- Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
Ultrasonic flow and BTU meter (BACnet IP card) · BACnet points list
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet points list
Updated 11 November 2026
With the optional Ethernet card set to BACnet/IP, the TFX-5000 serves a read-only set of Analog Values: flow rate and velocity (home-screen, US and metric units), totals and overflow counters in home-screen units, gallons and liters, cutoff settings and signal strength, plus Multi-state Values that report the selected units. Energy meters add energy rate, two temperatures, delta T and energy totals in home-screen units, kBTU and kWh. The instance numbers differ from the RS-485 BACnet MS/TP list.
This page lists 73 BACnet objects for the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Badger Meter’s own free documentation, linked below.
- Manufacturer
- Badger Meter
- Model
- Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
- Equipment
- Ultrasonic flow and BTU meter (BACnet IP card)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 73 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- TFX-5000 BACnet/IP, TFX-5000 Ethernet, Dynasonics TFX-5000 BACnet IP, TTM-UM-03250, TFX-5000 Energy BACnet IP
Reference only, provided as-is: verify against Badger Meter’s current documentation and the live device before use. Not official Badger Meter information. Terms of use.
BMS integration notes: Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
Fit the Ethernet card, set Card Type to Autodetect or BACnet/IP, then read flow rate, the net total and (on BTU meters) energy rate, temperatures and the net energy total. All objects are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 600 | Flow Rate on Screen | Flow rate, home-screen units | Read |
| AV 1100 | Flow Totalizer, Net | Net volume total, home-screen units | Read |
| AV 604 | Energy/BTU Rate | Energy rate (BTU meters) | Read |
| AV 605 | Temperature #1 | Temperature 1 (BTU meters) | Read |
| AV 606 | Temperature #2 | Temperature 2 (BTU meters) | Read |
| AV 1108 | Energy/BTU Total, Net | Net energy total (BTU meters) | Read |
| AV 1500 | Signal Quality | Ultrasonic signal strength | Read |
Network setup
- The BACnet/IP card is an option with an RJ-45 port; set Main Menu > System Setup > Options > Card Type to Autodetect or BACnet/IP.
- Network and BACnet settings are made in the meter's BACnet/IP menu.
Watch out for
- Totals are 32-bit AVs only on this card; watch the overflow counters on large totals.
- Flow-only meters do not have the energy and temperature objects.
- Instance numbers differ from the RS-485 BACnet MS/TP list; don't reuse an MS/TP mapping.
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 600 | Flow Rate on Screen | Flow Rate in home-screen units | Read | ||
| AV | 601 | Velocity on Screen | Velocity in home-screen units | Read | ||
| AV | 602 | Delta Time Filtered (ns) | Upstream/downstream transit-time difference | ns | Read | |
| AVmin | 604 | Energy/BTU Rate | Energy rate in home-screen units | Read | ||
| AVmin | 605 | Temperature #1 | Temperature 1 in home-screen units | Read | ||
| AVmin | 606 | Temperature #2 | Temperature 2 in home-screen units | Read | ||
| AV | 607 | Delta Temperature | Temperature difference in home-screen units | Read | ||
| AV | 800 | Flow Rate (gal/min) | Flow rate | gal/min | Read | |
| AV | 801 | Velocity (ft/sec) | Fluid velocity | ft/s | Read | |
| AV | 802 | Energy Rate (kBTU/h) | Energy rate | kBTU/h | Read | |
| AV | 1000 | Flow Rate (l/min) | Flow rate | L/min | Read | |
| AV | 1001 | Velocity (m/sec) | Fluid velocity | m/s | Read | |
| AV | 1002 | Energy Rate (kW) | Energy rate | kW | Read | |
| AV | 1304 | Flow Total Decimal Places | Decimal places shown for flow totals | Read | ||
| AV | 1309 | Energy Total Decimal Places | Decimal places shown for energy totals | Read | ||
| AVmin | 1100 | Flow Totalizer, Net | Forward minus reverse volume, home-screen units | Read | ||
| AV | 1101 | Flow Totalizer, Positive | Forward volume total, home-screen units | Read | ||
| AV | 1102 | Flow Totalizer, Negative | Reverse volume total, home-screen units | Read | ||
| AV | 1103 | Flow Totalizer, Gross | Forward plus reverse volume, home-screen units | Read | ||
| AV | 1104 | Flow Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1105 | Flow Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1106 | Flow Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1107 | Flow Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AVmin | 1108 | Energy/BTU Total, Net | Positive minus negative energy, home-screen units | Read | ||
| AV | 1109 | Energy/BTU Total, Positive | Energy total, forward (heating), home-screen units | Read | ||
| AV | 1110 | Energy/BTU Total, Negative | Energy total, reverse (cooling), home-screen units | Read | ||
| AV | 1111 | Energy/BTU Total, Gross | Positive plus negative energy, home-screen units | Read | ||
| AV | 1112 | Energy/BTU Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1113 | Energy/BTU Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1114 | Energy/BTU Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1115 | Energy/BTU Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AV | 1150 | Flow Totalizer (gal), Net | Forward minus reverse volume | gal | Read | |
| AV | 1151 | Flow Totalizer (gal), Positive | Forward volume total | gal | Read | |
| AV | 1152 | Flow Totalizer (gal), Negative | Reverse volume total | gal | Read | |
| AV | 1153 | Flow Totalizer (gal), Gross | Forward plus reverse volume | gal | Read | |
| AV | 1154 | Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1155 | Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1156 | Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1157 | Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AV | 1158 | Energy/BTU Total (kBTU), Net | Positive minus negative energy | kBTU | Read | |
| AV | 1159 | Energy/BTU Total (kBTU), Positive | Energy total, forward (heating) | kBTU | Read | |
| AV | 1160 | Energy/BTU Total (kBTU), Negative | Energy total, reverse (cooling) | kBTU | Read | |
| AV | 1161 | Energy/BTU Total (kBTU), Gross | Positive plus negative energy | kBTU | Read | |
| AV | 1162 | kBTU Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1163 | kBTU Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1164 | kBTU Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1165 | kBTU Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AV | 1200 | Flow Totalizer (liters), Net | Forward minus reverse volume | L | Read | |
| AV | 1201 | Flow Totalizer (liters), Positive | Forward volume total | L | Read | |
| AV | 1202 | Flow Totalizer (liters), Negative | Reverse volume total | L | Read | |
| AV | 1203 | Flow Totalizer (liters), Gross | Forward plus reverse volume | L | Read | |
| AV | 1204 | Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1205 | Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1206 | Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1207 | Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AV | 1208 | Energy Total (kWh), Net | Positive minus negative energy | kWh | Read | |
| AV | 1209 | Energy Total (kWh), Positive | Energy total, forward (heating) | kWh | Read | |
| AV | 1210 | Energy Total (kWh), Negative | Energy total, reverse (cooling) | kWh | Read | |
| AV | 1211 | Energy Total (kWh), Gross | Positive plus negative energy | kWh | Read | |
| AV | 1212 | kWh Totalizer Overflow Counter, Net | Times this total has rolled over | Read | ||
| AV | 1213 | kWh Totalizer Overflow Counter, Positive | Times this total has rolled over | Read | ||
| AV | 1214 | kWh Totalizer Overflow Counter, Negative | Times this total has rolled over | Read | ||
| AV | 1215 | kWh Totalizer Overflow Counter, Gross | Times this total has rolled over | Read | ||
| AV | 1400 | Low Flow Cutoff | Flow below this reads zero and stops totalizing | Read | ||
| AV | 1401 | Low Signal Cutoff | Signal below this reads zero flow | Read | ||
| AV | 1402 | High Signal Cutoff | Signal above this reads zero flow | Read | ||
| AVmin | 1500 | Signal Quality | Ultrasonic signal strength | Read | ||
| MV | 1300 | Flow Rate Units | Flow Rate units selected for the home screen | Read | 1=L/s, 2=L/min, 3=L/h, 4=m³/s, 5=m³/min, 6=m³/h, 7=ft³/s, 8=ft³/min, 9=ft³/h, 10=gal/s, 11=gal/min, 12=gal/h, 13=Mgal/day, 14=Imp gal/s, 15=Imp gal/min, 16=Imp gal/h, 19=oil bbl/min, 20=Mega Imp gal/day, 21=oil bbl/day, 22=acre-ft/day, 23=fluid bbl/day, 24=Imp bbl/day, 25=custom | |
| MV | 1302 | Velocity Units | Velocity units selected for the home screen | Read | 1=m/s, 10=ft/s | |
| MV | 1303 | Flow Total Units | Flow Total units selected for the home screen | Read | 1=L, 2=hL, 3=m³, 4=ft³, 5=gal, 6=Mgal, 7=Imp gal, 10=acre-ft, 11=oil bbl, 12=Imp Mgal, 13=liquid bbl, 17=custom | |
| MV | 1306 | Energy Rate Units | Energy Rate units selected for the home screen | Read | 1=custom, 2=W, 3=kW, 4=MW, 5=BTU/h, 6=kBTU/h, 7=MBTU/h, 8=kJ/h, 9=MJ/h, 10=kcal/h, 11=Mcal/h, 12=tons | |
| MV | 1308 | Temperature Units | Temperature units selected for the home screen | Read | 1=°C, 2=°F, 3=K | |
| MV | 1309 | Energy Total Units | Energy Total units selected for the home screen | Read | 1=custom, 2=Wh, 3=kWh, 4=MWh, 5=BTU, 6=kBTU, 7=MMBTU, 8=kJ, 9=MJ, 10=kcal, 11=Mcal, 12=ton-hours |
No points match these filters.
Object ID lookup: Badger Meter TFX-5000 BACnet/IP point IDs by name
AV600Flow Rate on ScreenAV601Velocity on ScreenAV602Delta Time Filtered (ns)AV604Energy/BTU RateAV605Temperature #1AV606Temperature #2AV607Delta TemperatureAV800Flow Rate (gal/min)AV801Velocity (ft/sec)AV802Energy Rate (kBTU/h)AV1000Flow Rate (l/min)AV1001Velocity (m/sec)AV1002Energy Rate (kW)AV1304Flow Total Decimal PlacesAV1309Energy Total Decimal PlacesAV1100Flow Totalizer, NetAV1101Flow Totalizer, PositiveAV1102Flow Totalizer, NegativeAV1103Flow Totalizer, GrossAV1104Flow Totalizer Overflow Counter, NetAV1105Flow Totalizer Overflow Counter, PositiveAV1106Flow Totalizer Overflow Counter, NegativeAV1107Flow Totalizer Overflow Counter, GrossAV1108Energy/BTU Total, NetAV1109Energy/BTU Total, PositiveAV1110Energy/BTU Total, NegativeAV1111Energy/BTU Total, GrossAV1112Energy/BTU Totalizer Overflow Counter, NetAV1113Energy/BTU Totalizer Overflow Counter, PositiveAV1114Energy/BTU Totalizer Overflow Counter, NegativeAV1115Energy/BTU Totalizer Overflow Counter, GrossAV1150Flow Totalizer (gal), NetAV1151Flow Totalizer (gal), PositiveAV1152Flow Totalizer (gal), NegativeAV1153Flow Totalizer (gal), GrossAV1154Totalizer Overflow Counter, NetAV1155Totalizer Overflow Counter, PositiveAV1156Totalizer Overflow Counter, NegativeAV1157Totalizer Overflow Counter, GrossAV1158Energy/BTU Total (kBTU), NetAV1159Energy/BTU Total (kBTU), PositiveAV1160Energy/BTU Total (kBTU), NegativeAV1161Energy/BTU Total (kBTU), GrossAV1162kBTU Totalizer Overflow Counter, NetAV1163kBTU Totalizer Overflow Counter, PositiveAV1164kBTU Totalizer Overflow Counter, NegativeAV1165kBTU Totalizer Overflow Counter, GrossAV1200Flow Totalizer (liters), NetAV1201Flow Totalizer (liters), PositiveAV1202Flow Totalizer (liters), NegativeAV1203Flow Totalizer (liters), GrossAV1204Totalizer Overflow Counter, NetAV1205Totalizer Overflow Counter, PositiveAV1206Totalizer Overflow Counter, NegativeAV1207Totalizer Overflow Counter, GrossAV1208Energy Total (kWh), NetAV1209Energy Total (kWh), PositiveAV1210Energy Total (kWh), NegativeAV1211Energy Total (kWh), GrossAV1212kWh Totalizer Overflow Counter, NetAV1213kWh Totalizer Overflow Counter, PositiveAV1214kWh Totalizer Overflow Counter, NegativeAV1215kWh Totalizer Overflow Counter, GrossAV1400Low Flow CutoffAV1401Low Signal CutoffAV1402High Signal CutoffAV1500Signal QualityMV1300Flow Rate UnitsMV1302Velocity UnitsMV1303Flow Total UnitsMV1306Energy Rate UnitsMV1308Temperature UnitsMV1309Energy Total Units
Integration notes
- This is the energy-meter table; flow-only meters lack AV 604-607, AV 802, AV 1002, AV 1309, the energy totals and counters (AV 1108-1115, 1158-1165, 1208-1215) and MV 1306, 1308, 1309.
- Every object in this list is read-only; the BACnet/IP card has no reset or reboot objects.
- The flow-meter table names AV 1500 'Signal Strength'; the energy-meter table calls it 'Signal Quality'.
- Several overflow counters share a name; the instance tells them apart.
- If the BACnet/IP menu is missing, set Main Menu > System Setup > Options > Card Type to Autodetect or BACnet/IP.
- Source is user manual TTM-UM-03250-EN-04 (January 2026).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)
How many BACnet points does the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) have?
This list has 73 BACnet objects: 67 analog values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card) BACnet documentation?
The source is TFX-5000 Meter BACnet/IP Ethernet Protocol User Manual (TTM-UM-03250-EN-04), revision 2026-01, published free by Badger Meter at https://badgermeter.widen.net/content/slo6qi1gwu/original?download=false&x.app=api.
What are the minimum BACnet points to integrate the Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)?
Start with AV 600 Flow Rate on Screen (Flow rate, home-screen units); AV 1100 Flow Totalizer, Net (Net volume total, home-screen units); AV 604 Energy/BTU Rate (Energy rate (BTU meters)); AV 605 Temperature #1 (Temperature 1 (BTU meters)); AV 606 Temperature #2 (Temperature 2 (BTU meters)); AV 1108 Energy/BTU Total, Net (Net energy total (BTU meters)); AV 1500 Signal Quality (Ultrasonic signal strength).
How do I check these points on the real Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet/IP card)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Badger Meter BACnet points lists
- Btu energy meter (transmitter)
Badger Meter Data Industrial Series 340 BN/MB Btu energy transmitter (BACnet MS/TP)
Badger Meter / Data Industrial 340 BN/MB Btu energy transmitters with one pulse or sine flow sensor and two temperature sensors.
Also known as: 340 BN/MB, 340BN/MB, B340BN, Series 340, Data Industrial 340, Badger 340 Btu transmitter, XMT-UM-01660 - Btu energy meter (impeller)
Badger Meter Data Industrial Series 380 impeller Btu system 380CS / 380HS (BACnet MS/TP)
Badger Meter / Data Industrial Series 380 impeller Btu systems (380CS cold, 380HS hot) with the RS-485 output set to BACnet.
Also known as: Series 380, 380CS, 380HS, 380CS/HS, Data Industrial 380, Badger 380 Btu meter, 880102-0001 - Ultrasonic flow / energy meter
Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet IP Ethernet module)
Dynasonics TFX Ultra clamp-on flow and energy transmitters ordered with the Ethernet module, set to BACnet IP.
Also known as: TFX Ultra, TFX Ultra BACnet IP, Dynasonics TFX Ultra, TFX Ultra Ethernet, TTM-UM-00136 - Ultrasonic flow / energy meter
Badger Meter Dynasonics TFX Ultra transit-time flow / energy meter (BACnet MS/TP)
Dynasonics TFX Ultra clamp-on flow and energy transmitters ordered with the BACnet MS/TP RS-485 option.
Also known as: TFX Ultra, TFX Ultra BACnet MS/TP, Dynasonics TFX Ultra, TTM-UM-00136 - Ultrasonic flow and BTU meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-5000 ultrasonic flow / energy meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-5000 clamp-on ultrasonic flow meters and TFX-5000 energy (BTU) meters, using the built-in RS-485 port in BACnet MS/TP mode.
Also known as: TFX-5000, Dynasonics TFX-5000, TFX-5000 BACnet, TFX-5000 Energy, TTM-UM-03074, clamp-on BTU meter BACnet, Badger ultrasonic flow meter BACnet - Ultrasonic flow meter (clamp-on)
Badger Meter Dynasonics TFX-500w clamp-on ultrasonic flow meter (BACnet MS/TP)
Badger Meter Dynasonics TFX-500w clamp-on transit-time ultrasonic flow meters with the RS-485 port set to BACnet MS/TP.
Also known as: TFX-500w, TFX-500, Dynasonics TFX-500w, TTM-UM-02773 - Electromagnetic flow meter (BACnet daughterboard)
Badger Meter ModMAG M2000 electromagnetic flow meter (BACnet MS/TP and BACnet/IP)
Badger Meter ModMAG M2000 electromagnetic flow meters with the BACnet MS/TP or BACnet/IP communication daughterboard.
Also known as: M2000, ModMAG M2000, M2000 BACnet, M2000 mag meter BACnet, MAG-UM-03547, MAG-UM-03548, Badger mag meter BACnet - Vortex flow / BTU energy meter
Badger Meter VN2000 vortex flow meter (BACnet MS/TP)
Badger Meter VN2000 vortex flow meters for steam, gas and liquids (including BTU/energy models) with the optional BACnet MS/TP card.
Also known as: VN2000, Badger VN2000 vortex, VN2000 BTU meter
Source: TFX-5000 Meter BACnet/IP Ethernet Protocol User Manual · TTM-UM-03250-EN-04 · rev. 2026-01. Object names, instances and units are reproduced as published; descriptions are our own.