Power and energy meter (BACnet MS/TP module) · BACnet points list
Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module BACnet points list
Updated 28 October 2026
The AXM-BMS clips onto an Acuvim II power meter and serves 56 fixed Analog Value objects over BACnet MS/TP: frequency, voltages, currents, power per phase and total, power factor, unbalance, demand, energy totals and THD. No mapping is needed. The manual lists object names and data types but no units.
This page lists 56 BACnet objects for the Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Accuenergy’s own free documentation, linked below.
- Manufacturer
- Accuenergy
- Model
- Acuvim II with AXM-BMS BACnet MS/TP module
- Equipment
- Power and energy meter (BACnet MS/TP module)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 56 (0 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BMS, Acuvim II BACnet MS/TP, 1040E2102
Reference only, provided as-is: verify against Accuenergy’s current documentation and the live device before use. Not official Accuenergy information. Terms of use.
BMS integration notes: Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module
Set the meter's second port protocol to BACNET, then set the module's MS/TP MAC address, baud rate and max info frames from the meter's NET pages and reset the module. Read total power, imported energy, demand, power factor, current and voltage.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 17 | P_rms | Total active power, W | Read |
| AV 39 | Active_Energy_IMP | Imported active energy total | Read |
| AV 33 | P_dema | Active power demand | Read |
| AV 25 | S_rms | Total apparent power | Read |
| AV 29 | PF_rms | Total power factor | Read |
| AV 12 | Iavg_rms | Average phase current | Read |
| AV 8 | Ulavg_rms | Average line-to-line voltage | Read |
| AV 0 | Freq_rms | Supply frequency | Read |
Network setup
- Module defaults: MS/TP MAC 0, 9600 baud, max info frames 1.
- On the meter set S34 Protocol 2 = BACNET, then use the NET pages to set the MAC address (0-127), baud rate (9600, 19200, 38400 or 76800) and max info frames (1-255).
- Reset the module from the fourth NET page after any change.
- Up to 127 MS/TP masters; frames up to 480 bytes.
Watch out for
- Default MAC is 0; give each module a unique MS/TP address before connecting.
- No units are documented; check energy and THD scaling against the meter display.
Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 0 | Freq_rms | Frequency (Float) | Read | ||
| AV | 1 | Ua_rms | Voltage A (Float) | Read | ||
| AV | 2 | Ub_rms | Voltage B (Float) | Read | ||
| AV | 3 | Uc_rms | Voltage C (Float) | Read | ||
| AV | 4 | Uvag_rms | Average Phase Voltage (Float) | Read | ||
| AV | 5 | Uab_rms | Voltage A-B (Float) | Read | ||
| AV | 6 | Ubc_rms | Voltage B-C (Float) | Read | ||
| AV | 7 | Uca_rms | Voltage C-A (Float) | Read | ||
| AVmin | 8 | Ulavg_rms | Average Line Voltage (Float) | Read | ||
| AV | 9 | Ia_rms | Current A (Float) | Read | ||
| AV | 10 | Ib_rms | Current B (Float) | Read | ||
| AV | 11 | Ic_rms | Current C (Float) | Read | ||
| AVmin | 12 | Iavg_rms | Average Current (Float) | Read | ||
| AV | 13 | In_rms | Neutral Current (Float) | Read | ||
| AV | 14 | Pa_rms | Pa (Float) | Read | ||
| AV | 15 | Pb_rms | Pb (Float) | Read | ||
| AV | 16 | Pc_rms | Pc (Float) | Read | ||
| AVmin | 17 | P_rms | Total Active Power (Float) | Read | ||
| AV | 18 | Qa_rms | Qa (Float) | Read | ||
| AV | 19 | Qb_rms | Qb (Float) | Read | ||
| AV | 20 | Qc_rms | Qc (Float) | Read | ||
| AV | 21 | Q_rms | Total Reactive Power (Float) | Read | ||
| AV | 22 | Sa_rms | Sa (Float) | Read | ||
| AV | 23 | Sb_rms | Sb (Float) | Read | ||
| AV | 24 | Sc_rms | Sc (Float) | Read | ||
| AVmin | 25 | S_rms | Total Apparent Power (Float) | Read | ||
| AV | 26 | PFa_rms | PFa (Float) | Read | ||
| AV | 27 | PFb_rms | PFb (Float) | Read | ||
| AV | 28 | PFc_rms | PFc (Float) | Read | ||
| AVmin | 29 | PF_rms | Total Power Factor (Float) | Read | ||
| AV | 30 | Unbl_u2 | Voltage Imbalance (Float) | Read | ||
| AV | 31 | Unbl_i2 | Current Imbalance (Float) | Read | ||
| AV | 32 | Rlc_val | Load Characteristics (Float) | Read | ||
| AVmin | 33 | P_dema | P Demand (Float) | Read | ||
| AV | 34 | Q_dema | Q Demand (Float) | Read | ||
| AV | 35 | S_dema | S Demand (Float) | Read | ||
| AV | 36 | Ia_Demand | Ia Demand (Float) | Read | ||
| AV | 37 | Ib_Demand | Ib Demand (Float) | Read | ||
| AV | 38 | Ic_Demand | Ic Demand (Float) | Read | ||
| AVmin | 39 | Active_Energy_IMP | Active_Energy_IMP (UINT32) | Read | ||
| AV | 40 | Active_Energy_EXP | Active_Energy_EXP (UINT32) | Read | ||
| AV | 41 | Reactive_Energy_IMP | Reactive_Energy_IMP (UINT32) | Read | ||
| AV | 42 | Reactive_Energy_EXP | Reactive_Energy_EXP (UINT32) | Read | ||
| AV | 43 | Active_Energy_TOTAL | Active_Energy_TOTAL (UINT32) | Read | ||
| AV | 44 | Active_Energy_NET | Active_Energy_NET (SINT32) | Read | ||
| AV | 45 | Reactive_Energy_TOTAL | Reactive_Energy_TOTAL (UINT32) | Read | ||
| AV | 46 | Reactive_Energy_NET S | Reactive_Energy_NET (SINT32) | Read | ||
| AV | 47 | Apparent_Energy | Apparent_Energy (UINT32) | Read | ||
| AV | 48 | THD_V1 | THD_V1 (UINT32) | Read | ||
| AV | 49 | THD_V2 | THD_V2 (UINT32) | Read | ||
| AV | 50 | THD_V3 | THD_V3 (UINT32) | Read | ||
| AV | 51 | THD_V | THD_V (UINT32) | Read | ||
| AV | 52 | THD_I1 | THD_I1 (UINT32) | Read | ||
| AV | 53 | THD_I2 | THD_I2 (UINT32) | Read | ||
| AV | 54 | THD_I3 | THD_I3 (UINT32) | Read | ||
| AV | 55 | THD_I | THD_I (UINT32) | Read |
No points match these filters.
Object ID lookup: Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module point IDs by name
AV0Freq_rmsAV1Ua_rmsAV2Ub_rmsAV3Uc_rmsAV4Uvag_rmsAV5Uab_rmsAV6Ubc_rmsAV7Uca_rmsAV8Ulavg_rmsAV9Ia_rmsAV10Ib_rmsAV11Ic_rmsAV12Iavg_rmsAV13In_rmsAV14Pa_rmsAV15Pb_rmsAV16Pc_rmsAV17P_rmsAV18Qa_rmsAV19Qb_rmsAV20Qc_rmsAV21Q_rmsAV22Sa_rmsAV23Sb_rmsAV24Sc_rmsAV25S_rmsAV26PFa_rmsAV27PFb_rmsAV28PFc_rmsAV29PF_rmsAV30Unbl_u2AV31Unbl_i2AV32Rlc_valAV33P_demaAV34Q_demaAV35S_demaAV36Ia_DemandAV37Ib_DemandAV38Ic_DemandAV39Active_Energy_IMPAV40Active_Energy_EXPAV41Reactive_Energy_IMPAV42Reactive_Energy_EXPAV43Active_Energy_TOTALAV44Active_Energy_NETAV45Reactive_Energy_TOTALAV46Reactive_Energy_NET SAV47Apparent_EnergyAV48THD_V1AV49THD_V2AV50THD_V3AV51THD_VAV52THD_I1AV53THD_I2AV54THD_I3AV55THD_I
Integration notes
- All objects are Analog Values; the manual has no access column and they are listed here as read-only measurements.
- The object table gives no engineering units; the manual's worked example says P_rms (AV 17) reads in watts. Check the units property on site.
- Energy objects (AV 39-47) and THD objects (AV 48-55) are integer data types (UINT32/SINT32) in the manual.
- Object names are short codes (e.g. P_rms, Ulavg_rms); each description gives the meter parameter it carries.
- AV 46 is printed as 'Reactive_Energy_NET S' in the table.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Acuvim II with AXM-BMS BACnet MS/TP module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module
How many BACnet points does the Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module have?
This list has 56 BACnet objects: 56 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module BACnet documentation?
The source is BACnet for Acuvim II Series Power Meter, User's Manual (1040E2102 (V2.0.1)), revision 2023-08, published free by Accuenergy at https://www.accuenergy.com/wp-content/uploads/Acuvim-II-Power-Meter-BACnet-User-Manual-EN.pdf.
What are the minimum BACnet points to integrate the Accuenergy Acuvim II with AXM-BMS BACnet MS/TP module?
Start with AV 17 P_rms (Total active power, W); AV 39 Active_Energy_IMP (Imported active energy total); AV 33 P_dema (Active power demand); AV 25 S_rms (Total apparent power); AV 29 PF_rms (Total power factor); AV 12 Iavg_rms (Average phase current); AV 8 Ulavg_rms (Average line-to-line voltage); AV 0 Freq_rms (Supply frequency).
How do I check these points on the real Acuvim II with AXM-BMS BACnet MS/TP module?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Accuenergy BACnet points lists
- Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1310 series DIN-rail power meter (BACnet MS/TP)
Accuenergy AcuRev 1310 series DIN-rail power meters (1312, 1313, 1314) set to the BACnet MS/TP protocol.
Also known as: AcuRev 1310, AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 BACnet - Power and energy meter (DIN-rail submeter)
Accuenergy AcuRev 1320 series DIN-rail multi-channel meter (BACnet)
Accuenergy AcuRev 1320 series DIN-rail meters (three-phase main plus an independent fourth current channel).
Also known as: AcuRev 1320, AcuRev 1320 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 2100 multi-circuit meter with WEB2 module (BACnet IP)
Accuenergy AcuRev 2100 multi-circuit meters (up to 18 input channels) with the WEB2 communication module.
Also known as: AcuRev 2100, AcuRev 2100-WEB2, AcuRev 2100 BACnet - Multi-circuit power and energy meter (submeter)
Accuenergy AcuRev 4100 multi-circuit power meter (BACnet)
Accuenergy AcuRev 4100 multi-circuit meters with up to 24 input (CT) channels and 12 user (summed) channels.
Also known as: AcuRev 4100, AcuRev 4100 BACnet points list - Power quality meter (panel meter)
Accuenergy Acuvim 3 power quality meter (BACnet)
Accuenergy Acuvim 3 series multifunction power quality meters, with optional I/O modules.
Also known as: Acuvim 3, Acuvim-3, Acuvim 3 BACnet - Power and energy meter
Accuenergy Acuvim II V3 power meter (native BACnet, firmware v6.39)
Accuenergy Acuvim II V3 multifunction power meters with firmware v6.39.
Also known as: Acuvim II V3, Acuvim-II V3, Acuvim II V3 BACnet, Acuvim-II_BACnet-Obj-List - Power and energy meter (BACnet IP module)
Accuenergy Acuvim II with AXM-BIP BACnet IP module
Accuenergy Acuvim II series power meters fitted with the AXM-BIP BACnet IP communication module, with or without AXM-IO modules.
Also known as: Acuvim II, Acuvim IIR, Acuvim IIE, Acuvim IIW, AXM-BIP, Acuvim II BACnet IP, 1040E2102 - Power and energy meter (multifunction)
Accuenergy Acuvim-L series power and energy meter (BACnet MS/TP / BACnet IP)
Accuenergy Acuvim-L series multifunction meters on BACnet MS/TP (RS-485 port 1) or BACnet IP through an AXM-WEB2 module.
Also known as: Acuvim-L, Acuvim-CL, Acuvim-EL, Acuvim-L-M, Acuvim L BACnet - Power and energy meter (communication module)
Accuenergy AXM-WEB2 Ethernet module for Acuvim II meters (BACnet IP)
Accuenergy AXM-WEB2 Ethernet / web module fitted to Acuvim II series meters, with optional IO11/12, IO21/22 and IO31/32 modules.
Also known as: AXM-WEB2, AXM-WEB2 BACnet, Acuvim II AXM-WEB2
Source: BACnet for Acuvim II Series Power Meter, User's Manual · 1040E2102 (V2.0.1) · rev. 2023-08. Object names, instances and units are reproduced as published; descriptions are our own.