6-way pressure-independent control valve · BACnet points list
Belimo 6-way EPIV BACnet points list
Updated 28 October 2026
The 6-way EPIV combines a 6-way changeover valve with a flow sensor, so one coil can be fed from either a heating or a cooling circuit with flow control. On BACnet MS/TP a single AO 1 setpoint covers both sequences: in flow control, 0-33% runs sequence 1 from Vmax1 down to zero, 33-67% is the dead band, and 67-100% runs sequence 2 from zero up to Vmax2. It reports flow, position, active sequence and status.
This page lists 24 BACnet objects for the Belimo 6-way EPIV — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.
- Manufacturer
- Belimo
- Model
- 6-way EPIV
- Equipment
- 6-way pressure-independent control valve
- Equipment type
- Valves & actuators
- BACnet objects
- 24 (6 writable)
- Transport
- BACnet MS/TP
- Firmware
- 6-Way-EPIV V3.0
- Default device instance
- 1
- Also known as
- EP..R-R6+BAC, 6-way characterised control valve, Belimo 6-way valve
- Source document
- BACnet PICS, 6-way EPIV · rev. 2024-09
Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.
BMS integration notes: Belimo 6-way EPIV
Set MV 122 SpSource to Bus and command AO 1 SpRel, remembering that in flow control the 0-100% range is split into sequence 1, dead band and sequence 2. Set Vmax1 and Vmax2 once at commissioning. Read AI 19 flow, MI 1 active sequence and BI 101 summary status.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 1 | SpRel | Single setpoint for both heating/cooling sequences | Command |
| MV 122 | SpSource | Must be Bus for AO 1 to take effect | Write |
| MI 1 | ActSequence | Shows which sequence is active | Read |
| AI 19 | AbsFlow_UnitSel | Measured flow | Read |
| AI 1 | RelPos | Valve position feedback | Read |
| BI 101 | SummaryStatus | Overall OK / not OK alarm | Read |
Enable & remote start
Write MV 122 SpSource = 2 (Bus); with Analog (default) the valve follows the 0-10 V signal on wire 3. MO 1 Override can force sequence 1 or 2 open, close, or a sequence Vmax.
Network setup
- MS/TP only: baud 9600-76800, default 38400; MAC address 0-127, default 10.
- Default device instance 1.
- Max 32 nodes without repeater; the 120 Ω terminating resistor must be fitted externally.
- Configure with Belimo Assistant 2.
Watch out for
- Writable objects with instance 90 and above are persistent; do not write them on a regular basis.
- In flow control, setpoints 33-67% are a dead band with zero flow.
- Max 5 active COV subscriptions.
Belimo 6-way EPIV BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | RelPos | Relative valve position | % | Read | |
| AI | 2 | AbsPos | Absolute valve position | ° | Read | |
| AI | 5 | SpAnalog_V | Analog setpoint when setpoint source is analog | V | Read | |
| AI | 10 | RelFlow | Flow relative to active Vmax | % | Read | |
| AI | 13 | AbsFlow_gpm | Absolute flow | gpm | Read | |
| AI | 15 | AbsFlow_lh | Absolute flow | l/h | Read | |
| AImin | 19 | AbsFlow_UnitSel | Absolute flow in selected unit | m³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 121) | Read | |
| AI | 109 | SpAbsFlow_UnitSel | Active flow setpoint in selected unit | m³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 121) | Read | |
| AOmin | 1 | SpRel | Relative setpoint; flow mode splits it into two sequences | % | Command | |
| AV | 99 | Vmax1 | Maximum flow limit, sequence 1 (5-100% of nominal) | % | Write | |
| AV | 100 | Vmax2 | Maximum flow limit, sequence 2 (5-100% of nominal) | % | Write | |
| AV | 102 | Vnom_gpm | Nominal flow (depends on DN size) | gpm | Read | |
| AV | 115 | Vnom_lh | Nominal flow (depends on DN size) | l/h | Read | |
| AV | 119 | Vnom_UnitSel | Nominal flow in selected unit | m³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 121) | Read | |
| BImin | 101 | SummaryStatus | Summary of status objects MI 103-106 | Read | Inactive=OK, Active=Not OK | |
| MImin | 1 | ActSequence | Active sequence | Read | 1=Sequence 1, 2=Sequence 2, 3=Dead Band | |
| MI | 103 | StatusSensor | Flow sensor status | Read | 1=OK, 2=Flow sensor not OK | |
| MI | 104 | StatusFlow | Flow status | Read | 1=OK, 2=-, 3=Flow not reached, 4=Flow in closed position | |
| MI | 105 | StatusMedia | Medium status (air bubbles) | Read | 1=OK, 2=Airbubbles | |
| MI | 106 | StatusActuator | Actuator status | Read | 1=OK, 2=Actuator cannot move, 3=Gear disengaged | |
| MO | 1 | Override | Override control of the setpoint | Command | 1=None, 2=Sequence 1 open, 3=Sequence 2 open, 4=Close, 5=Sequence 1 Vmax, 6=Sequence 1 Vmax (printed twice; likely Sequence 2 Vmax) | |
| MV | 100 | ControlMode | Position or flow control | Read | 1=PosCtrl, 2=FlowCtrl | |
| MV | 121 | UnitSelFlow | Engineering unit for selected-unit flow objects | Write | 1=m³/s, 2=m³/h, 3=l/s, 4=l/min, 5=l/h, 6=gpm, 7=cfm | |
| MVmin | 122 | SpSource | Setpoint source: analog wire 3 or bus AO 1 | Write | 1=Analog, 2=Bus |
No points match these filters.
Object ID lookup: Belimo 6-way EPIV point IDs by name
AI1RelPosAI2AbsPosAI5SpAnalog_VAI10RelFlowAI13AbsFlow_gpmAI15AbsFlow_lhAI19AbsFlow_UnitSelAI109SpAbsFlow_UnitSelAO1SpRelAV99Vmax1AV100Vmax2AV102Vnom_gpmAV115Vnom_lhAV119Vnom_UnitSelBI101SummaryStatusMI1ActSequenceMI103StatusSensorMI104StatusFlowMI105StatusMediaMI106StatusActuatorMO1OverrideMV100ControlModeMV121UnitSelFlowMV122SpSource
Integration notes
- MV 100 ControlMode has no access marking in the document, so it is listed read-only here; it is likely writable.
- MO 1 state 6 is printed with the same text as state 5.
- MV 121 sets the unit of AI 19, AI 109 and AV 119 (the document refers to AV 119 as AI 119).
- Air bubbles in the system force position control until they clear, regardless of MV 100.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 6-way EPIV and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Belimo 6-way EPIV
How many BACnet points does the Belimo 6-way EPIV have?
This list has 24 BACnet objects: 8 analog inputs, 1 analog output, 5 analog values, 1 binary input, 5 multi-state inputs, 1 multi-state output, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Belimo 6-way EPIV BACnet points are writable?
6 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Belimo 6-way EPIV BACnet documentation?
The source is BACnet PICS, 6-way EPIV, revision 2024-09, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_6way-EPIV_en-gb.pdf.
What are the minimum BACnet points to integrate the Belimo 6-way EPIV?
Start with AO 1 SpRel (Single setpoint for both heating/cooling sequences); MV 122 SpSource (Must be Bus for AO 1 to take effect); MI 1 ActSequence (Shows which sequence is active); AI 19 AbsFlow_UnitSel (Measured flow); AI 1 RelPos (Valve position feedback); BI 101 SummaryStatus (Overall OK / not OK alarm).
How do I enable BMS control of the Belimo 6-way EPIV?
Write MV 122 SpSource = 2 (Bus); with Analog (default) the valve follows the 0-10 V signal on wire 3. MO 1 Override can force sequence 1 or 2 open, close, or a sequence Vmax.
How do I check these points on the real 6-way EPIV?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Belimo BACnet points lists
- Pressure-independent control valve
Belimo 2-way EPIV V4
Belimo 2-way electronic pressure-independent valves (EPIV) version 4.2, DN 15 to 50, BACnet models EP..R2+(K)BAC.
Also known as: EPIV, EP..R2+BAC, EP..R2+KBAC, Electronic Pressure Independent Valve, 2-way EPIV DN 15-50 - Ultrasonic liquid flow sensor
Belimo 22PF Flow Sensor
Belimo 22PF-.. ultrasonic flow sensors for water and glycol pipes, interface version 4.3.0.
Also known as: 22PF, 22PF-.., Belimo ultrasonic flow sensor, Flow Sensor 22PF - 6-way pressure-independent zone valve
Belimo 6-way PI zone valve (C6..QP..+BAC)
Belimo 6-way pressure-independent zone valves C615QP-B/D/F+BAC and C620QPT-G+BAC, application 6-Way-PIQCV V1.0, on BACnet MS/TP.
Also known as: C6..QP(T)-..+BAC, C615QP-B+BAC, C615QP-D+BAC, C615QP-F+BAC, C620QPT-G+BAC, 6-Way-PIQCV, 6-way PI zone valve, Belimo 6-way PIQCV - Damper and valve actuator
Belimo Air/Water Actuators (BACnet MS/TP)
Belimo general-purpose damper and valve actuators with the BACnet MS/TP interface (rotary, linear and fail-safe types).
Also known as: Belimo air/water actuator, Belimo AirWater BACnet, ..M(C)24A, ..R24A, ..V(K)24A, ..F24A, ..RF24A - Fire damper actuator interface
Belimo BKN230-24-MOD fire damper communication and power unit
Belimo BKN230-24-MOD unit that powers and networks one motorised fire damper actuator (BF24..-ST, BFN24..-ST, BFL24..-ST).
Also known as: BKN230-24-MOD, BKN230-24-MOD-BAC, BKN230, Belimo BKN230 BACnet, Schako BKN230, 71589-00002 - Zone valve actuator
Belimo CQ24A-BAC CQ zone rotary actuator
Belimo CQ24A-BAC rotary actuator for CQ zone valves, BACnet MS/TP application version 01.05.0001.
Also known as: CQ24A-BAC, CQ Zone Rotary Actuator, Belimo CQ BACnet, ZoneTight CQ actuator - Duct / outdoor sensors (temperature, humidity, CO2, VOC, differential pressure)
Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet
Belimo BACnet MS/TP sensors: 22DTH duct temperature/humidity, 22UTH outdoor temperature/humidity, 22DTM duct CO2/VOC and 22ADP differential pressure/airflow sensors.
Also known as: 22DTH-..6.., 22UTH-..60X, 22DTM-..6, 22ADP-..6.., 22DTH-16M, 22DTH-56M, 22UTH-160X, 22UTH-560X, 22DTM-16, 22DTM-56, 22ADP-164, 22ADP-164L, 22ADP-56Q, 22ADP-56QB, 22ADP-564L, 22ADP-566L - Pressure-independent control valve with energy meter
Belimo Energy Valve V3
Belimo Energy Valve generation 3 (EV..R+(K)BAC, EV..R3+BAC, EV..F+(K)BAC), the installed base before Energy Valve V4.
Also known as: Energy Valve, EV..R+BAC, EV..R+KBAC, EV..R3+BAC, EV..F+BAC, EV..F+KBAC, Belimo Energy Valve 3 - Pressure-independent control valve with energy meter
Belimo Energy Valve V4
Belimo Energy Valve version 4, DN 15 to 50, BACnet models EV..R2+(K)BAC, EV..R2+MID and EV..R3+BAC.
Also known as: Energy Valve, EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Belimo Energy Valve 4 - Fire and smoke damper actuator test module
Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module
Belimo FSKN120-BAC and FSKN24-BAC remote test modules for spring-return fire and combination fire/smoke damper actuators (FSTF, FSLF, FSNF, FSAFB, FSAF*A) in containment applications.
Also known as: FSKN120-BAC, FSKN24-BAC, FSKN, Belimo FSKN BACnet - Gas detection sensor / monitor
Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others)
Belimo 22G..-5A and 22G..-5B wall gas monitors (CO, NO2, CO2, NH3, refrigerant and other gases) with CAN bus and BACnet MS/TP.
Also known as: 22G, 22G02-5A, 22G02-5B, 22G14-5A, 22G14-5B, 22G0214-5A, 22G0214-5B, Belimo gas monitor BACnet, Belimo CO monitor - Valve actuator (Ethernet, IoT)
Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)
Belimo IoT product range valve actuators VLM/VLR, VNM/VNR, VSM/VSR and VGM/VGR 24A-LP1 with Ethernet and BACnet IP.
Also known as: VLM24A-LP1, VLR24A-LP1, VNM24A-LP1, VNR24A-LP1, VSM24A-LP1, VSR24A-LP1, VGM24A-LP1, VGR24A-LP1, Belimo IoT Product Range - Butterfly valve actuator
Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo JR rotary actuators for butterfly valves in the BACnet MS/TP version (JR..A-BAC-..).
Also known as: JR actuator, JR..A-BAC-.., Belimo JR BACnet, JR/QR - Butterfly valve actuator
Belimo PR..-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo PR rotary actuators for butterfly valves in the BACnet MS/TP version (PR..-BAC-..).
Also known as: PR..-BAC-.., Belimo PR actuator, PR BACnet - Room sensor / operating unit
Belimo Room Operating Unit 22RT-5U00
Belimo 22RT...-5U00... room operating units with virtual or ePaper touch display, measuring temperature, humidity and CO2.
Also known as: 22RT, 22RT…-5U00…, Room Operating Unit, ROU, 22RTM-5U00, Belimo room sensor BACnet - Thermal (BTU) energy meter
Belimo Thermal Energy Meter V4
Belimo Thermal Energy Meters version 4, DN 15 to 50 (22PE..-1U.., including MID-certified 22PEM models).
Also known as: TEM, Thermal Energy Meter, 22PE-1U, 22PEM-1UC, 22PE…-1U.., Belimo energy meter - VAV compact controller (actuator with flow sensor)
Belimo VAV-Compact
Belimo VAV-Compact volumetric flow controllers with the BACnet/Modbus interface (..MV-D3-MOD and ..HV24A-MOD).
Also known as: VAV-Compact MOD, ..MV-D3-MOD, ..HV24A-MOD, LMV-D3-MOD, NMV-D3-MOD, SMV-D3-MOD, LHV24A-MOD - VAV / CAV / pressure controller
Belimo VAV-Universal VRU
Belimo VAV-Universal controllers VRU-D3-BAC, VRU-M1-BAC and VRU-M1R-BAC used for VAV/CAV airflow, duct pressure and room pressure control.
Also known as: VAV-Universal, VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC, VRU-..-BAC - Rooftop unit economizer controller
Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM)
Belimo ZIP Economizer controllers for packaged rooftop units (ECON-ZIP-BASE) with the ECON-ZIP-COM communication module for BACnet MS/TP.
Also known as: ZIP Economizer, ECON-ZIP-BASE, ECON-ZIP-COM, ECON-ZIP-EM, Belimo economizer controller BACnet, ZIP Economizer BACnet - VAV zone controller / actuator
Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)
Belimo ZoneEase VAV actuators LMV-BAC-.. and NMV-BAC-.. with the built-in zone control applications, application software ZoneEase 1.7.
Also known as: ZoneEase VAV, LMV-BAC-.., NMV-BAC-.., Belimo ZoneEase
Source: BACnet PICS, 6-way EPIV · rev. 2024-09. Object names, instances and units are reproduced as published; descriptions are our own.