- Home
- BACnet points lists
- AAON
- VCCX2 Controller
Rooftop unit / air handler controller · BACnet points list
AAON VCCX2 Controller BACnet points list
Updated 28 October 2026
The VCCX2 is AAON's main unit controller and has an on-board BACnet MS/TP port. Its object map has about 280 read-only analog inputs (temperatures, pressures, airflow, compressor and refrigerant module data), about 100 writable analog values (setpoints, offsets, overrides and BAS-supplied sensor values) and about 150 read-only binary inputs (alarms, relay and module status).
This page lists 534 BACnet objects for the AAON VCCX2 Controller — 99 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.
- Manufacturer
- AAON
- Model
- VCCX2 Controller
- Equipment
- Rooftop unit / air handler controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 534 (99 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- VCC-X2, VCCX, VCC-X, ASM01698, Orion VCCX2, SS1088
Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.
BMS integration notes: AAON VCCX2 Controller
Connect the on-board MS/TP port and set MAC address, device ID and baud on the controller's LCD BACnet screens. The BAS schedules the unit with AV 67 Schedule Force, adjusts setpoints with the occupied heating/cooling and supply-air AVs, and can supply sensor values through AV 72-79 when the controller is configured for it. Alarms are read from the BI objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 67 | Schedule Force | Occupied/unoccupied command from the BAS | Write |
| AV 1 | Occupied Cooling Setpoint | Cooling starts one deadband above this, °F | Write |
| AV 2 | Occupied Heating Setpoint | Heating starts one deadband below this, °F | Write |
| AV 10 | Supply Air Cooling Setpoint | Discharge air temp target in cooling, °F | Write |
| AI 3 | Control Status | Current occupancy status | Read |
| AI 4 | HVAC Mode | Off, vent, cool, heat, dehum, purge or defrost mode | Read |
| AI 5 | Control Temperature | Reading from the configured control sensor | Read |
| AI 9 | Supply Air Temperature | Discharge air temp leaving the unit | Read |
| AI 144 | Alarm Status | Summary alarm | Read |
Enable & remote start
Occupancy comes from AV 67 Schedule Force (0 = follow the controller schedule, 1 = forced occupied, 2 = forced unoccupied), the internal week schedule, a GPC-XP broadcast schedule, or the BI4 remote forced occupied contact. AV 68, AV 69, AV 70 and AV 71 override HVAC mode, fan VFD, OA damper and supply setpoint; writing Auto (0 or 65535 as listed) hands control back.
Sensors & values from the BMS
If the controller is configured for it, the BAS can write AV 72 Space Temperature, AV 73 Space Humidity, AV 76 Relief Pressure, AV 77 CO2, AV 78 Outdoor Air Temperature and AV 79 Outdoor Air Humidity; these are the only sensor values the BAS may write. The guide gives no refresh timeout for them. A relief pressure value received over BACnet that is out of range raises an alarm.
Network setup
- MAC address 0-127, default 1; set on the LCD BACnet screen.
- Device ID up to seven digits, set on the same screen; no default is printed.
- MS/TP baud 9600, 19200, 38400, 57600 or 76800; default 38400.
Watch out for
- Writing AV 70 OA damper override to anything between 0 and 100 % while compressors run locks the compressors out; use AV 49 minimum position instead.
- An emergency shutdown (smoke detector/firestat input) cancels all BACnet override commands.
- Refrigerant module, preheater, MODGAS, MHGRV and expansion-board points only report when that hardware is installed.
- AI 159-248 RSMZ status points are bit strings; decode them with the guide's bitfield tables.
AAON VCCX2 Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Application Software Version | Current version of the software in the unit | Read | ||
| AI | 2 | Control Mode | Configured unit application | Read | 0=Supply Air Cooling Only, 1=Supply Air Tempering, 2=Outdoor Temperature Control, 3=Return Air Constant Volume Mode, 4=Space Temp Constant Volume Mode, 5=Space Temp w/ High OA Content, 6=Single Zone VAV | |
| AImin | 3 | Control Status | Current Occupied/Unoccupied Status | Read | 0=Unoccupied, 1=Occupied, 2=Override Mode, 3=Holiday Unoccupied, 4=Holiday Occupied, 5=Forced Occupied, 6=Forced Unoccupied, 7=Remote Contact Occupied, 8-10=Reserved, 11=OA Damper Calibration | |
| AImin | 4 | HVAC Mode | Current operational status | Read | 0=Off, 1=Vent Mode, 2=Cooling Mode, 3=Heating Mode, 4=Vent RH Mode, 5=Cooling RH Mode, 6=Heating RH Mode, 7=Warm Up Mode, 8=Purge Mode, 9=Defrost Mode, 10=Cool Down Mode | |
| AImin | 5 | Control Temperature | Control Temperature Sensor | Read | ||
| AI | 6 | Mode Cooling Setpoint | Cooling Mode Enable Setpoint Mirror (adjusted by the Space Sensor Slide adjustment | Read | ||
| AI | 7 | Mode Heating Setpoint | Heating Mode Enable Setpoint Mirror (adjusted by the Space Sensor Slide adjustment | Read | ||
| AI | 8 | Sensor Slide Adjust Effect | Amount of Current Sensor Slide Adjust | Read | ||
| AImin | 9 | Supply Air Temperature | Supply Air Temperature sensor | Read | ||
| AI | 10 | Supply Air Setpoint | Current SAT Cooling or Heating Setpoint if there is no reset source | Read | ||
| AI | 11 | Controlling Coil Temp Setpoint | Current calculated Coil Suction Temperature target during Dehumidification Mode | Read | ||
| AI | 12 | Space Temperature | Space Temperature Sensor | Read | ||
| AI | 13 | Space Humidity | Space Humidity | Read | ||
| AI | 14 | Return Air Temperature | Return Temperature Sensor | Read | ||
| AI | 15 | Return Air Humidity | Return Air Humidity | Read | ||
| AI | 16 | Outdoor Air Temperature | Outdoor Air Temperature Sensor | Read | ||
| AI | 17 | Outdoor Air Humidity | Outdoor Humidity Sensor | Read | ||
| AI | 18 | Outdoor Air Wetbulb | Current calculated Outdoor Wetbulb Temperature | Read | ||
| AI | 19 | Outdoor Air Dewpoint | Current Calculated Outdoor Air Dewpoint Temperature | Read | ||
| AI | 20 | Supply Air Setpoint Reset Voltage | Supply Air Temp Setpoint Reset Input Signal | Read | ||
| AI | 21 | Duct Static Pressure | Current Duct Static Pressure | Read | ||
| AI | 22 | Duct Static Control Signal | Current Duct Static Control Signal (Fan VFD) | Read | ||
| AI | 23 | Building Pressure | Building Pressure Sensor | Read | ||
| AI | 24 | Building Pressure Control Signal | Current Building Pressure Control Signal | Read | ||
| AI | 25 | Outdoor Airflow | Current Outdoor Airflow Measurement | Read | ||
| AI | 26 | Supply Airflow | Current Supply Airflow Measurement | Read | ||
| AI | 27 | Return Airflow | Current Return Airflow Measurement | Read | ||
| AI | 28 | Exhaust Airflow | Current Exhaust Airflow Measurement | Read | ||
| AI | 29 | Carbon Dioxide | Current Indoor CO2 Level | Read | ||
| AI | 30 | Desired Economizer Position | Current Modulating Signal to the Economizer Damper | Read | ||
| AI | 31 | Economizer Feedback Position | Title 24 current position of feedback from Economizer actuator | Read | ||
| AI | 32 | Return Damper Position | Current Signal to the Return Air Damper if using Return Air Bypass | Read | ||
| AI | 33 | Return Bypass Position | Current Signal to the Return Air Bypass Damper if using Return Air | Read | ||
| AI | 34 | Modulating Cooling Position | Current percentage of the Modulating Chilled Water Signal | Read | ||
| AI | 35 | Modulating Heat Position | Current percentage of the Modulating Heating signal (Hot Water or SCR heat) | Read | ||
| AI | 36 | Preheater Leaving Air Temp #1 | Current Preheater Leaving Air Temperature #1 | Read | ||
| AI | 37 | Preheater Leaving Air Temp #2 | Current Preheater Leaving Air Temperature #2 | Read | ||
| AI | 38 | Preheater Entering Air Temp | Current Entering Air Temp for Preheater | Read | ||
| AI | 39 | Preheater Setpoint Reset Voltage | Current Voltage Reset Input Value for Preheater | Read | ||
| AI | 40 | Preheater SCR Output Signal | Current Modulating Heat Signal for Preheater | Read | ||
| AI | 41 | Preheater PWM Output Signal | Current PWM Output Signal for Preheater | Read | ||
| AI | 42 | Mod Hot Gas Reheat Valve Position | Current position of MHGRV Modulating Hot Gas Reheat Valve | Read | ||
| AI | 43 | Mod Gas Heat Valve Position | Current position of MODGAS Modulating Gas Valve Control | Read | ||
| AI | 44 | A1 Compressor Signal | Current Compressor A1 Modulating Cooling Signal | Read | ||
| AI | 45 | A2 Compressor Signal | Current Compressor A2 Modulating Cooling Signal | Read | ||
| AI | 46 | A1 Condenser Signal | Current A1 Condenser Signal | Read | ||
| AI | 47 | A2 Condenser Signal | Current A2 Condenser Signal or WSE Bypass Valve Signal | Read | ||
| AI | 48 | A1 Suction Pressure | Current Compressor A1 Suction Pressure | Read | ||
| AI | 49 | A2 Suction Pressure | Current Compressor A2 Suction Pressure | Read | ||
| AI | 50 | A1 Head Pressure | Current Compressor A1 Head Pressure | Read | ||
| AI | 51 | A2 Head Pressure | Current Compressor A2 Head Pressure | Read | ||
| AI | 52 | A1 Saturation Temperature | Current Compressor A1 Coil Saturation Temperature | Read | ||
| AI | 53 | A2 Saturation Temperature | Current Compressor A2 Coil Saturation Temperature | Read | ||
| AI | 54 | A1 Suction Line Temperature | Current Compressor A1 Suction Line Temperature | Read | ||
| AI | 55 | A2 Suction Line Temperature | Current Compressor A2Suction Line Temperature | Read | ||
| AI | 56 | A1 Condenser Suction Temp (Heat Pump) | Current Compressor A1 Suction Line Temperature (Heat Pump) | Read | ||
| AI | 57 | A2 Condenser Suction Temp (Heat Pump) | Current Compressor A2 Suction Line Temperature (Heat Pump) | Read | ||
| AI | 58 | A1 Superheat Temperature | Current Compressor A1 Superheat Temperature | Read | ||
| AI | 59 | A2 Superheat Temperature | Current Compressor A2 Superheat Temperature | Read | ||
| AI | 60 | Condenser A1 Superheat (Heat Pump) | Current Compressor A1 Superheat Temperature (Heat Pump) | Read | ||
| AI | 61 | Condenser A2 Superheat (Heat Pump) | Current Compressor A2 Superheat Temperature (Heat Pump) | Read | ||
| AI | 62 | A1 Expansion Valve Position | Current position of Compressor A1 Expansion Valve | Read | ||
| AI | 63 | A2 Expansion Valve Position | Current position of Compressor A2 Expansion Valve | Read | ||
| AI | 64 | Condenser A1 Expansion Valve Position | Current position of Condenser A1 Expansion Valve | Read | ||
| AI | 65 | Condenser A2 Expansion Valve Position | Current position of Condenser A2 Expansion Valve | Read | ||
| AI | 66 | A1 Discharge Temperature | Current Compressor A1 Discharge Temperature | Read | ||
| AI | 67 | A2 Discharge Temperature | Current Compressor A2 Discharge Temperature | Read | ||
| AI | 68 | A1 Leaving Water Temp | Current A1 Leaving Water Temperature for WSHP | Read | ||
| AI | 69 | B1 Compressor Signal | Current Compressor B1 Modulating Cooling Signal | Read | ||
| AI | 70 | B2 Compressor Signal | Current Compressor B2 Modulating Cooling Signal | Read | ||
| AI | 71 | B1 Condenser Signal | Current B1 Condenser Signal | Read | ||
| AI | 72 | B2 Condenser Signal | Current B2 Condenser Signal or WSE Bypass Valve Signal | Read | ||
| AI | 73 | B1 Suction Pressure | Current Compressor B1 Suction Pressure | Read | ||
| AI | 74 | B2 Suction Pressure | Current Compressor B2 Suction Pressure | Read | ||
| AI | 75 | B1 Head Pressure | Current Compressor B1 Head Pressure | Read | ||
| AI | 76 | B2 Head Pressure | Current Compressor B2 Head Pressure | Read | ||
| AI | 77 | B1 Saturation Temperature | Current Compressor B1 Coil Saturation Temperature | Read | ||
| AI | 78 | B2 Saturation Temperature | Current Compressor B2 Coil Saturation Temperature | Read | ||
| AI | 79 | B1 Suction Line Temperature | Current Compressor B1 Suction Line Temperature | Read | ||
| AI | 80 | B2 Suction Line Temperature | Current Compressor B2 Suction Line Temperature | Read | ||
| AI | 81 | B1 Condenser Suction Temp (Heat Pump) | Current Compressor B1 Suction Line Temperature (Heat Pump) | Read | ||
| AI | 82 | B2 Condenser Suction Temp (Heat Pump) | Current Compressor B2 Suction Line Temperature (Heat Pump) | Read | ||
| AI | 83 | B1 Superheat Temperature | Current Compressor B1 Superheat Temperature | Read | ||
| AI | 84 | B2 Superheat Temperature | Current Compressor B2 Superheat Temperature | Read | ||
| AI | 85 | Condenser B1 Superheat (Heat Pump) | Current Compressor B1 Superheat Temperature (Heat Pump) | Read | ||
| AI | 86 | Condenser B2 Superheat (Heat Pump) | Current Compressor B2 Superheat Temperature (Heat Pump) | Read | ||
| AI | 87 | B1 Expansion Valve Position | Current position of Compressor B1 Expansion Valve | Read | ||
| AI | 88 | B2 Expansion Valve Position | Current position of Compressor B2 Expansion Valve | Read | ||
| AI | 89 | Condenser B1 Expansion Valve Position | Current position of Condenser B1 Expansion Valve | Read | ||
| AI | 90 | Condenser B2 Expansion Valve Position | Current position of Condenser B2 Expansion Valve | Read | ||
| AI | 91 | B1 Discharge Temperature | Current Compressor B1 Discharge Temperature | Read | ||
| AI | 92 | B2 Discharge Temperature | Current Compressor B2 Discharge Temperature | Read | ||
| AI | 93 | B1 Leaving Water Temp | Current B1 Leaving Water Temperature for WSHP | Read | ||
| AI | 94 | C1 Compressor Signal | Current Compressor C1 Modulating Cooling Signal | Read | ||
| AI | 95 | C2 Compressor Signal | Current Compressor C2 Modulating Cooling Signal | Read | ||
| AI | 96 | C1 Condenser Signal | Current C1 Condenser Signal | Read | ||
| AI | 97 | C2 Condenser Signal | Current C2 Condenser Signal or WSE Bypass Valve Signal | Read | ||
| AI | 98 | C1 Suction Pressure | Current Compressor C1 Suction Pressure | Read | ||
| AI | 99 | C2 Suction Pressure | Current Compressor C2 Suction Pressure | Read | ||
| AI | 100 | C1 Head Pressure | Current Compressor C1 Head Pressure | Read | ||
| AI | 101 | C2 Head Pressure | Current Compressor C2 Head Pressure | Read | ||
| AI | 102 | C1 Saturation Temperature | Current Compressor C1 Coil Saturation Temperature | Read | ||
| AI | 103 | C2 Saturation Temperature | Current Compressor C2 Coil Saturation Temperature | Read | ||
| AI | 104 | C1 Suction Line Temperature | Current Compressor C1 Suction Line Temperature | Read | ||
| AI | 105 | C2 Suction Line Temperature | Current Compressor C2 Suction Line Temperature | Read | ||
| AI | 106 | C1 Condenser Suction Temp (Heat Pump) | Current Compressor C1 Suction Line Temperature (Heat Pump) | Read | ||
| AI | 107 | C2 Condenser Suction Temp (Heat Pump) | Current Compressor C2 Suction Line Temperature (Heat Pump) | Read | ||
| AI | 108 | C1 Superheat Temperature | Current Compressor C1 Superheat Temperature | Read | ||
| AI | 109 | C2 Superheat Temperature | Current Compressor C2 Superheat Temperature | Read | ||
| AI | 110 | Condenser C1 Superheat (Heat Pump) | Current Compressor C1 Superheat Temperature (Heat Pump) | Read | ||
| AI | 111 | Condenser C2 Superheat (Heat Pump) | Current Compressor C2 Superheat Temperature (Heat Pump) | Read | ||
| AI | 112 | C1 Expansion Valve Position | Current position of Compressor C1 Expansion Valve | Read | ||
| AI | 113 | C2 Expansion Valve Position | Current position of Compressor C2 Expansion Valve | Read | ||
| AI | 114 | Condenser C1 Expansion Valve Position | Current position of Condenser C1 Expansion Valve | Read | ||
| AI | 115 | Condenser C2 Expansion Valve Position | Current position of Condenser C2 Expansion Valve | Read | ||
| AI | 116 | C1 Discharge Temperature | Current Compressor C1 Discharge Temperature | Read | ||
| AI | 117 | C2 Discharge Temperature | Current Compressor C2 Discharge Temperature | Read | ||
| AI | 118 | C1 Leaving Water Temp | Current C1 Leaving Water Temperature for WSHP | Read | ||
| AI | 119 | D1 Compressor Signal | Current Compressor D1 Modulating Cooling Signal | Read | ||
| AI | 120 | D2 Compressor Signal | Current Compressor D2 Modulating Cooling Signal | Read | ||
| AI | 121 | D1 Condenser Signal | Current D1 Condenser Signal | Read | ||
| AI | 122 | D2 Condenser Signal | Current D2 Condenser Signal or WSE Bypass Valve Signal | Read | ||
| AI | 123 | D1 Suction Pressure | Current Compressor D1 Suction Pressure | Read | ||
| AI | 124 | D2 Suction Pressure | Current Compressor D2 Suction Pressure | Read | ||
| AI | 125 | D1 Head Pressure | Current Compressor D1 Head Pressure | Read | ||
| AI | 126 | D2 Head Pressure | Current Compressor D2 Head Pressure | Read | ||
| AI | 127 | D1 Saturation Temperature | Current Compressor D1 Coil Saturation Temperature | Read | ||
| AI | 128 | D2 Saturation Temperature | Current Compressor D2 Coil Saturation Temperature | Read | ||
| AI | 129 | D1 Suction Line Temperature | Current Compressor D1 Suction Line Temperature | Read | ||
| AI | 130 | D2 Suction Line Temperature | Current Compressor D2 Suction Line Temperature | Read | ||
| AI | 131 | D1 Condenser Suction Temp (Heat Pump) | Current Compressor D1 Suction Line Temperature (Heat Pump) | Read | ||
| AI | 132 | D2 Condenser Suction Temp (Heat Pump) | Current Compressor D2 Suction Line Temperature (Heat Pump) | Read | ||
| AI | 133 | D1 Superheat Temperature | Current Compressor D1 Superheat Temperature | Read | ||
| AI | 134 | D2 Superheat Temperature | Current Compressor D2 Superheat Temperature | Read | ||
| AI | 135 | Condenser D1 Superheat (Heat Pump) | Current Compressor D1 Superheat Temperature (Heat Pump) | Read | ||
| AI | 136 | Condenser D2 Superheat (Heat Pump) | Current Compressor D2 Superheat Temperature (Heat Pump) | Read | ||
| AI | 137 | D1 Expansion Valve Position | Current position of Compressor D1 Expansion Valve | Read | ||
| AI | 138 | D2 Expansion Valve Position | Current position of Compressor D2 Expansion Valve | Read | ||
| AI | 139 | Condenser D1 Expansion Valve Position | Current position of Condenser D1 Expansion Valve | Read | ||
| AI | 140 | Condenser D2 Expansion Valve Position | Current position of Condenser D2 Expansion Valve | Read | ||
| AI | 141 | D1 Discharge Temperature | Current Compressor D1 Discharge Temperature | Read | ||
| AI | 142 | D2 Discharge Temperature | Current Compressor D2 Discharge Temperature | Read | ||
| AI | 143 | D1 Leaving Water Temp | Current D1 Leaving Water Temperature for WSHP | Read | ||
| AImin | 144 | Alarm Status | Alarm condition summary | Read | 0=No Alarms, 1=Alarm(s) Present | |
| AI | 145 | Outdoor Enthalpy | Current Outdoor Enthalpy | Read | ||
| AI | 146 | Plenum Pressure | Reserved | Read | ||
| AI | 147 | Return Fan Speed | Reserved | Read | ||
| AI | 148 | Plenum Calculated Setpoint | Reserved | Read | ||
| AI | 149 | Return Air Enthalpy Status | Return Air Enthalpy | Read | ||
| AI | 150 | Current Duct Static Setpoint | Status of the duct static setpoint | Read | ||
| AI | 151 | RSMZ 1 Condenser Fan | Current RSMZ 1 condenser fan signal | Read | ||
| AI | 152 | RSMZ 1 VFD Comp Perc | Current RSMZ 1 VFD Compressor Percentage | Read | ||
| AI | 153 | RSMZ 1 Discharge Pressure | Current RSMZ 1 discharge pressure | Read | ||
| AI | 154 | RSMZ 1 Suction Pressure | Current RSMZ 1 Suction Pressure | Read | ||
| AI | 155 | RSMZ 1 Suction Line Temp | Current RSMZ 1 Suction Line Temperature | Read | ||
| AI | 156 | RSMZ 1 Saturation Temp | Current RSMZ 1 Saturation Temperature | Read | ||
| AI | 157 | RSMZ 1 Superheat | Current RSMZ 1 Superheat Temperature | Read | ||
| AI | 158 | RSMZ 1 EEV Position | Current RSMZ 1 EEV Valve Position | Read | ||
| AI | 159 | RSMZ 1 Warnings | Current RSMZ 1 Warnings | Read | ||
| AI | 160 | RSMZ 1 Comp VFD Alarms 1 | Current RSMZ 1 Comp VFD Alarms 1 | Read | ||
| AI | 161 | RSMZ 1 Comp VFD Alarms 2 | Current RSMZ 1 Comp VFD Alarms 2 | Read | ||
| AI | 162 | RSMZ 1 Comp VFD Drive Status | Current RSMZ 1 Comp VFD drive status | Read | ||
| AI | 163 | RSMZ 1 Compressor Current | Current reading in Amps that the RSMZ 1 compressor is using | Read | ||
| AI | 164 | RSMZ 1 Discharge Line Temp | Current RSMZ 1 discharge line temperature | Read | ||
| AI | 165 | RSMZ 1 Faults | Current RSMZ 1 Faults | Read | ||
| AI | 166 | RSMZ 1 Lockouts | Current RSMZ 1 Lockouts | Read | ||
| AI | 167 | RSMZ 2 Condenser Fan | Current RSMZ 2 condenser fan signal | Read | ||
| AI | 168 | RSMZ 2 VFD Comp Perc | Current RSMZ 2 VFD Compressor Percentage | Read | ||
| AI | 169 | RSMZ 2 Discharge Pressure | Current RSMZ 2 discharge pressure | Read | ||
| AI | 170 | RSMZ 2 Suction Pressure | Current RSMZ 2 Suction Pressure | Read | ||
| AI | 171 | RSMZ 2 Suction Line Temp | Current RSMZ 2 Suction Line Temperature | Read | ||
| AI | 172 | RSMZ 2 Saturation Temp | Current RSMZ 2 Saturation Temperature | Read | ||
| AI | 173 | RSMZ 2 Superheat | Current RSMZ 2 Superheat temperature | Read | ||
| AI | 174 | RSMZ 2 EEV Position | Current RSMZ 2 EEV valve position | Read | ||
| AI | 175 | RSMZ 2 Warnings | Current RSMZ 2 Warnings | Read | ||
| AI | 176 | RSMZ 2 Comp VFD Alarms 1 | Current RSMZ 2 Comp VFD Alarms 1 | Read | ||
| AI | 177 | RSMZ 2 Comp VFD Alarms 2 | Current RSMZ 2 Comp VFD Alarms 2 | Read | ||
| AI | 178 | RSMZ 2 Comp VFD Drive Status | Current RSMZ 2 Comp VFD drive status | Read | ||
| AI | 179 | RSMZ 2 Compressor Current | Current reading in Amps that the RSMZ 2 compressor is using | Read | ||
| AI | 180 | RSMZ 2 Discharge Line Temp | Current RSMZ 2 discharge line temperature | Read | ||
| AI | 181 | RSMZ 2 Faults | Current RSMZ 2 Faults | Read | ||
| AI | 182 | RSMZ 2 Lockouts | Current RSMZ 2 Lockouts | Read | ||
| AI | 183 | RSMZ 3 Condenser Fan | Current RSMZ 3 condenser fan signal | Read | ||
| AI | 184 | RSMZ 3 Reheat Valve 1 | Current RSMZ 3 Reheat Valve 1 position | Read | ||
| AI | 185 | RSMZ 3 Discharge Pressure | Current RSMZ 3 discharge pressure | Read | ||
| AI | 186 | RSMZ 3 Suction Pressure | Current RSMZ 3 Suction Pressure | Read | ||
| AI | 187 | RSMZ 3 Suction Line Temp | Current RSMZ 3 Suction Line Temperature | Read | ||
| AI | 188 | RSMZ 3 Saturation Temp | Current RSMZ 3 Saturation Temperature | Read | ||
| AI | 189 | RSMZ 3 Superheat | Current RSMZ 3 Superheat temperature | Read | ||
| AI | 190 | RSMZ 3 EEV Position | Current RSMZ 3 EEV valve position | Read | ||
| AI | 191 | RSMZ 3 Suction Pressure 2 | Current RSMZ 3 Suction pressure 2 | Read | ||
| AI | 192 | RSMZ 3 Suction Line Temp 2 | Current RSMZ 3 Suction Line Temperature 2 | Read | ||
| AI | 193 | RSMZ 3 Saturation Temp 2 | Current RSMZ 3 Saturation Temperature 2 | Read | ||
| AI | 194 | RSMZ 3 Superheat 2 | Current RSMZ 3 Superheat Temperature 2 | Read | ||
| AI | 195 | RSMZ 3 EEV Position 2 | Current RSMZ 3 EEV valve position 2 | Read | ||
| AI | 196 | RSMZ 3 Warnings | Current RSMZ 3 Warnings | Read | ||
| AI | 197 | RSMZ 3 Discharge Line Temp | Current RSMZ 3 discharge line temperature | Read | ||
| AI | 198 | RSMZ 3 Faults | Current RSMZ 3 Faults | Read | ||
| AI | 199 | RSMZ 3 Lockouts | Current RSMZ 3 Lockouts | Read | ||
| AI | 200 | RSMZ 4 Condenser Fan | Current RSMZ 4 Condenser Fan Signal | Read | ||
| AI | 201 | RSMZ 4 VFD Comp Perc | Current RSMZ 4 VFD Compressor Percentage | Read | ||
| AI | 202 | RSMZ 4 Discharge Pressure | Current RSMZ 4 Discharge Pressure | Read | ||
| AI | 203 | RSMZ 4 Suction Pressure | Current RSMZ 4 Suction Pressure | Read | ||
| AI | 204 | RSMZ 4 Suction Line Temp | Current RSMZ 4 Suction Line Temperature | Read | ||
| AI | 205 | RSMZ 4 Saturation Temp | Current RSMZ 4 Saturation Temperature | Read | ||
| AI | 206 | RSMZ 4 Superheat | Current RSMZ 4 Superheat Temperature | Read | ||
| AI | 207 | RSMZ 4 EEV Position | Current RSMZ 4 EEV valve position | Read | ||
| AI | 208 | RSMZ 4 Warnings | Current RSMZ 4 Warnings | Read | ||
| AI | 209 | RSMZ 4 Comp VFD Alarms 1 | Current RSMZ 4 Comp VFD Alarms 1 | Read | ||
| AI | 210 | RSMZ 4 Comp VFD Alarms 2 | Current RSMZ 4 Comp VFD Alarms 2 | Read | ||
| AI | 211 | RSMZ 4 Comp VFD Drive Status | Current RSMZ 4 Comp VFD drive status | Read | ||
| AI | 212 | RSMZ 4 Comp VFD Compressor Current | Current reading in Amps that the RSMZ 4 compressor is using | Read | ||
| AI | 213 | RSMZ 4 Discharge Line Temp | Current RSMZ 4 discharge line temperature | Read | ||
| AI | 214 | RSMZ 4 Faults | Current RSMZ 4 Faults | Read | ||
| AI | 215 | RSMZ 4 Lockouts | Current RSMZ 4 Lockouts | Read | ||
| AI | 216 | RSMZ 5 Condenser Fan | Current RSMZ 5 Condenser Fan Signal | Read | ||
| AI | 217 | RSMZ 5 VFD Comp Perc | Current RSMZ 5 VFD Compressor Percentage | Read | ||
| AI | 218 | RSMZ 5 Discharge Pressure | Current RSMZ 5 discharge pressure | Read | ||
| AI | 219 | RSMZ 5 Suction Pressure | Current RSMZ 5 Suction pressure | Read | ||
| AI | 220 | RSMZ 5 Suction Line Temp | Current RSMZ 5 Suction Line Temperature | Read | ||
| AI | 221 | RSMZ 5 Saturation Temp | Current RSMZ 5 Saturation Temperature | Read | ||
| AI | 222 | RSMZ 5 Superheat | Current RSMZ5 Superheat temperature | Read | ||
| AI | 223 | RSMZ 5 EEV Position | Current RSMZ 5 EEV valve position | Read | ||
| AI | 224 | RSMZ 5 Warnings | Current RSMZ 5 Warnings | Read | ||
| AI | 225 | RSMZ 5 Comp VFD Alarms 1 | Current RSMZ 5 Comp VFD Alarms 1 | Read | ||
| AI | 226 | RSMZ 5 Comp Alarms 2 | Current RSMZ 5 Comp VFD Alarms 2 | Read | ||
| AI | 227 | RSMZ 5 Comp VFD Drive Status | Current RSMZ 5 Comp VFD drive status | Read | ||
| AI | 228 | RSMZ 5 Compressor Current | Current reading in Amps that the RSMZ 5 compressor is using | Read | ||
| AI | 229 | RSMZ 5 Discharge Line Temp | Current RSMZ 5 discharge line temperature | Read | ||
| AI | 230 | RSMZ 5 Faults | Current RSMZ 5 Faults | Read | ||
| AI | 231 | RSMZ 5 Lockouts | Current RSMZ 5Lockouts | Read | ||
| AI | 232 | RSMZ 6 Condenser Fan | Current RSMZ 6 condenser fan signal | Read | ||
| AI | 233 | RSMZ 6 Reheat Valve 1 | Current RSMZ 6 Reheat Valve 1 position | Read | ||
| AI | 234 | RSMZ 6 Discharge Pressure | Current RSMZ 6 discharge pressure | Read | ||
| AI | 235 | RSMZ 6 Suction Pressure | Current RSMZ 6 Suction Pressure | Read | ||
| AI | 236 | RSMZ 6 Suction Line Temp | Current RSMZ 6 Suction Line Temperature | Read | ||
| AI | 237 | RSMZ 6 Saturation Temp | Current RSMZ 6 Saturation Temperature | Read | ||
| AI | 238 | RSMZ 6 Superheat | Current RSMZ 6 Superheat Temperature | Read | ||
| AI | 239 | RSMZ 6 EEV Position | Current RSMZ 6 EEV valve position | Read | ||
| AI | 240 | RSMZ 6 Suction Pressure 2 | Current RSMZ 6 Suction pressure 2 | Read | ||
| AI | 241 | RSMZ 6 Suction Line Temp 2 | Current RSMZ 6 Suction Line Temperature 2 | Read | ||
| AI | 242 | RSMZ 6 Saturation Temp 2 | Current RSMZ 6 Saturation Temperature 2 | Read | ||
| AI | 243 | RSMZ 6 Superheat 2 | Current RSMZ 6 Superheat Temperature 2 | Read | ||
| AI | 244 | RSMZ 6 EEV Position 2 | Current RSMZ 6 EEV valve position 2 | Read | ||
| AI | 245 | RSMZ 6 Warnings | Current RSMZ 6 Warnings | Read | ||
| AI | 246 | RSMZ 6 Discharge Line Temp | Current RSMZ 6 discharge line temperature | Read | ||
| AI | 247 | RSMZ 6 Faults | Current RSMZ 6 Faults | Read | ||
| AI | 248 | RSMZ 6 Lockouts | Current RSMZ 6 Lockouts | Read | ||
| AI | 249 | Not used | Not used | Read | ||
| AI | 250 | Not used | Not used | Read | ||
| AI | 251 | Not used | Not used | Read | ||
| AI | 252 | Not used | Not used | Read | ||
| AI | 253 | SUB 1 Sub Cool 1 | Current Subcooling Module 1 Sub Cool 1 reading | Read | ||
| AI | 254 | SUB 1 Sub Cool 2 | Current Subcooling Module 1 Sub Cool 2 reading | Read | ||
| AI | 255 | SUB 1 Sub Cool 3 | Current Subcooling Module 1 Sub Cool 3 reading | Read | ||
| AI | 256 | SUB 1 Pressure 1 | Current Subcooling Module 1 liquid line pressure 1 reading | Read | ||
| AI | 257 | SUB 1 Pressure 2 | Current Subcooling Module 1 liquid line pressure 2 reading | Read | ||
| AI | 258 | SUB 1 Pressure 3 | Current Subcooling Module 1 liquid line pressure 3 reading | Read | ||
| AI | 259 | SUB 1 Saturation 1 | Subcooling Module 1 saturation temperature 1 reading | Read | ||
| AI | 260 | SUB 1 Saturation 2 | Subcooling Module 1 saturation temperature 2 reading | Read | ||
| AI | 261 | SUB 1 Saturation 3 | Subcooling Module 1 saturation temperature 3 reading | Read | ||
| AI | 262 | SUB 1 Line Temp 1 | Subcooling Module 1 liquid line temperature 1 reading | Read | ||
| AI | 263 | SUB 1 Line Temp 2 | Subcooling Module 1 liquid line temperature 2 reading | Read | ||
| AI | 264 | SUB 1 Line Temp 3 | Subcooling Module 1 liquid line temperature 3 reading | Read | ||
| AI | 265 | SUB 2 Sub Cool 1 | Current Subcooling Module 2 Sub Cool 1 reading | Read | ||
| AI | 266 | SUB 2 Sub Cool 2 | Current Subcooling Module 2 Sub Cool 2 reading | Read | ||
| AI | 267 | SUB 2 Sub Cool 3 | Current Subcooling Module 2 Sub Cool 3 reading | Read | ||
| AI | 268 | SUB 2 Pressure 1 | Current Subcooling Module 2 liquid line pressure 1 reading | Read | ||
| AI | 269 | SUB 2 Pressure 2 | Subcooling Module 2 liquid line pressure 2 reading | Read | ||
| AI | 270 | SUB 2 Pressure 3 | Subcooling Module 2 liquid line pressure 3 reading | Read | ||
| AI | 271 | SUB 2 Saturation 1 | Subcooling Module 2 saturation temperature 1 reading | Read | ||
| AI | 272 | SUB 2 Saturation 2 | Subcooling Module 2 saturation temperature 2 reading | Read | ||
| AI | 273 | SUB 2 Saturation 3 | Subcooling Module 2 saturation temperature 3 reading | Read | ||
| AI | 274 | SUB 2 Line Temp 1 | Subcooling Module 2 liquid line temperature 1 reading | Read | ||
| AI | 275 | SUB 2 Line Temp 2 | Subcooling Module 2 liquid line temperature 2 reading | Read | ||
| AI | 276 | SUB 2 Line Temp 3 | Subcooling Module 2 liquid line temperature 3 reading | Read | ||
| AI | 277 | Enter Water Pump | Status of Entering Water Temperature | Read | ||
| AI | 278 | Return Plenum Pressure Status | Return Plenum Pressure Sensor | Read | ||
| AI | 279 | Return Plenum Control Signal | Current Return Plenum Control Signal (Motorized Exhaust Damper) | Read | ||
| AI | 280 | Mixed Air Temp | Mixed air temperature sensor status | Read | ||
| AI | 281 | Actual Heat Rise | Difference between supply air temperature and mixed air temperature on units | Read | ||
| AI | 282 | Calculated Heat Rise | The heat rise limit determined by how open the Outside Damper is | Read | ||
| AI | 283 | Supply Air Relative Humidity | If an EBUS Supply Air Sensor is being used this shows | Read | ||
| AI | 284 | Supply Air Dew Point | If an EBUS Supply Air Sensor is being used this shows | Read | ||
| AI | 285 | Space Dew Point | Calculated Space Dew Point | Read | ||
| AI | 286 | Return Dew Point | Calculated Return Dew Point | Read | ||
| AVmin | 1 | Occupied Cooling Setpoint | If the control temperature rises one deadband above this setpoint, the control | °F | Write | |
| AVmin | 2 | Occupied Heating Setpoint | If the control temperature drops one deadband below this setpoint, the control | °F | Write | |
| AV | 3 | Hood On Cooling Setpoint | Cooling Mode Enable Setpoint used only in Hood On Mode or Space | °F | Write | |
| AV | 4 | Hood On Heating Setpoint | Heating Mode Enable Setpoint used only in Hood On Mode or Space | °F | Write | |
| AV | 5 | Unoccupied Cooling Offset | During the Unoccupied Mode of Operation, this Setpoint offsets the Occupied Cooling | °F | Write | |
| AV | 6 | Unoccupied Heating Offset | During the Unoccupied Mode of Operation, this Setpoint offsets the Occupied Heating | °F | Write | |
| AV | 7 | Mode Select Deadband | This value is added to and subtracted from the HVAC Mode Setpoints | °F | Write | |
| AV | 8 | Max Coil Setpoint Reset Limit | Highest that the Coil Temperature resets to during Space Humidity Reset | °F | Write | |
| AV | 9 | Min Coil Setpoint Reset Limit | Lowest the Coil Temperature resets to during Space Humidity Reset | °F | Write | |
| AVmin | 10 | Supply Air Cooling Setpoint | Supply Air Cooling Setpoint | °F | Write | |
| AV | 11 | Supply Air Heating Setpoint | Supply Air Heating Setpoint | °F | Write | |
| AV | 12 | Max SAT Cooling Setpoint Reset Limit | If Supply Air Reset is configured this is the High SAT Cooling | °F | Write | |
| AV | 13 | Max SAT Heating Setpoint Reset Limit | If Supply Air Reset is configured this is the High SAT Heating | °F | Write | |
| AV | 14 | Supply Air Cooling Staging Window | In Cooling Mode, if the Supply Air Temperature drops below the Active | °F | Write | |
| AV | 15 | Supply Air Heating Staging Window | In Heating Mode, if the Supply Air Temperature rises above the Active | °F | Write | |
| AV | 16 | Warm-Up Target Temperature | If Morning Warm-Up is configured, then upon entering occupied mode, the Warm-Up | °F | Write | |
| AV | 17 | Warm-Up Mode Supply Air Setpoint | During Morning Warm-Up, the Supply Air Temperature is controlled to this Setpoint | °F | Write | |
| AV | 18 | Cool-Down Mode Supply Air Setpoint | During Morning Cool-Down, the Supply Air Temperature is controlled to this Setpoint | °F | Write | |
| AV | 19 | Mechanical Cooling Outdoor Air Lockout | Mechanical Cooling is locked out when the Outdoor Air Temperature is below | °F | Write | |
| AV | 20 | Mechanical Heating Outdoor Air Lockout | Mechanical Heating is locked out when the Outdoor Air Temperature is above | °F | Write | |
| AV | 21 | Low Supply Temp Cutoff Alarm | Cooling is disabled if the Supply Air Temperature falls below this value | °F | Write | |
| AV | 22 | High Supply Temp Cutoff Alarm | Heating is disabled if the Supply Air Temperature rises above this value | °F | Write | |
| AV | 23 | Preheater Cooling Mode Setpoint | If the Preheater is enabled, and the unit is in the Cooling | °F | Write | |
| AV | 24 | Preheater Venting Mode Setpoint | If the Preheater is enabled, and the unit is in the Vent | °F | Write | |
| AV | 25 | Preheater Heating Mode Setpoint | If the Preheater is enabled, and the unit is in the Heating | °F | Write | |
| AV | 26 | Outdoor Air Dewpoint Setpoint | On an MUA unit, if the OA dewpoint rises above this setpoint | °F | Write | |
| AV | 27 | Economizer Enable Setpoint | The economizer is enabled if the outdoor drybulb, dewpoint, or wetbulb temperature | °F | Write | |
| AV | 28 | Heat Wheel Defrost Enable Setpoint | The unit goes into Heat Wheel Defrost if the Outdoor Air | °F | Write | |
| AV | 29 | PreHeat Enable Setpoint | If the Supply Fan is energized, this is the temperature at which | °F | Write | |
| AV | 30 | Sensor Slide Offset Max Effect | If the space sensor has the optional slide adjustment feature | °F | Write | |
| AV | 31 | Space Sensor Calibration Offset | If the Space Temperature Sensor is reading incorrectly, use this option | °F | Write | |
| AV | 32 | Supply Air Sensor Calibration Offset | If the Supply Air Temperature Sensor is reading incorrectly, use this option | °F | Write | |
| AV | 33 | Return Air Sensor Calibration Offset | If the Return Temperature Sensor is reading incorrectly, use this option | °F | Write | |
| AV | 34 | Outdoor Air Sensor Calibration Offset | If the Outdoor Temperature Sensor is reading incorrectly, use this option | °F | Write | |
| AV | 35 | Carbon Dioxide Sensor Calibration Offset | If the CO2 Sensor is reading incorrectly, use this option to -500 | Write | ||
| AV | 36 | Low Ambient Protection Setpoint | Temperature at which the Low Ambient Relay activates in the Occupied | °F | Write | |
| AV | 37 | SAT Cool Setpoint Reset Source Low Limit | If doing Supply Air Setpoint Reset, this is the Low Reset Source | °F | Write | |
| AV | 38 | SAT Cool Setpoint Reset Source High Limit | If doing Supply Air Setpoint Reset, this is the High Reset Source | °F | Write | |
| AV | 39 | SAT Heat Setpoint Reset Source Low Limit | If doing Supply Air Setpoint Reset, this is the Low Reset Source | °F | Write | |
| AV | 40 | SAT Heat Setpoint Reset Source High Limit | If doing Supply Air Setpoint Reset, this is the High Reset Source | °F | Write | |
| AV | 41 | Control Temperature High Alarm Offset | If the temperature of the controlling sensor rises above the Occupied Cooling | °F | Write | |
| AV | 42 | Control Temperature Low Alarm Offset | If the temperature of the controlling sensor falls below the Occupied Heating | °F | Write | |
| AV | 43 | Heat Pump Compressor Heat Lockout | Compressor Heat is locked out below this setpoint | °F | Write | |
| AV | 44 | Maximum Main Fan VFD in SZ VAV Heating Mode | In Single Zone VAV configuration, this is the max fan speed | Write | ||
| AV | 45 | Minimum Main Fan VFD in Cooling Mode | In Single Zone VAV configuration, this is the fan speed at which | Write | ||
| AV | 46 | Minimum Main Fan VFD in Heating Mode | In Single Zone VAV configuration, this is the fan speed at which | Write | ||
| AV | 47 | Minimum Main Fan VFD in Vent Mode | Speed at which the VFD operates in the Vent Mode in Single | Write | ||
| AV | 48 | Maximum Economizer in Heating Mode | Max position the Economizer Damper opens to in Supply Air Tempering during | Write | ||
| AV | 49 | Minimum Economizer Position | The minimum position of the Outdoor Air damper in the Occupied Mode | Write | ||
| AV | 50 | Maximum Economizer CO2 Reset Limit | The maximum value the Economizer Minimum Position can be reset up | Write | ||
| AV | 51 | Minimum Carbon Dioxide Setpoint | Threshold CO2 level at which the Economizer Min Damper Position Setpoint begins | Write | ||
| AV | 52 | Maximum Carbon Dioxide Setpoint | CO2 level at which the Economizer Min Damper Position resets | Write | ||
| AV | 53 | Indoor Humidity Setpoint Low Reset Limit | On indoor controlled (non-MUA) units, this is the Humidity setpoint at which | Write | ||
| AV | 54 | Indoor Humidity Setpoint High Reset Limit | On indoor controlled (non-MUA) units, this is the Humidity setpoint at which | Write | ||
| AV | 55 | Duct Static Pressure Setpoint | Current Static Pressure Setpoint | Write | ||
| AV | 56 | Duct Static Pressure Control Deadband | Value above and below the Duct Static Pressure Setpoint where no control | Write | ||
| AV | 57 | Building Pressure Control Setpoint | Building Pressure Setpoint or Exhaust Duct Static Pressure Setpoint | Write | ||
| AV | 58 | Building Pressure Control Deadband | Value above and below the Building Pressure Setpoint or the Exhaust Duct | Write | ||
| AV | 59 | Minimum Outdoor CFM Requirement | Minimum Outdoor Airflow CFM Setpoint | Write | ||
| AV | 60 | Outdoor CFM Control Deadband | Controls rate of change for damper signal | Write | ||
| AV | 61 | Single Zone VAV Fan Speed Integral | The Integral Constant for Single Zone VAV Fan Control | Write | ||
| AV | 62 | Relay Run-time Hours Warning Limit | If any configured relay’s run time exceeds this number of hours | Write | ||
| AV | 63 | Cooling Mode Head Pressure Setpoint | Head Pressure Setpoint in the Cooling Mode | Write | ||
| AV | 64 | Dehum Mode Head Pressure Setpoint | Head Pressure Setpoint in the Dehumidification Mode | Write | ||
| AV | 65 | Superheat Setpoint | Superheat Setpoint | °F | Write | |
| AV | 66 | Maximum Outdoor CFM Requirement | Maximum Outdoor Airflow CFM Setpoint in High CO2 | Write | ||
| AVmin | 67 | Schedule Force | Forces occupancy or follows the controller schedule | Write | 0=Auto (controller schedule), 1=Forced Occupied, 2=Forced Unoccupied | |
| AV | 68 | HVAC Mode Override | Forces the unit into a mode; Auto restores normal control | Write | 0=Auto, 1=Vent, 2=Cool, 3=Heat, 4=Vent Dehum, 5=Cool Dehum, 6=Heat Dehum | |
| AV | 69 | Fan VFD Override | Overrides main fan VFD speed; 65535 returns to auto | Write | ||
| AV | 70 | Outdoor Air Damper Override | Overrides outdoor air damper position; 65535 returns to auto | Write | ||
| AV | 71 | Supply Setpoint Override | Overrides the supply air temperature setpoint; 0 = no override | °F | Write | |
| AV | 72 | Space Temperature Value | If the controller is configured for this operation, the user can write | °F | Write | |
| AV | 73 | Space Humidity Value | If the controller is configured for this operation, the user can write | Write | ||
| AV | 74 | Indoor RH Calibration Offset | If the Space Humidity Sensor is reading incorrectly, use -1 this option | Write | ||
| AV | 75 | Relief Fan VFD | Overrides relief fan VFD speed; 65535 returns to auto | Write | ||
| AV | 76 | Relief Pressure Value | If the controller is configured for this operation, the user can write | Write | ||
| AV | 77 | Carbon Dioxide Value | If the controller is configured for this operation, the user can write | Write | ||
| AV | 78 | Outdoor Air Temperature Value | If the controller is configured for this operation, the user can write | °F | Write | |
| AV | 79 | Outdoor Air Humidity Value | If the controller is configured for this operation, the user can write | Write | ||
| AV | 80 | High Level Enthalpy (Reserved) | Reserved | Write | ||
| AV | 81 | Low Level Enthalpy (Reserved) | Reserved | Write | ||
| AV | 82 | Max Plenum Pressure Setpoint Reset Limit | Reserved | Write | ||
| AV | 83 | Min Plenum Pressure Setpoint Reset Limit | Reserved | Write | ||
| AV | 84 | Enthalpy Enable Setpoint | If configured for Comparative Enthalpy Economizer Control, the OA Enthalpy must | BTU/lb | Write | |
| AV | 85 | EnthalpyEnable Deadband | The OA Enthalpy must be below the Enthalpy Enable Setpoint | BTU/lb | Write | |
| AV | 86 | Maximum Static Setpoint Reset Limit | As the most open VAV damper rises above 80%, the static setpoint | in. W.C. | Write | |
| AV | 87 | Minimum Static Setpoint Reset Limit | As the most open VAV damper drops below 80%, the static setpoint | in. W.C. | Write | |
| AV | 88 | Static Setpoint Reset Interval | The Reset Interval is how often the setpoint reset calculation 10 min | Write | ||
| AV | 89 | Cool-Down Target Temperature | If Morning Cool-Down is configured then upon entering occupied mode, the Cool-Down | °F | Write | |
| AV | 90 | Warm-Up Override | Commands Morning Warm-Up Mode | Write | 1=Command Warm-Up Mode | |
| AV | 91 | Cool Down Override | Commands Morning Cool-Down Mode | Write | 1=Command Cool-Down Mode | |
| AV | 92 | Return Air High Limit Protection | Return air high limit; unit reverts above it (voting/CV units only) | Write | ||
| AV | 93 | Return Air Low Limit Protection | Return air low limit; unit reverts below it (voting/CV units only) | Write | ||
| AV | 94 | Sump Drain Override | Turns the sump drain relay on or back to auto | Write | 0=Auto, 1=On | |
| AV | 95 | Return Plenum Pressure Setpoint | Current Return Plenum Pressure Setpoint | in. W.C. | Write | |
| AV | 96 | Return Plenum Pressure Deadband | Value above and below the Return Plenum Pressure Setpoint where no control | in. W.C. | Write | |
| AV | 97 | Dehum Lockout Setpoint | If Outdoor Air temperature is below this setpoint, Dehumidification Mode is locked | °F | Write | |
| AV | 98 | Emergency Compressor Lockout | Lets the BMS lock out the compressors | Write | ||
| AV | 99 | Supply Air Dew Point Setpoint | When the VCCX2 is configured for DX-DOAS control it modulates the compressors | Write | ||
| BI | 1 | Cooling Enabled Status | Mechanical Cooling is enabled based on the Cooling Lockout | Read | ||
| BI | 2 | Heating Enabled Status | That Mechanical Heating is enabled based on the Heating Lockout | Read | ||
| BI | 3 | Economizer Enabled Status | The Economizer is enabled based on the Economizer Enable Setpoint | Read | ||
| BI | 4 | Aux Heat Enabled Status | Heat Pump Auxiliary Heat enabled | Read | ||
| BI | 5 | Emergency Heat Enabled Status | Shows the Emergency Heat is enabled based on the Compressor Heating Lockout | Read | ||
| BI | 6 | Fan Proof of Airflow Status | Proof of Airflow Binary Input Status | Read | ||
| BI | 7 | Exhaust Hood On/Off Status | Exhaust Hood On/Off Binary Input Status | Read | ||
| BI | 8 | Remote Forced Occupied Status | Remote Forced Occupied Mode Binary Input Status | Read | ||
| BI | 9 | Remote Forced Cooling Status | Remote Forced Cooling Mode Binary Input Status | Read | ||
| BI | 10 | Remote Forced Heating Status | Remote Forced Heating Mode Binary Input Status | Read | ||
| BI | 11 | Remote Force Dehum Status | Remote Force Dehumidification Mode Binary Input Status | Read | ||
| BI | 12 | Bad Supply Air Sensor | Alarm that indicates a failure of the Supply Air Sensor | Read | ||
| BI | 13 | Bad Return Air Sensor | Alarm that indicates a failure of the Return Air Sensor | Read | ||
| BI | 14 | Bad Outdoor Air Sensor | Failure of the Outdoor Air Temperature Sensor | Read | ||
| BI | 15 | Bad Space Temp Sensor | Failure of the Space Temperature Sensor | Read | ||
| BI | 16 | Bad Carbon Dioxide Sensor | Failure of the CO2 Sensor | Read | ||
| BI | 17 | Bad Building Pressure Sensor | Alarm indicating missing or failed Building Pressure Sensor | Read | ||
| BI | 18 | Bad Outdoor Airflow Sensor | An Outdoor Airflow Sensor is configured, but not detected | Read | ||
| BI | 19 | Bad Exhaust Airflow Sensor | An Exhaust Airflow Sensor is configured, but not detected | Read | ||
| BI | 20 | Bad Supply Airflow Sensor | A Supply Airflow Sensor is configured, but not detected | Read | ||
| BI | 21 | Bad Return Airflow Sensor | A Return Airflow Sensor is configured, but not detected | Read | ||
| BI | 22 | Mechanical Cooling Alarm | Compressor Relays are enabled but the Supply Air Temperature has not fallen | Read | ||
| BI | 23 | Mechanical Heating Alarm | Heating Mode has been initiated but the Supply Air Temperature has not | Read | ||
| BI | 24 | Fan Proving Alarm | Alarm that indicates an Airflow failure from the Main Fan | Read | ||
| BI | 25 | Dirty Filter Alarm | Alarm that indicates the filters are dirty | Read | ||
| BI | 26 | Emergency Shutdown Alarm | Alarm that indicates that Emergency Shutdown has been activated | Read | ||
| BI | 27 | Relay Runtime Warning | When any of the configured relays exceeds a configured number of hours | Read | ||
| BI | 28 | Economizer Missing Alarm | Title 24 operation indicates missing economizer feedback | Read | ||
| BI | 29 | Economizer Title 24 Failure A | Title 24 Air Temperature Sensor Failure | Read | ||
| BI | 30 | Economizer Title 24 Failure B | Title 24 Not Economizing when it should | Read | ||
| BI | 31 | Economizer Title 24 Failure C | Title 24 Economizing when it should not | Read | ||
| BI | 32 | Economizer Title 24 Failure D | Title 24 Damper Not Modulating | Read | ||
| BI | 33 | Economizer Title 24 Failure E | Title 24 Excess Outdoor Air | Read | ||
| BI | 34 | High Supply Temp Cutoff | The Supply Air has risen above the Hi SAT Cutoff Setpoint | Read | ||
| BI | 35 | Low Supply Temp Cutoff | The Supply Air has fallen below the Low SAT Cutoff Setpoint | Read | ||
| BI | 36 | High Control Mode Alarm | Occurs when the Controlling Sensor Temperature rises above the Cooling Mode Enable | Read | ||
| BI | 37 | Low Control Mode Alarm | Occurs when the Controlling Sensor Temperature falls below the Heating Mode Enable | Read | ||
| BI | 38 | Missing Refrigerant Module #1 | Refrigerant Module #1 is bad or missing | Read | ||
| BI | 39 | Missing Refrigerant Module #2 | Refrigerant Module #2 is bad or missing | Read | ||
| BI | 40 | Missing Refrigerant Module #3 | Refrigerant Module #3 is bad or missing | Read | ||
| BI | 41 | Missing Refrigerant Module #4 | Refrigerant Module #4 is bad or missing | Read | ||
| BI | 42 | Missing Preheater Board | Preheater Module is bad or missing | Read | ||
| BI | 43 | Missing Reheat Board | The MHGR board is configured but not detected | Read | ||
| BI | 44 | Missing Mod Gas Board | The MODGAS board is configured but not detected | Read | ||
| BI | 45 | Missing EM1 Board | EM1 Expansion Board is bad or missing | Read | ||
| BI | 46 | Missing 12 Relay Expansion Board | The 12 Relay Expansion Board is configured but not detected | Read | ||
| BI | 47 | On Board Relay 1 Main Fan | Current Status of Main Fan Relay #1 on Main Board | Read | ||
| BI | 48 | On Board Relay 2 | Current Status of Configurable Relay #2 on Main Board | Read | ||
| BI | 49 | On Board Relay 3 | Current Status of Configurable Relay #3 on Main Board | Read | ||
| BI | 50 | On Board Relay 4 | Current Status of Configurable Relay #4 on Main Board | Read | ||
| BI | 51 | On Board Relay 5 | Current Status of Configurable Relay #5 on Main Board | Read | ||
| BI | 52 | On Board Relay 6 | Current Status of Configurable Relay #6 on Main Board | Read | ||
| BI | 53 | On Board Relay 7 | Current Status of Configurable Relay #7 on Main Board | Read | ||
| BI | 54 | On Board Relay 8 | Current Status of Configurable Relay #8 on Main Board | Read | ||
| BI | 55 | Expansion Board EM1 Relay 1 | Current Status of Configurable Relay #1 on EM1 Board | Read | ||
| BI | 56 | Expansion Board EM1 Relay 2 | Current Status of Configurable Relay #2 on EM1 Board | Read | ||
| BI | 57 | Expansion Board EM1 Relay 3 | Current Status of Configurable Relay #3 on EM1 Board | Read | ||
| BI | 58 | Expansion Board EM1 Relay 4 | Current Status of Configurable Relay #4 on EM1 Board | Read | ||
| BI | 59 | Expansion Board EM1 Relay 5 | Current Status of Configurable Relay #5 on EM1 Board | Read | ||
| BI | 60 | 12 Relay Expansion Board Relay 1 | Current Status of Configurable Relay #1 on 12 Relay Board | Read | ||
| BI | 61 | 12 Relay Expansion Board Relay 2 | Current Status of Configurable Relay #2 on 12 Relay Board | Read | ||
| BI | 62 | 12 Relay Expansion Board Relay 3 | Current Status of Configurable Relay #3 on 12 Relay Board | Read | ||
| BI | 63 | 12 Relay Expansion Board Relay 4 | Current Status of Configurable Relay #4 on 12 Relay Board | Read | ||
| BI | 64 | 12 Relay Expansion Board Relay 5 | Current Status of Configurable Relay #5 on 12 Relay Board | Read | ||
| BI | 65 | 12 Relay Expansion Board Relay 6 | Current Status of Configurable Relay #6 on 12 Relay Board | Read | ||
| BI | 66 | 12 Relay Expansion Board Relay 7 | Current Status of Configurable Relay #7 on 12 Relay Board | Read | ||
| BI | 67 | 12 Relay Expansion Board Relay 8 | Current Status of Configurable Relay #8 on 12 Relay Board | Read | ||
| BI | 68 | 12 Relay Expansion Board Relay 9 | Current Status of Configurable Relay #9 on 12 Relay Board | Read | ||
| BI | 69 | 12 Relay Expansion Board Relay 10 | Current Status of Configurable Relay #10 on 12 Relay Board | Read | ||
| BI | 70 | 12 Relay Expansion Board Relay 11 | Current Status of Configurable Relay #11 on 12 Relay Board | Read | ||
| BI | 71 | 12 Relay Expansion Board Relay 12 | Current Status of Configurable Relay #12 on 12 Relay Board | Read | ||
| BI | 72 | Preheater Enable Status | Status of Preheater Enable Input | Read | ||
| BI | 73 | Preheater Emergency Shutdown | Status of Preheater Emergency Shutdown Input | Read | ||
| BI | 74 | Preheater Spare Binary Input #3 | Status of Preheater Binary Input #3 | Read | ||
| BI | 75 | MODGAS Enable Status | Status of MODGAS Controller | Read | ||
| BI | 76 | MHGR Enable Status | Status of MHGRV Controller | Read | ||
| BI | 77 | A1 Compressor Enable | Current Status of Enable Signal to Compressor A1 | Read | ||
| BI | 78 | A2 Compressor Enable | Current Status of Enable Signal to Compressor A2 | Read | ||
| BI | 79 | A1 Compressor Alarms | An RSM alarm is present on the A1 circuit | Read | ||
| BI | 80 | A2 Compressor Alarms | An RSM alarm is present on the A2 circuit | Read | ||
| BI | 81 | A1-2 Defrost Switch | Outside Coil A1/A2 Temp Switch for Defrost Mode | Read | ||
| BI | 82 | A1-2 Water Proof of Flow | A1/A2 Water Proof of Flow Switch | Read | ||
| BI | 83 | A1-4 Emergency Shutdown (RSMD) | Emergency Shutdown Input on Module A | Read | ||
| BI | 84 | Refrigerant Module 1 Relay 1 | Current Status of Compressor A1 Enable Relay | Read | ||
| BI | 85 | Refrigerant Module 1 Relay 2 | Current Status of Compressor A2 Enable Relay | Read | ||
| BI | 86 | Refrigerant Module 1 Relay 3 | Current Status of Condenser 1 Enable Relay | Read | ||
| BI | 87 | Refrigerant Module 1 Relay 4 | Current Status of Relay #4 | Read | ||
| BI | 88 | Refrigerant Module 1 Relay 5 | Current Status of Relay #5 | Read | ||
| BI | 89 | B1 Compressor Enable | Current Status of Enable Signal to Compressor B1 | Read | ||
| BI | 90 | B2 Compressor Enable | Current Status of Enable Signal to Compressor B2 | Read | ||
| BI | 91 | B1 Compressor Alarms | An RSM alarm is present on the B1 circuit | Read | ||
| BI | 92 | B2 Compressor Alarms | An RSM alarm is present on the B2 circuit | Read | ||
| BI | 93 | B1-2 Defrost Switch | Outside Coil B1/B2 Temp Switch for Defrost Mode | Read | ||
| BI | 94 | B1-2 Water Proof of Flow | B1/B2 Switch for Water Proof of Flow | Read | ||
| BI | 95 | B1-4 Emergency Shutdown (RSMD) | Emergency Shutdown Input on Module B | Read | ||
| BI | 96 | Refrigerant Module 2 Relay 1 | Current Status of Compressor 1 Enable Relay | Read | ||
| BI | 97 | Refrigerant Module 2 Relay 2 | Current Status of Compressor 2 Enable Relay | Read | ||
| BI | 98 | Refrigerant Module 2 Relay 3 | Current Status of Condenser 1 Enable Relay | Read | ||
| BI | 99 | Refrigerant Module 2 Relay 4 | Current Status of Relay #4 | Read | ||
| BI | 100 | Refrigerant Module 2 Relay 5 | Current Status of Relay #5 | Read | ||
| BI | 101 | C1 Compressor Enable | Current Status of Enable Signal to Compressor C1 | Read | ||
| BI | 102 | C2 Compressor Enable | Current Status of Enable Signal to Compressor C2 | Read | ||
| BI | 103 | C1 Compressor Alarms | An RSM alarm is present on the C1 circuit | Read | ||
| BI | 104 | C2 Compressor Alarms | An RSM alarm is present on the C2 circuit | Read | ||
| BI | 105 | C1-2 Defrost Switch | Outside Coil C1/C2Temp Switch for Defrost Mode | Read | ||
| BI | 106 | C1-2 Water Proof of Flow | C1/C2 Switch for Water Proof of Flow | Read | ||
| BI | 107 | C1-4 Emergency Shutdown (RSMD) | Emergency Shutdown Input on Module C | Read | ||
| BI | 108 | Refrigerant Module 3 Relay 1 | Current Status of Compressor 1 Enable Relay | Read | ||
| BI | 109 | Refrigerant Module 3 Relay 2 | Current Status of Compressor 2 Enable Relay | Read | ||
| BI | 110 | Refrigerant Module 3 Relay 3 | Current Status Condenser 1 Enable Relay | Read | ||
| BI | 111 | Refrigerant Module 3 Relay 4 | Current Status of Relay #4 | Read | ||
| BI | 112 | Refrigerant Module 3 Relay 5 | Current Status of Relay #5 | Read | ||
| BI | 113 | D1 Compressor Enable | Current Status of Enable Signal to Compressor D1 | Read | ||
| BI | 114 | D2 Compressor Enable | Current Status of Enable Signal to Compressor D2 | Read | ||
| BI | 115 | D1 Compressor Alarms | An RSM alarm is present on the D1 circuit | Read | ||
| BI | 116 | D2 Compressor Alarms | An RSM alarm is present on the D2 circuit | Read | ||
| BI | 117 | D1-2 Defrost Switch | Outside Coil D1/D2 Temp Switch for Defrost Mode | Read | ||
| BI | 118 | D1-2 Water Proof of Flow | D1/D2 Switch for Water Proof of Flow | Read | ||
| BI | 119 | D1-4 Emergency Shutdown (RSMD) | Emergency Shutdown Input on Module D | Read | ||
| BI | 120 | Refrigerant Module 4 Relay 1 | Current Status of Compressor 1 Enable Relay | Read | ||
| BI | 121 | Refrigerant Module 4 Relay 2 | Current Status of Compressor 2 Enable Relay | Read | ||
| BI | 122 | Refrigerant Module 4 Relay 3 | Current Status of Condenser 1 Enable Relay | Read | ||
| BI | 123 | Refrigerant Module 4 Relay 4 | Current Status of Relay #4 | Read | ||
| BI | 124 | Refrigerant Module 4 Relay 5 | Current Status of Relay #5 | Read | ||
| BI | 125 | Preheater Alarm | Preheater Alarm Indicator | Read | ||
| BI | 126 | Return Fan Proving Alarm | Exhaust Fan / Return Fan Proof of Flow Alarm | Read | ||
| BI | 127 | Compressor Running A | Current Run Status of Compressor A | Read | ||
| BI | 128 | Compressor Running B | Current Run Status of Compressor B | Read | ||
| BI | 129 | Compressor Running C | Current Run Status of Compressor C | Read | ||
| BI | 130 | Compressor Running C2 | Current Run Status of Compressor C2 | Read | ||
| BI | 131 | Compressor Running D | Current Run Status of Compressor D | Read | ||
| BI | 132 | Compressor Running E | Current Run Status of Compressor E | Read | ||
| BI | 133 | Compressor Running E2 | Current Run Status of Compressor E2 | Read | ||
| BI | 134 | Compressor Running F | Current Run Status of Compressor F | Read | ||
| BI | 135 | Compressor Running F2 | Current Run Status of Compressor F2 | Read | ||
| BI | 136 | Return Fan Proving Status | Proof of Return Fan Airflow Binary Input Status | Read | ||
| BI | 137 | IAQ Mode Active | IAQ Mode is active | Read | ||
| BI | 138 | Heat Wheel Defrost Active | Heat Wheel Defrost is active | Read | ||
| BI | 139 | Direct Fire Status | Signal on EM1 binary input 2 from Direct Fire Module that indicates | Read | ||
| BI | 140 | Direct Fire Alarm Status | Signal on EM1 binary input 3 that indicates there is an active | Read | ||
| BI | 141 | Temp Rise Warning | The heat rise when direct fire heat is active has exceeded | Read | ||
| BI | 142 | Temp Rise Alarm | The heat rise when direct fire heat is active has exceeded | Read | ||
| BI | 143 | Temp Rise Lockout | Three High Temp Rise alarms occurred within a 1-hour span | Read | ||
| BI | 144 | High CO2 Rise Warning | High return CO2 was detected when running direct fire heat | Read | ||
| BI | 145 | High CO2 Rise Alarm | High return CO2 was detected and direct fire heat has been temporarily | Read | ||
| BI | 146 | High CO2 Rise Lockout | Three CO2 warning alarms occurred within a 1-hour span and direct fire | Read | ||
| BI | 147 | Ignition Lockout | An active alarm on the Direct Fire Module | Read | ||
| BI | 148 | Direct Fire Status Lockout | Direct Fire Status Signal is not active within 10 minutes | Read | ||
| BI | 149 | Direct Fire Setpoint Override | The max calculated heat rise is limiting the Supply Air Setpoint | Read |
No points match these filters.
Object ID lookup: AAON VCCX2 Controller point IDs by name
AI1Application Software VersionAI2Control ModeAI3Control StatusAI4HVAC ModeAI5Control TemperatureAI6Mode Cooling SetpointAI7Mode Heating SetpointAI8Sensor Slide Adjust EffectAI9Supply Air TemperatureAI10Supply Air SetpointAI11Controlling Coil Temp SetpointAI12Space TemperatureAI13Space HumidityAI14Return Air TemperatureAI15Return Air HumidityAI16Outdoor Air TemperatureAI17Outdoor Air HumidityAI18Outdoor Air WetbulbAI19Outdoor Air DewpointAI20Supply Air Setpoint Reset VoltageAI21Duct Static PressureAI22Duct Static Control SignalAI23Building PressureAI24Building Pressure Control SignalAI25Outdoor AirflowAI26Supply AirflowAI27Return AirflowAI28Exhaust AirflowAI29Carbon DioxideAI30Desired Economizer PositionAI31Economizer Feedback PositionAI32Return Damper PositionAI33Return Bypass PositionAI34Modulating Cooling PositionAI35Modulating Heat PositionAI36Preheater Leaving Air Temp #1AI37Preheater Leaving Air Temp #2AI38Preheater Entering Air TempAI39Preheater Setpoint Reset VoltageAI40Preheater SCR Output SignalAI41Preheater PWM Output SignalAI42Mod Hot Gas Reheat Valve PositionAI43Mod Gas Heat Valve PositionAI44A1 Compressor SignalAI45A2 Compressor SignalAI46A1 Condenser SignalAI47A2 Condenser SignalAI48A1 Suction PressureAI49A2 Suction PressureAI50A1 Head PressureAI51A2 Head PressureAI52A1 Saturation TemperatureAI53A2 Saturation TemperatureAI54A1 Suction Line TemperatureAI55A2 Suction Line TemperatureAI56A1 Condenser Suction Temp (Heat Pump)AI57A2 Condenser Suction Temp (Heat Pump)AI58A1 Superheat TemperatureAI59A2 Superheat TemperatureAI60Condenser A1 Superheat (Heat Pump)AI61Condenser A2 Superheat (Heat Pump)AI62A1 Expansion Valve PositionAI63A2 Expansion Valve PositionAI64Condenser A1 Expansion Valve PositionAI65Condenser A2 Expansion Valve PositionAI66A1 Discharge TemperatureAI67A2 Discharge TemperatureAI68A1 Leaving Water TempAI69B1 Compressor SignalAI70B2 Compressor SignalAI71B1 Condenser SignalAI72B2 Condenser SignalAI73B1 Suction PressureAI74B2 Suction PressureAI75B1 Head PressureAI76B2 Head PressureAI77B1 Saturation TemperatureAI78B2 Saturation TemperatureAI79B1 Suction Line TemperatureAI80B2 Suction Line TemperatureAI81B1 Condenser Suction Temp (Heat Pump)AI82B2 Condenser Suction Temp (Heat Pump)AI83B1 Superheat TemperatureAI84B2 Superheat TemperatureAI85Condenser B1 Superheat (Heat Pump)AI86Condenser B2 Superheat (Heat Pump)AI87B1 Expansion Valve PositionAI88B2 Expansion Valve PositionAI89Condenser B1 Expansion Valve PositionAI90Condenser B2 Expansion Valve PositionAI91B1 Discharge TemperatureAI92B2 Discharge TemperatureAI93B1 Leaving Water TempAI94C1 Compressor SignalAI95C2 Compressor SignalAI96C1 Condenser SignalAI97C2 Condenser SignalAI98C1 Suction PressureAI99C2 Suction PressureAI100C1 Head PressureAI101C2 Head PressureAI102C1 Saturation TemperatureAI103C2 Saturation TemperatureAI104C1 Suction Line TemperatureAI105C2 Suction Line TemperatureAI106C1 Condenser Suction Temp (Heat Pump)AI107C2 Condenser Suction Temp (Heat Pump)AI108C1 Superheat TemperatureAI109C2 Superheat TemperatureAI110Condenser C1 Superheat (Heat Pump)AI111Condenser C2 Superheat (Heat Pump)AI112C1 Expansion Valve PositionAI113C2 Expansion Valve PositionAI114Condenser C1 Expansion Valve PositionAI115Condenser C2 Expansion Valve PositionAI116C1 Discharge TemperatureAI117C2 Discharge TemperatureAI118C1 Leaving Water TempAI119D1 Compressor SignalAI120D2 Compressor SignalAI121D1 Condenser SignalAI122D2 Condenser SignalAI123D1 Suction PressureAI124D2 Suction PressureAI125D1 Head PressureAI126D2 Head PressureAI127D1 Saturation TemperatureAI128D2 Saturation TemperatureAI129D1 Suction Line TemperatureAI130D2 Suction Line TemperatureAI131D1 Condenser Suction Temp (Heat Pump)AI132D2 Condenser Suction Temp (Heat Pump)AI133D1 Superheat TemperatureAI134D2 Superheat TemperatureAI135Condenser D1 Superheat (Heat Pump)AI136Condenser D2 Superheat (Heat Pump)AI137D1 Expansion Valve PositionAI138D2 Expansion Valve PositionAI139Condenser D1 Expansion Valve PositionAI140Condenser D2 Expansion Valve PositionAI141D1 Discharge TemperatureAI142D2 Discharge TemperatureAI143D1 Leaving Water TempAI144Alarm StatusAI145Outdoor EnthalpyAI146Plenum PressureAI147Return Fan SpeedAI148Plenum Calculated SetpointAI149Return Air Enthalpy StatusAI150Current Duct Static SetpointAI151RSMZ 1 Condenser FanAI152RSMZ 1 VFD Comp PercAI153RSMZ 1 Discharge PressureAI154RSMZ 1 Suction PressureAI155RSMZ 1 Suction Line TempAI156RSMZ 1 Saturation TempAI157RSMZ 1 SuperheatAI158RSMZ 1 EEV PositionAI159RSMZ 1 WarningsAI160RSMZ 1 Comp VFD Alarms 1AI161RSMZ 1 Comp VFD Alarms 2AI162RSMZ 1 Comp VFD Drive StatusAI163RSMZ 1 Compressor CurrentAI164RSMZ 1 Discharge Line TempAI165RSMZ 1 FaultsAI166RSMZ 1 LockoutsAI167RSMZ 2 Condenser FanAI168RSMZ 2 VFD Comp PercAI169RSMZ 2 Discharge PressureAI170RSMZ 2 Suction PressureAI171RSMZ 2 Suction Line TempAI172RSMZ 2 Saturation TempAI173RSMZ 2 SuperheatAI174RSMZ 2 EEV PositionAI175RSMZ 2 WarningsAI176RSMZ 2 Comp VFD Alarms 1AI177RSMZ 2 Comp VFD Alarms 2AI178RSMZ 2 Comp VFD Drive StatusAI179RSMZ 2 Compressor CurrentAI180RSMZ 2 Discharge Line TempAI181RSMZ 2 FaultsAI182RSMZ 2 LockoutsAI183RSMZ 3 Condenser FanAI184RSMZ 3 Reheat Valve 1AI185RSMZ 3 Discharge PressureAI186RSMZ 3 Suction PressureAI187RSMZ 3 Suction Line TempAI188RSMZ 3 Saturation TempAI189RSMZ 3 SuperheatAI190RSMZ 3 EEV PositionAI191RSMZ 3 Suction Pressure 2AI192RSMZ 3 Suction Line Temp 2AI193RSMZ 3 Saturation Temp 2AI194RSMZ 3 Superheat 2AI195RSMZ 3 EEV Position 2AI196RSMZ 3 WarningsAI197RSMZ 3 Discharge Line TempAI198RSMZ 3 FaultsAI199RSMZ 3 LockoutsAI200RSMZ 4 Condenser FanAI201RSMZ 4 VFD Comp PercAI202RSMZ 4 Discharge PressureAI203RSMZ 4 Suction PressureAI204RSMZ 4 Suction Line TempAI205RSMZ 4 Saturation TempAI206RSMZ 4 SuperheatAI207RSMZ 4 EEV PositionAI208RSMZ 4 WarningsAI209RSMZ 4 Comp VFD Alarms 1AI210RSMZ 4 Comp VFD Alarms 2AI211RSMZ 4 Comp VFD Drive StatusAI212RSMZ 4 Comp VFD Compressor CurrentAI213RSMZ 4 Discharge Line TempAI214RSMZ 4 FaultsAI215RSMZ 4 LockoutsAI216RSMZ 5 Condenser FanAI217RSMZ 5 VFD Comp PercAI218RSMZ 5 Discharge PressureAI219RSMZ 5 Suction PressureAI220RSMZ 5 Suction Line TempAI221RSMZ 5 Saturation TempAI222RSMZ 5 SuperheatAI223RSMZ 5 EEV PositionAI224RSMZ 5 WarningsAI225RSMZ 5 Comp VFD Alarms 1AI226RSMZ 5 Comp Alarms 2AI227RSMZ 5 Comp VFD Drive StatusAI228RSMZ 5 Compressor CurrentAI229RSMZ 5 Discharge Line TempAI230RSMZ 5 FaultsAI231RSMZ 5 LockoutsAI232RSMZ 6 Condenser FanAI233RSMZ 6 Reheat Valve 1AI234RSMZ 6 Discharge PressureAI235RSMZ 6 Suction PressureAI236RSMZ 6 Suction Line TempAI237RSMZ 6 Saturation TempAI238RSMZ 6 SuperheatAI239RSMZ 6 EEV PositionAI240RSMZ 6 Suction Pressure 2AI241RSMZ 6 Suction Line Temp 2AI242RSMZ 6 Saturation Temp 2AI243RSMZ 6 Superheat 2AI244RSMZ 6 EEV Position 2AI245RSMZ 6 WarningsAI246RSMZ 6 Discharge Line TempAI247RSMZ 6 FaultsAI248RSMZ 6 LockoutsAI249Not usedAI250Not usedAI251Not usedAI252Not usedAI253SUB 1 Sub Cool 1AI254SUB 1 Sub Cool 2AI255SUB 1 Sub Cool 3AI256SUB 1 Pressure 1AI257SUB 1 Pressure 2AI258SUB 1 Pressure 3AI259SUB 1 Saturation 1AI260SUB 1 Saturation 2AI261SUB 1 Saturation 3AI262SUB 1 Line Temp 1AI263SUB 1 Line Temp 2AI264SUB 1 Line Temp 3AI265SUB 2 Sub Cool 1AI266SUB 2 Sub Cool 2AI267SUB 2 Sub Cool 3AI268SUB 2 Pressure 1AI269SUB 2 Pressure 2AI270SUB 2 Pressure 3AI271SUB 2 Saturation 1AI272SUB 2 Saturation 2AI273SUB 2 Saturation 3AI274SUB 2 Line Temp 1AI275SUB 2 Line Temp 2AI276SUB 2 Line Temp 3AI277Enter Water PumpAI278Return Plenum Pressure StatusAI279Return Plenum Control SignalAI280Mixed Air TempAI281Actual Heat RiseAI282Calculated Heat RiseAI283Supply Air Relative HumidityAI284Supply Air Dew PointAI285Space Dew PointAI286Return Dew PointAV1Occupied Cooling SetpointAV2Occupied Heating SetpointAV3Hood On Cooling SetpointAV4Hood On Heating SetpointAV5Unoccupied Cooling OffsetAV6Unoccupied Heating OffsetAV7Mode Select DeadbandAV8Max Coil Setpoint Reset LimitAV9Min Coil Setpoint Reset LimitAV10Supply Air Cooling SetpointAV11Supply Air Heating SetpointAV12Max SAT Cooling Setpoint Reset LimitAV13Max SAT Heating Setpoint Reset LimitAV14Supply Air Cooling Staging WindowAV15Supply Air Heating Staging WindowAV16Warm-Up Target TemperatureAV17Warm-Up Mode Supply Air SetpointAV18Cool-Down Mode Supply Air SetpointAV19Mechanical Cooling Outdoor Air LockoutAV20Mechanical Heating Outdoor Air LockoutAV21Low Supply Temp Cutoff AlarmAV22High Supply Temp Cutoff AlarmAV23Preheater Cooling Mode SetpointAV24Preheater Venting Mode SetpointAV25Preheater Heating Mode SetpointAV26Outdoor Air Dewpoint SetpointAV27Economizer Enable SetpointAV28Heat Wheel Defrost Enable SetpointAV29PreHeat Enable SetpointAV30Sensor Slide Offset Max EffectAV31Space Sensor Calibration OffsetAV32Supply Air Sensor Calibration OffsetAV33Return Air Sensor Calibration OffsetAV34Outdoor Air Sensor Calibration OffsetAV35Carbon Dioxide Sensor Calibration OffsetAV36Low Ambient Protection SetpointAV37SAT Cool Setpoint Reset Source Low LimitAV38SAT Cool Setpoint Reset Source High LimitAV39SAT Heat Setpoint Reset Source Low LimitAV40SAT Heat Setpoint Reset Source High LimitAV41Control Temperature High Alarm OffsetAV42Control Temperature Low Alarm OffsetAV43Heat Pump Compressor Heat LockoutAV44Maximum Main Fan VFD in SZ VAV Heating ModeAV45Minimum Main Fan VFD in Cooling ModeAV46Minimum Main Fan VFD in Heating ModeAV47Minimum Main Fan VFD in Vent ModeAV48Maximum Economizer in Heating ModeAV49Minimum Economizer PositionAV50Maximum Economizer CO2 Reset LimitAV51Minimum Carbon Dioxide SetpointAV52Maximum Carbon Dioxide SetpointAV53Indoor Humidity Setpoint Low Reset LimitAV54Indoor Humidity Setpoint High Reset LimitAV55Duct Static Pressure SetpointAV56Duct Static Pressure Control DeadbandAV57Building Pressure Control SetpointAV58Building Pressure Control DeadbandAV59Minimum Outdoor CFM RequirementAV60Outdoor CFM Control DeadbandAV61Single Zone VAV Fan Speed IntegralAV62Relay Run-time Hours Warning LimitAV63Cooling Mode Head Pressure SetpointAV64Dehum Mode Head Pressure SetpointAV65Superheat SetpointAV66Maximum Outdoor CFM RequirementAV67Schedule ForceAV68HVAC Mode OverrideAV69Fan VFD OverrideAV70Outdoor Air Damper OverrideAV71Supply Setpoint OverrideAV72Space Temperature ValueAV73Space Humidity ValueAV74Indoor RH Calibration OffsetAV75Relief Fan VFDAV76Relief Pressure ValueAV77Carbon Dioxide ValueAV78Outdoor Air Temperature ValueAV79Outdoor Air Humidity ValueAV80High Level Enthalpy (Reserved)AV81Low Level Enthalpy (Reserved)AV82Max Plenum Pressure Setpoint Reset LimitAV83Min Plenum Pressure Setpoint Reset LimitAV84Enthalpy Enable SetpointAV85EnthalpyEnable DeadbandAV86Maximum Static Setpoint Reset LimitAV87Minimum Static Setpoint Reset LimitAV88Static Setpoint Reset IntervalAV89Cool-Down Target TemperatureAV90Warm-Up OverrideAV91Cool Down OverrideAV92Return Air High Limit ProtectionAV93Return Air Low Limit ProtectionAV94Sump Drain OverrideAV95Return Plenum Pressure SetpointAV96Return Plenum Pressure DeadbandAV97Dehum Lockout SetpointAV98Emergency Compressor LockoutAV99Supply Air Dew Point SetpointBI1Cooling Enabled StatusBI2Heating Enabled StatusBI3Economizer Enabled StatusBI4Aux Heat Enabled StatusBI5Emergency Heat Enabled StatusBI6Fan Proof of Airflow StatusBI7Exhaust Hood On/Off StatusBI8Remote Forced Occupied StatusBI9Remote Forced Cooling StatusBI10Remote Forced Heating StatusBI11Remote Force Dehum StatusBI12Bad Supply Air SensorBI13Bad Return Air SensorBI14Bad Outdoor Air SensorBI15Bad Space Temp SensorBI16Bad Carbon Dioxide SensorBI17Bad Building Pressure SensorBI18Bad Outdoor Airflow SensorBI19Bad Exhaust Airflow SensorBI20Bad Supply Airflow SensorBI21Bad Return Airflow SensorBI22Mechanical Cooling AlarmBI23Mechanical Heating AlarmBI24Fan Proving AlarmBI25Dirty Filter AlarmBI26Emergency Shutdown AlarmBI27Relay Runtime WarningBI28Economizer Missing AlarmBI29Economizer Title 24 Failure ABI30Economizer Title 24 Failure BBI31Economizer Title 24 Failure CBI32Economizer Title 24 Failure DBI33Economizer Title 24 Failure EBI34High Supply Temp CutoffBI35Low Supply Temp CutoffBI36High Control Mode AlarmBI37Low Control Mode AlarmBI38Missing Refrigerant Module #1BI39Missing Refrigerant Module #2BI40Missing Refrigerant Module #3BI41Missing Refrigerant Module #4BI42Missing Preheater BoardBI43Missing Reheat BoardBI44Missing Mod Gas BoardBI45Missing EM1 BoardBI46Missing 12 Relay Expansion BoardBI47On Board Relay 1 Main FanBI48On Board Relay 2BI49On Board Relay 3BI50On Board Relay 4BI51On Board Relay 5BI52On Board Relay 6BI53On Board Relay 7BI54On Board Relay 8BI55Expansion Board EM1 Relay 1BI56Expansion Board EM1 Relay 2BI57Expansion Board EM1 Relay 3BI58Expansion Board EM1 Relay 4BI59Expansion Board EM1 Relay 5BI6012 Relay Expansion Board Relay 1BI6112 Relay Expansion Board Relay 2BI6212 Relay Expansion Board Relay 3BI6312 Relay Expansion Board Relay 4BI6412 Relay Expansion Board Relay 5BI6512 Relay Expansion Board Relay 6BI6612 Relay Expansion Board Relay 7BI6712 Relay Expansion Board Relay 8BI6812 Relay Expansion Board Relay 9BI6912 Relay Expansion Board Relay 10BI7012 Relay Expansion Board Relay 11BI7112 Relay Expansion Board Relay 12BI72Preheater Enable StatusBI73Preheater Emergency ShutdownBI74Preheater Spare Binary Input #3BI75MODGAS Enable StatusBI76MHGR Enable StatusBI77A1 Compressor EnableBI78A2 Compressor EnableBI79A1 Compressor AlarmsBI80A2 Compressor AlarmsBI81A1-2 Defrost SwitchBI82A1-2 Water Proof of FlowBI83A1-4 Emergency Shutdown (RSMD)BI84Refrigerant Module 1 Relay 1BI85Refrigerant Module 1 Relay 2BI86Refrigerant Module 1 Relay 3BI87Refrigerant Module 1 Relay 4BI88Refrigerant Module 1 Relay 5BI89B1 Compressor EnableBI90B2 Compressor EnableBI91B1 Compressor AlarmsBI92B2 Compressor AlarmsBI93B1-2 Defrost SwitchBI94B1-2 Water Proof of FlowBI95B1-4 Emergency Shutdown (RSMD)BI96Refrigerant Module 2 Relay 1BI97Refrigerant Module 2 Relay 2BI98Refrigerant Module 2 Relay 3BI99Refrigerant Module 2 Relay 4BI100Refrigerant Module 2 Relay 5BI101C1 Compressor EnableBI102C2 Compressor EnableBI103C1 Compressor AlarmsBI104C2 Compressor AlarmsBI105C1-2 Defrost SwitchBI106C1-2 Water Proof of FlowBI107C1-4 Emergency Shutdown (RSMD)BI108Refrigerant Module 3 Relay 1BI109Refrigerant Module 3 Relay 2BI110Refrigerant Module 3 Relay 3BI111Refrigerant Module 3 Relay 4BI112Refrigerant Module 3 Relay 5BI113D1 Compressor EnableBI114D2 Compressor EnableBI115D1 Compressor AlarmsBI116D2 Compressor AlarmsBI117D1-2 Defrost SwitchBI118D1-2 Water Proof of FlowBI119D1-4 Emergency Shutdown (RSMD)BI120Refrigerant Module 4 Relay 1BI121Refrigerant Module 4 Relay 2BI122Refrigerant Module 4 Relay 3BI123Refrigerant Module 4 Relay 4BI124Refrigerant Module 4 Relay 5BI125Preheater AlarmBI126Return Fan Proving AlarmBI127Compressor Running ABI128Compressor Running BBI129Compressor Running CBI130Compressor Running C2BI131Compressor Running DBI132Compressor Running EBI133Compressor Running E2BI134Compressor Running FBI135Compressor Running F2BI136Return Fan Proving StatusBI137IAQ Mode ActiveBI138Heat Wheel Defrost ActiveBI139Direct Fire StatusBI140Direct Fire Alarm StatusBI141Temp Rise WarningBI142Temp Rise AlarmBI143Temp Rise LockoutBI144High CO2 Rise WarningBI145High CO2 Rise AlarmBI146High CO2 Rise LockoutBI147Ignition LockoutBI148Direct Fire Status LockoutBI149Direct Fire Setpoint Override
Integration notes
- AI objects are read-only and AV objects are read/write; of the sensor values, only AV 72, 73 and 76-79 may be written by the BAS.
- Points for refrigerant modules (RSMV/RSMD/RSMZ), preheater, MODGAS, MHGRV and expansion boards only report data when that hardware is installed.
- AI 159-248 RSMZ warning, fault, lockout and VFD status points are bit strings; the bit meanings are in the guide's Bitfields tables.
- Units are not printed for analog inputs; analog value units shown here come from the guide's min/max limits.
- MAC address, device ID and baud rate are set from the controller's LCD BACnet screens.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VCCX2 Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the AAON VCCX2 Controller
How many BACnet points does the AAON VCCX2 Controller have?
This list has 534 BACnet objects: 286 analog inputs, 99 analog values, 149 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which AAON VCCX2 Controller BACnet points are writable?
99 of the 534 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official AAON VCCX2 Controller BACnet documentation?
The source is VCCX2 Controller Technical Guide (Appendix C: BACnet Guide) (G115820), revision Rev. AA, January 7, 2025, published free by AAON at https://www.aaon.com/hubfs/G039840-VCCX2-T.pdf.
What are the minimum BACnet points to integrate the AAON VCCX2 Controller?
Start with AV 67 Schedule Force (Occupied/unoccupied command from the BAS); AV 1 Occupied Cooling Setpoint (Cooling starts one deadband above this, °F); AV 2 Occupied Heating Setpoint (Heating starts one deadband below this, °F); AV 10 Supply Air Cooling Setpoint (Discharge air temp target in cooling, °F); AI 3 Control Status (Current occupancy status); AI 4 HVAC Mode (Off, vent, cool, heat, dehum, purge or defrost mode); AI 5 Control Temperature (Reading from the configured control sensor); AI 9 Supply Air Temperature (Discharge air temp leaving the unit); AI 144 Alarm Status (Summary alarm).
How do I enable BMS control of the AAON VCCX2 Controller?
Occupancy comes from AV 67 Schedule Force (0 = follow the controller schedule, 1 = forced occupied, 2 = forced unoccupied), the internal week schedule, a GPC-XP broadcast schedule, or the BI4 remote forced occupied contact. AV 68, AV 69, AV 70 and AV 71 override HVAC mode, fan VFD, OA damper and supply setpoint; writing Auto (0 or 65535 as listed) hands control back.
Can the BMS supply sensor values to the AAON VCCX2 Controller?
If the controller is configured for it, the BAS can write AV 72 Space Temperature, AV 73 Space Humidity, AV 76 Relief Pressure, AV 77 CO2, AV 78 Outdoor Air Temperature and AV 79 Outdoor Air Humidity; these are the only sensor values the BAS may write. The guide gives no refresh timeout for them. A relief pressure value received over BACnet that is out of range raises an alarm.
How do I check these points on the real VCCX2 Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More AAON BACnet points lists
- Rooftop unit / air handler controller
AAON Touchscreen Controller
AAON packaged units fitted with the AAON Touchscreen unit controller.
Also known as: AAON Touchscreen, Touch Screen Controller, AAON TS controller - Rooftop unit controller (zoning)
AAON Auto-Zone 3 (AZ 3) Controller
AAON packaged units run by the Auto-Zone 3 controller, alone or with AZ 3 VAV/zone dampers.
Also known as: AZ 3, AZ3, Auto-Zone 3, AAON AZ3, G071000, SS8014, SS8015, Orion AZ3 - General-purpose BACnet I/O controller
AAON BACnet General Controller (BGC)
AAON BGC general-purpose controller with 8 analog inputs, 8 binary inputs, 8 relays and 4 analog outputs.
Also known as: AAON BGC, BGC Controller, AAON BACnet General Controller, G042460, AAON general purpose I/O controller - DX chiller controller
AAON DX Chiller Controller
AAON packaged DX chillers (non-Turbocor compressors) with the Main DX Chiller Controller, refrigerant modules and optional waterside economizer and evaporative condenser modules.
Also known as: AAON DX Chiller Controller, Main DX Chiller Controller, G054280, SS1149, AAON DX chiller BACnet - DX chiller controller
AAON LF Chiller Controller
AAON LF series one- or two-circuit DX chillers with the LF Chiller Main Controller, optional pumping package and waterside economizer.
Also known as: AAON LF Chiller, LF Chiller Main Controller, G059100, SS1131, DT005683-001, LF chiller BACnet - DX chiller controller
AAON Main DX Barrel Chiller Controller
AAON DX barrel chillers with the Main DX Barrel Chiller Controller, up to two barrels and three refrigerant circuits per barrel, with optional pumping, WSE, evaporative condenser and vestibule modules.
Also known as: AAON DX Barrel Chiller, Main DX Barrel Chiller Controller, G070300, SS1140, DX barrel chiller BACnet - Air handler preheat controller
AAON PREHEAT-X Controller
AAON PREHEAT-X controllers that stage and modulate electric (SCR/SSR) preheat on AAON units and air handlers.
Also known as: PREHEAT-X, PREHEATX, Preheat-X, G086640, AAON preheat controller, Orion PREHEAT-X - Rooftop unit / air handler controller (gateway)
AAON SA Controller (via PT-Link II BACnet gateway)
AAON units with the SA (single-zone) controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: SA controller, AAON SA, PT-Link II, PT-Link BACnet5, G114680 - Rooftop unit / air handler controller
AAON Stratus Unit Manager (Stratus controls)
AAON units built with Stratus controls (Stratus Unit Manager, software 1.3.3).
Also known as: Stratus, AAON Stratus, Stratus Unit Manager, Stratus BACnet Points Guide, Stratus controller, Stratus Series - VAV / zone controller
AAON VAV/Zone BACnet Controller (VAVZB)
Pressure-independent and pressure-dependent VAV boxes and zone dampers controlled by the AAON VAV/Zone BACnet controller.
Also known as: VAVZB, VAV/Zone Controller, ASM02426, ASM02427, ASM02661, ASM02662, SS1116, SS1146, G067750 - Rooftop unit / air handler controller
AAON VCB-X Controller
AAON packaged rooftop units, air handlers, DOAS and water-source units controlled by the Orion VCB-X (OE335-26B-VCBX) unit controller.
Also known as: VCBX, VCB-X, Orion VCB-X, OE335-26B-VCBX, V28940, WattMaster VCB-X, AAON VCB-X BACnet - Rooftop unit / air handler controller
AAON VCCX-454 Controller
AAON rooftop units, air handlers, DOAS and self-contained units built for R-454B and controlled by the VCCX-454 unit controller with RM454 refrigerant modules.
Also known as: VCCX-454, VCCX 454, ASM07503, SS1188, AAON VCCX-454 controller, R-454B unit controller - Rooftop unit / air handler controller
AAON VCCX-454-GH Controller (grow house)
AAON R-454B units for indoor agriculture (grow rooms) controlled by the VCCX-454-GH controller.
Also known as: VCCX-454-GH, VCCX454-GH, ASM07792, SS1207, AAON grow house controller, indoor agriculture HVAC controller - Rooftop unit / air handler controller (gateway)
AAON VCM Controller (legacy, via PT-Link II BACnet gateway)
Older AAON units with the legacy VCM controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: VCM, AAON VCM, PT-Link II, PT-Link BACnet5, G114680 - Rooftop unit / air handler controller (gateway)
AAON VCM-X Controller (via PT-Link II BACnet gateway)
AAON rooftop units, air handlers and other equipment with the VCM-X controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: VCM-X, VCMX, PT-Link II, PT-Link BACnet5, G114680
Source: VCCX2 Controller Technical Guide (Appendix C: BACnet Guide) · G115820 · rev. Rev. AA, January 7, 2025. Object names, instances and units are reproduced as published; descriptions are our own.