 "manufacturer": "AERCO",
 "manufacturer_slug": "aerco",
 "model": "ECS and SmartPlate water heaters (ProtoNode RER)",
 "model_slug": "ecs-smartplate-protonode",
 "aliases": [
  "ECS",
  "Electronic Control System",
  "SmartPlate",
  "SmartPlate water heater",
  "E Valve",
  "ProtoNode RER",
  "64084",
  "GF-129",
  "OMM-0080"
 ],
 "equipment_type": "Water heater controller via ProtoNode gateway",
 "applies_to": "AERCO SmartPlate and ECS (Electric Valve) water heaters, up to four, read through the AERCO ProtoNode RER.",
 "summary": "The AERCO ProtoNode RER profile for four ECS/SmartPlate systems serves 7 analog values per heater on BACnet IP or BACnet MS/TP: control output, setpoint in use, a writable remote setpoint, outlet and feedback temperatures, an alarm bit field and flow rate.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": "Node_Offset + A-bank DIP switch value (MAC); the manual's example uses Node_Offset 50,000",
 "access_inferred": false,
 "notes": [
  "Older document (OMM-0080_0H, November 2014) for the ProtoNode RER gateway.",
  "Object IDs are fixed per profile and do not follow a formula; heaters 1-4 are ECS/SmartPlate Modbus addresses 29-32.",
  "Point names repeat for each heater; the heater number is in the description."
 ],
 "integration": {
  "summary": "Set S2 On (S0, S1, S3, A1 Off) for the BACnet profile with 4 ECS/SP systems, give the heaters addresses 29-32, and for remote setpoint set Rmt = SP and L-r = rmt on each heater. Then write 03-RmSetpt and read outlet temperature, control output and the alarm bit field.",
  "minimum_points": [
   {
    "ref": "AV 81",
    "name": "03-RmSetpt",
    "why": "Heater 1 remote setpoint, 40-180 °F"
   },
   {
    "ref": "AV 80",
    "name": "02-Setpoint",
    "why": "Heater 1 setpoint in use, °F"
   },
   {
    "ref": "AV 84",
    "name": "04-Outlet Temp",
    "why": "Heater 1 outlet temperature, °F"
   },
   {
    "ref": "AV 11",
    "name": "01-Cntl Output Signal",
    "why": "Heater 1 control output, %"
   },
   {
    "ref": "AV 86",
    "name": "06-Over Temp Alarm",
    "why": "Heater 1 alarm bits; bit 0-3 = alarm 1-4"
   }
  ],
  "enable": "For remote setpoint control set Rmt = SP and L-r = rmt on the heater, then write its 03-RmSetpt. There is no start/stop object.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "S2 On, S0/S1/S3 Off, A1 Off = BACnet IP / MS/TP profile with 4 ECS/SP systems.",
   "Device instance = Node_Offset (set in the Web Configurator) + A-bank DIP value; MS/TP MAC is 1-127 on A0-A7, baud on B0-B3.",
   "Default IP 192.168.1.24; change it in the ProtoNode web GUI.",
   "Modbus side: every AERCO unit at 9600 baud, 8 data bits, 1 stop bit, no parity.",
   "ECS/SmartPlate controller address (Addr) 29-32."
  ],
  "gotchas": [
   "Heater object IDs are scattered (heater 1 setpoint is AV 80-81, heater 2 is AV 3-4); use the table, not a pattern."
  ]
 },
 "source": {
  "title": "AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129",
  "doc_number": "OMM-0080_0H",
  "revision_date": "2014-11-06",
  "url": "https://www.aerco.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/58249-source/637395359810000000/omm-0080-0h-gf-129-protonode-ler-rer-11-06-14.pdf"
 },
 "points": [
  {
   "type": "AV",
   "instance": 11,
   "name": "01-Cntl Output Signal",
   "description": "Heater 1: control output signal (0-100)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "02-Setpoint",
   "description": "Heater 1: setpoint in use (40-180)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "03-RmSetpt",
   "description": "Heater 1: remote setpoint written over the network (40-180)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "04-Outlet Temp",
   "description": "Heater 1: outlet temperature (40-205)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "05-FBk Sensor Temp",
   "description": "Heater 1: feedback sensor temperature (40-180)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "06-Over Temp Alarm",
   "description": "Heater 1: alarm bit field (alarms 1-4, manual, sensor/loop break, heater fail)",
   "units": "",
   "access": "R",
   "states": "Bit 0-3=Alarm 1-4 (1=alarm), Bit 4=Manual mode, Bit 5=Sensor break, Bit 6=Loop break, Bit 7=Heater fail"
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "07-Flow Rate",
   "description": "Heater 1: flow rate",
   "units": "GPM",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "01-Cntl Output Signal",
   "description": "Heater 2: control output signal (0-100)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "02-Setpoint",
   "description": "Heater 2: setpoint in use (40-180)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "03-RmSetpt",
   "description": "Heater 2: remote setpoint written over the network (40-180)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "04-Outlet Temp",
   "description": "Heater 2: outlet temperature (40-205)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "05-FBk Sensor Temp",
   "description": "Heater 2: feedback sensor temperature (40-180)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "06-Over Temp Alarm",
   "description": "Heater 2: alarm bit field (alarms 1-4, manual, sensor/loop break, heater fail)",
   "units": "",
   "access": "R",
   "states": "Bit 0-3=Alarm 1-4 (1=alarm), Bit 4=Manual mode, Bit 5=Sensor break, Bit 6=Loop break, Bit 7=Heater fail"
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "07-Flow Rate",
   "description": "Heater 2: flow rate",
   "units": "GPM",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "01-Cntl Output Signal",
   "description": "Heater 3: control output signal (0-100)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 150,
   "name": "02-Setpoint",
   "description": "Heater 3: setpoint in use (40-180)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "03-RmSetpt",
   "description": "Heater 3: remote setpoint written over the network (40-180)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 152,
   "name": "04-Outlet Temp",
   "description": "Heater 3: outlet temperature (40-205)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 153,
   "name": "05-FBk Sensor Temp",
   "description": "Heater 3: feedback sensor temperature (40-180)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 154,
   "name": "06-Over Temp Alarm",
   "description": "Heater 3: alarm bit field (alarms 1-4, manual, sensor/loop break, heater fail)",
   "units": "",
   "access": "R",
   "states": "Bit 0-3=Alarm 1-4 (1=alarm), Bit 4=Manual mode, Bit 5=Sensor break, Bit 6=Loop break, Bit 7=Heater fail"
  },
  {
   "type": "AV",
   "instance": 155,
   "name": "07-Flow Rate",
   "description": "Heater 3: flow rate",
   "units": "GPM",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "01-Cntl Output Signal",
   "description": "Heater 4: control output signal (0-100)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 158,
   "name": "02-Setpoint",
   "description": "Heater 4: setpoint in use (40-180)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 159,
   "name": "03-RmSetpt",
   "description": "Heater 4: remote setpoint written over the network (40-180)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 160,
   "name": "04-Outlet Temp",
   "description": "Heater 4: outlet temperature (40-205)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 161,
   "name": "05-FBk Sensor Temp",
   "description": "Heater 4: feedback sensor temperature (40-180)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 156,
   "name": "06-Over Temp Alarm",
   "description": "Heater 4: alarm bit field (alarms 1-4, manual, sensor/loop break, heater fail)",
   "units": "",
   "access": "R",
   "states": "Bit 0-3=Alarm 1-4 (1=alarm), Bit 4=Manual mode, Bit 5=Sensor break, Bit 6=Loop break, Bit 7=Heater fail"
  },
  {
   "type": "AV",
   "instance": 157,
   "name": "07-Flow Rate",
   "description": "Heater 4: flow rate",
   "units": "GPM",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/aerco/ecs-smartplate-protonode",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}