| BV | 172 | Catch up | Drive status flag | Read | ||
| BV | 173 | Feedback High | Drive status flag | Read | ||
| BV | 174 | Feedback Low | Drive status flag | Read | ||
| BV | 175 | Output Current High | Drive status flag | Read | ||
| BV | 176 | Output Current Low | Drive status flag | Read | ||
| BV | 177 | Output Freq High | Drive status flag | Read | ||
| BV | 178 | Output Freq low | Drive status flag | Read | ||
| BV | 179 | Brake Check OK | Drive status flag | Read | ||
| BV | 180 | Brake Max | Drive status flag | Read | ||
| BV | 181 | Braking | Drive status flag | Read | ||
| BV | 182 | Out of Speed range | Drive status flag | Read | ||
| BV | 183 | OVC Active | Drive status flag | Read | ||
| BV | 184 | AC Brake | Drive status flag | Read | ||
| BV | 185 | Password Timelock | Drive status flag | Read | ||
| BV | 186 | Password status | Drive status flag | Read | ||
| BV | 187 | Reference high | Drive status flag | Read | ||
| BV | 188 | Reference low | Drive status flag | Read | ||
| BV | 189 | Reference site | Drive status flag | Read | ||
| BV | 190 | Reserved - P1694/22 | Reserved status bit | Read | ||
| BV | 191 | Reserved - P1694/23 | Reserved status bit | Read | ||
| BV | 192 | Reserved - P1694/24 | Reserved status bit | Read | ||
| BV | 193 | Reserved - P1694/25 | Reserved status bit | Read | ||
| BV | 194 | Reserved - P1694/26 | Reserved status bit | Read | ||
| BV | 195 | Reserved - P1694/27 | Reserved status bit | Read | ||
| BV | 196 | Reserved - P1694/28 | Reserved status bit | Read | ||
| BV | 197 | Reserved - P1694/29 | Reserved status bit | Read | ||
| BV | 198 | Reserved - P1694/30 | Reserved status bit | Read | ||
| BV | 199 | Reserved - P1694/31 | Reserved status bit | Read | ||
| MO | 0 | Setup command | Selects the active parameter setup | Write |
No points match these filters.
Object ID lookup: Bell & Gossett MCA 109 Advanced point IDs by name
AI0Analog Input 53AI1Analog Input 54AI2Analog Input X30/11AI3Analog Input X30/12AI4Analog Input X42/1AI5Analog Input X42/3AI6Analog Input X42/5AO0Terminal 42 Output Bus ControlAO1Pulse out #27 Bus ControlAO2Pulse out #29 Bus ControlAO3Analogue Out X30/8 [mA]AO4Analogue Out X42/7 [V]AO5Analogue Out X42/9 [V]AO6Analogue Out X42/11 [V]AV0ReferenceAV1Speed Act ValueAV2Bus Feedback1AV3Bus Feedback2AV4Bus Feedback3AV5Motor VoltageAV6Motor CurrentAV7Torque [%]AV8DC Link VoltageAV9Motor ThermalAV10Heatsink Temp.AV11Inverter ThermalAV12Operating HoursAV13Running HoursAV14KWh CounterAV15Power [KW]AV16PID Start Speed [Hz]AV17PID Proportional GainAV18PID Integral TimeAV19PID Differential TimeAV20PID Dif. Gain LimitAV21On Reference BandwithAV22Ext. 1 SetpointAV23Ext. 1 Reference [Unit]AV24Ext. 1 Feedback [Unit]AV25Ext. 1 Propotional GainAV27Ext. 1 Integral TimeAV28Ext. 1 Differential TimeAV29Ext. 1 Dif. Gain LimitAV31Ext. 2 SetpointAV32Ext. 2 reference [Unit]AV33Ext. 2 Feedback [Unit]AV34Ext. 2 Proportional GainAV35Ext. 2 Integral TimeAV36Ext. 2 Differential TimeAV37Ext. 2 Dif. GainAV38Ext. 3 SetpointAV39Ext. 3 Reference [Unit]AV40Ext. 3 Feedback [Unit]AV41Ext. 3 Proportional GainAV42Ext. 3 Integral TimeAV43Ext. 3 Differential TimeAV44Ext. 3 Dif. Gain LimitAV45Running BypassAV46Setpoint 1AV47Setpoint 2AV48Setpoint 3AV50FrequencyAV51Feedback [Unit]AV58Sensorless ReadoutBI0Digital input 33BI1Digital input 32BI2Digital input 29BI3Digital input 27BI4Digital input 19BI5Digital input 18BI6Digital input 37BI7Digital Input X30/2BI8Digital Input X30/3BI9Digital Input X30/4BI10Digital input P1660/10BI11Digital input P1660/11BI12Digital input P1660/12BI13Digital input P1660/13BI14Digital input P1660/14BI15Digital input P1660/15BO0Digital output 27BO1Digital output 29BO2GPIO Output Term X30/6BO3GPIO Output Term X30/7BO4Relay 1 outputBO5Relay 2 outputBO6Option B Relay 1 OutputBO7Option B Relay 2 OutputBO8Option B Relay 3 OutputBO9Reserved output P590/09BO10Reserved output P590/10BO11Reserved output P590/11BO12Reserved output P590/12BO13Reserved output P590/13BO14Reserved output P590/14BO15Reserved output P590/15BO16Option C Relay 1 OutputBO17Option C Relay 2 OutputBO18Option C Relay 3 OutputBO19Option C Relay 4 OutputBO20Option C Relay 5 OutputBO21Option C Relay 6 OutputBO22Option C Relay 7 OutputBO23Option C Relay 8 OutputBO24Reserved output P590/24BO25Reserved output P590/25BO26Reserved output P590/26BO27Reserved output P590/27BO28Reserved output P590/28BO29Reserved output P590/29BO30Reserved output P590/30BV0Com. FaultBV1StartBV2CoastingBV3CW/CCWBV4JogBV5ResetBV6Reset KwH CounterBV7Reset Running Hour CounterBV10Drive ReadyBV12Speed = referenceBV13Bus controlBV14TripBV15Trip LockBV16Motor runningBV17WarningBV21ECB Test ModeBV22ECB DrivemodeBV23ECB Aut. Bypass EnableBV24ECB Bypass ModeBV25ECB StateBV26ECB Overload TripBV27M2 FaultBV28M3 FaultBV29ECB External InterlockBV30ECB Manual OverrideBV40A: Brake checkBV41A: Pwr. Card TempBV42A: Earth FaultBV43A: Ctrl.Card TempBV44A: Ctrl. Word TOBV45A: Over CurrentBV46A: Torque LimitBV47A: Motor TH OverBV48A: Motor ETR OverBV49A: Inverter Overld.BV50A: DC under VoltBV51A: DC over VoltBV52A: Short CircuitBV53A: Inrush FaultBV54A: Mains FaultBV55A: AMA Not OKBV56A: Live Zero ErrorBV57A: Internal FaultBV58A: Brake OverloadBV59A: U Phase LossBV60A: V Phase LossBV61A: W Phase LossBV62A: Fieldbus FaultBV63A: 24 V Supply LowBV64A: Mains faultBV65A: 1.8V supply lowBV66A: Brake FailureBV67A: Brake IGBTBV68A: Option ChangedBV69A: Drive InitialisedBV70A: Safe StopBV71A: Alarm: Brake lowBV72A: Service trip 1691/0BV73A: Service trip 1691/1BV74A: Service trip 1691/2BV75A: Service trip 1691/3BV76A: Service trip 1691/4BV77A: No flowBV78A: Dry PumpBV79A: Curve endBV80A: Broken BeltBV81A: Discharge HighBV82A: Start faultBV83A: Speed limitBV84A: State fault 1691/12BV85A: State fault 1691/13BV86A: State fault 1691/14BV87A: State fault 1691/15BV88A: KTY Temparture errorBV89A: Drive Fan errorBV90A: ECB errorBV91A: Alarm 1691/19BV92A: Alarm 1691/20BV93A: Alarm 1691/21BV94A: Alarm 1691/22BV95A: Alarm 1691/23BV96A: Alarm 1691/24BV97A: Alarm 1691/25BV98A: Alarm 1691/26BV99A: Alarm P1691/27BV100A: Alarm 1691/28BV101A: Alarm 1691/29BV102A: Alarm 1691/30BV103A: Alarm 1691/31BV104W: Brake CheckBV105W: Pwr. Card TempBV106W: Earth FaultBV107W: Ctrl. Card TempBV108W: Crtl. Word TOBV109W: Over CurrentBV110W: Torque LimitBV111W: Motor Th OverBV112W: Motor ETR OverBV113W: Inverter overld.BV114W: DC under VoltBV115W: DC over VoltBV116W: DC Voltage LowBV117W: DC Voltage highBV118W: Mains Ph. LossBV119W: No MotorBV120W: Live Zero ErrorBV121W: 10V lowBV122W: Brake OverloadBV123W: Brake ResistorBV124W: Brake IGBTBV125W: Speed LimitBV126W: Fieldbus FaultBV127W: 24V Supply LowBV128W: Mains FailureBV129W: Current LimitBV130W: Low TempBV131W: Voltage LimitBV132W: Encoder lossBV133W: Output Freq. limitBV134W: Safe stopBV135W: Ext. StatusBV136W: Start delayedBV137W: Stop delayedBV138W: Clock failureBV139W: Fire mode was activeBV140W: Reserved - P1693/04BV141W: No FlowBV142W: Dry PumpBV143W: End of CurveBV144W: Belt BrokenBV145W: Discharge HighBV146W: Reserved - P1693/10BV147W: Reserved - P1693/11BV148W: Reserved - P1693/12BV149W: Reserved - P1693/13BV150W: Reserved - P1693/14BV151W: Reserved - P1693/15BV152W: Reserved - P1693/16BV153W: KTY TemperatureBV154W: Drive Fan failureBV155W: ECB failureBV156W: Reserved - P1693/20BV157W: Reserved - P1693/21BV158W: Reserved - P1693/22BV159W: Reserved - P1693/23BV160W: Reserved - P1693/24BV161W: Reserved - P1693/25BV162W: Reserved - P1693/26BV163W: Reserved - P1693/27BV164W: Reserved - P1693/28BV165W: Reserved - P1693/29BV166W: PTC TemperatureBV167W: Reserved - P1693/31BV168Ramping activeBV169AMA RunningBV170Start CW/CCWBV171SlowdownBV172Catch upBV173Feedback HighBV174Feedback LowBV175Output Current HighBV176Output Current LowBV177Output Freq HighBV178Output Freq lowBV179Brake Check OKBV180Brake MaxBV181BrakingBV182Out of Speed rangeBV183OVC ActiveBV184AC BrakeBV185Password TimelockBV186Password statusBV187Reference highBV188Reference lowBV189Reference siteBV190Reserved - P1694/22BV191Reserved - P1694/23BV192Reserved - P1694/24BV193Reserved - P1694/25BV194Reserved - P1694/26BV195Reserved - P1694/27BV196Reserved - P1694/28BV197Reserved - P1694/29BV198Reserved - P1694/30BV199Reserved - P1694/31MO0Setup command
Integration notes
- The point list prints names as e.g. "analog_value: 1 (Speed Act Value)"; the text in brackets is used as the object name here.
- Rows the list marks as Reserved or NA are left out.
- Binary values prefixed "W:" are warning bits and "A:" are alarm bits.
- Bus commands only take effect when the drive is set to accept bus control.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MCA 109 Advanced BACnet Option (FC-102) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)
How many BACnet points does the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) have?
This list has 297 BACnet objects: 7 analog inputs, 7 analog outputs, 50 analog values, 16 binary inputs, 31 binary outputs, 185 binary values, 1 multi-state output. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) BACnet points are writable?
81 of the 297 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Bell & Gossett MCA 109 Advanced BACnet Option (FC-102) BACnet documentation?
The source is BacNET Points Firmware 3.90 and above (MCA109 FC-102 Advanced BACnet Option / FC-102 Embedded BACnet) (BGBACNET), revision December 2019, published free by Bell & Gossett at https://prod.xylem.com/siteassets/brand/bell-amp-gossett/resources/manual/bgbacnet.pdf.
What are the minimum BACnet points to integrate the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)?
Start with BV 1 Start (Start/stop the drive from the BMS); AV 0 Reference (Speed reference from the BMS (open-loop control)); AV 46 Setpoint 1 (Process setpoint 1 (when the drive runs its own PID)); BV 5 Reset (Reset a tripped drive); BV 10 Drive Ready (Ready to run when given a start); BV 16 Motor running (Running status); BV 13 Bus control (Drive is under bus control); AV 50 Frequency (Output frequency); AV 15 Power [KW] (Drive output power); BV 14 Trip (Any active drive fault).
How do I enable BMS control of the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)?
BV 1 Start, BV 2 Coasting, BV 3 CW/CCW and BV 4 Jog are writable commands, and BV 13 shows whether the drive is under bus control. The point list does not explain how bus control is set up on the drive.
Can the BMS supply sensor values to the Bell & Gossett MCA 109 Advanced BACnet Option (FC-102)?
AV 2-4 Bus Feedback1-3 and the Ext. 1-3 setpoint/feedback values are writable; the point list does not describe how the drive uses them.
How do I check these points on the real MCA 109 Advanced BACnet Option (FC-102)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Bell & Gossett BACnet points lists
- Pump variable frequency drive
Bell & Gossett FC-102 Embedded BACnet (pump drive)
Bell & Gossett pump packages that use the FC-102 HVAC drive with its built-in BACnet MS/TP (firmware 3.90 and above).
Also known as: FC-102, FC102, VLT HVAC Drive FC 102 - Booster pump controller
Bell & Gossett TechnoForce e-MTV booster pump controller
Bell & Gossett (Xylem) TechnoForce e-MTV variable speed water booster systems with up to three pumps.
Also known as: TechnoForce e-MTV, e-MTV, B&G TechnoForce, TechnoForce Pump Controller, IM361 - Constant speed pump system controller
Bell & Gossett Technologic Constant Speed Pump Controller
Bell & Gossett Technologic constant speed pumping systems for up to six pumps, with the BACnet MS/TP interface.
Also known as: Technologic CS, Technologic constant speed, B&G Technologic, ITT Technologic
Source: BacNET Points Firmware 3.90 and above (MCA109 FC-102 Advanced BACnet Option / FC-102 Embedded BACnet) · BGBACNET · rev. December 2019. Object names, instances and units are reproduced as published; descriptions are our own.